ATCP 78.22(1)(e)2.
2. Each container shall be thoroughly cleaned on
the
inside
and
outside
in
a
way
that
does
not
contaminate food, equipment, utensils or food preparation areas.
ATCP 78.22(2)(a)1.1. Garbage and refuse stored inside shall be stored in a manner to make the garbage and refuse inaccessible to pests.
ATCP 78.22(2)(a)2.
2. Outside storage of unprotected plastic bags or wet-strength paper
bags
or
baled
units
containing
garbage
or
refuse
is prohibited.
ATCP 78.22(2)(a)3.
3. Cardboard or other packaging material not containing garbage or
food
wastes
need
not
be
stored
in
covered
containers.
ATCP 78.22(2)(b)
(b)
Storage room design. Garbage or refuse storage rooms, if used, shall be constructed of
easily
cleanable,
nonabsorbent
materials,
shall
be
kept clean, shall be pest-proof and shall be large enough to
store
all the
garbage
and
refuse
containers.
ATCP 78.22(2)(c)
(c)
Outdoor storage capacity. Outdoor storage areas or enclosures shall meet all of the following:
ATCP 78.22(2)(d)
(d)
Recyclable and
returnable items. Shall
be
stored
in
a
clean
and sanitary manner to prevent pest attraction.
ATCP 78.22(3)(a)(a)
Frequency. Garbage and refuse shall be disposed of often enough to prevent odor and attracting pests.
ATCP 78.22(3)(b)
(b)
Wisconsin department of natural resources compliance. Solid waste disposal, including composting, on the premises shall comply with chs.
NR 500 to
538, as enforced by the Wisconsin department of natural resources.
ATCP 78.22 History
History: CR 21-109: cr.
Register June 2023 No. 810, eff. 9-24-23.
ATCP 78.23
ATCP 78.23
Food preparation and service. ATCP 78.23(1)(1)
Standards. The preparation and service of food and the equipment used for that purpose at camp dining halls, commissary operations, concession stands and outdoor food service operations shall comply with ch.
ATCP 75
Appendix.
ATCP 78.23(2)
(2)
Knowledge of food protection practices. The
operator
or
at
least
one
manager of
the
food
service
facility
at
each
camp
shall
have
a certified food protection manager in compliance with the requirements of chapter 12 of the ch.
ATCP 75 Appendix.
ATCP 78.23(3)
(3)
Use of food facilities. When a rental group uses a
camp's food service facilities and the camp operator does not provide staffing, the operator, in consultation with the person certified pursuant to
sub.
(2),
shall
provide
the
group
with
written
or
video-presented
procedures to be followed
for
the
safe
handling
of
food,
personal
hygiene, and proper washing and sanitizing of utensils and equipment.
ATCP 78.23(4)
(4)
Outdoor food service. Outdoor food service at camps shall meet all of the following requirements:
ATCP 78.23(4)(c)
(c) Restrict campers from using campfires, camp stoves, or flammable liquids until campers are provided with adequate instruction on their proper use and care and supervised until competency is demonstrated.
Pf
ATCP 78.23 History
History: CR 21-109: cr.
Register June 2023 No. 810, eff. 9-24-23; (4) (a) title repealed under s. 13.92 (4) (b) 2., Stats., and correction in numbering of (4) (a) to (c) under s. 13.92 (4) (b) 1., Stats.,
Register June 2023 No. 810.
ATCP 78.24(1)(1)
Wisconsin building code. Except as specified in this section, all
buildings
at
a camp shall comply with applicable Wisconsin department of safety and professional services standards as enforced by the Wisconsin department of safety and professional services.
ATCP 78.24(2)
(2)
Handrails, guards and stairs. Except as provided in par.
(d), handrails and guards shall be provided as follows:
ATCP 78.24(2)(a)
(a)
Handrails. A flight of stairs with more than 3 risers shall be provided with at least one handrail with a height of 30 to 38 inches above the step for the full length of the flight.
Pf
ATCP 78.24(2)(b)1.a.a. Guards shall be provided on all open sides of stairs consisting of more than 3 risers,
Pf and
ATCP 78.24(2)(b)1.b.
b. All elevated surfaces in interior and exterior structures shall be provided with guards on all open sides that are elevated more than 24 inches above the floor or grade,
Pf including lofts, open sides of landings, platforms, decks, balconies or porches.
ATCP 78.24(2)(b)2.
2. The guard height shall extend to at least 36 inches above the floor or to the underside of a stair handrail.
Pf
ATCP 78.24(2)(b)3.
3. Except as specified in subd.
4., a guard shall not have openings that allow passage of a sphere not less than 4 3/8 inches in diameter.
Pf
ATCP 78.24(2)(b)4.
4. A rope, cable, or similar material used in guard infill shall not have openings that allow passage of a sphere 3 and a half inches in diameter with vertical supports a maximum of 4 feet apart.
Pf
ATCP 78.24(2)(c)1.1. The triangular openings at the open sides of a stair, formed by the riser, tread and bottom rail shall not have openings that allow passage of a sphere 6 inches in diameter.
ATCP 78.24(2)(c)2.
2. Stairs with open risers shall not exceed more than 4 inches in height.
ATCP 78.24(2)(d)
(d)
Exemptions. This section, does not apply to window wells, egress wells, retaining walls, other landscaping features or detached walkways or stairs that are not part of the building structure.
ATCP 78.24(3)(a)1.1. Doors must be arranged to be opened from the occupant's side whenever the building is occupied.
ATCP 78.24(3)(a)2.
2. A latch or other fastening device on a door must be provided with a knob, panic bar, or other simple type of releasing device having a method of operation that is obvious under all lighting conditions.
ATCP 78.24(3)(b)
(b)
Exit signage. All exits and access ways in a public building or place of employment must be marked by an approved sign visible from any direction of exit access as enforced by the Wisconsin department of safety and professional services.
ATCP 78.24(4)(a)1.1. The walls, ceiling, floors and equipment in buildings shall be maintained in a clean condition and in good repair.
ATCP 78.24(4)(a)2.
2. Hot water pipes, steam radiators, fireplaces and permanently installed space heaters and registers shall be shielded, screened or otherwise equipped to protect campers from burns.
P
ATCP 78.24(4)(b)1.1. Roofs, exterior walls, doors and windows shall be maintained in good repair.
ATCP 78.24(4)(b)2.
2. Openings to the outside shall be protected from the entrance of pests.
ATCP 78.24(4)(c)
(c)
Grounds. The premises shall be maintained in a clean condition free from refuse and pests.
ATCP 78.24(4)(d)
(d)
Parking and roadways. Parking
areas and roadways
shall
be
maintained
to minimize dust and
dirt.
ATCP 78.24(5)
(5)
Lighting. All rooms shall be illuminated to permit cleaning and
maintenance.
ATCP 78.24(6)(a)1.1. Effective measures to minimize the presence of pests shall be utilized.
ATCP 78.24(6)(a)3.
3. Pest control measures shall be applied
according
to label
instructions.
P
ATCP 78.24(7)(a)(a)
Use. Chemicals, flammable materials and other hazardous substances shall be used for their intended purpose and according to the manufacturer's directions stated on the container label.
P
ATCP 78.24(7)(b)1.1. Chemicals and other hazardous substances shall
meet all of the following:
ATCP 78.24(7)(b)2.
2. Hazardous substances shall be stored in easily identifiable or labeled containers when removed from the storage area for use.
P
ATCP 78.24(7)(c)
(c)
Disposal. Hazardous substances shall be disposed of in a manner and
location
as
directed
on
the
manufacturer's
label
or
the safety
data
sheet
by
the
local
agency
having
jurisdiction over
handling
hazardous
substances
and
the
applicable
sections
of chs.
NR 660 to
670, as enforced by the Wisconsin department of natural resources.
Pf
ATCP 78.24(8)(a)(a)
Written notification of intent to operate. Local fire fighting and law enforcement officials shall be notified in writing when the camp is planning to be in operation or annually if the camp is open year-round.
Pf
ATCP 78.24 Note
Note: Camps should invite local fire and law enforcement to the camp, so they are familiar with the camp road systems and building structures.
ATCP 78.24(8)(b)
(b)
Fire extinguisher location. A fire extinguisher shall be located in all public buildings or places of employment according to the local fire official.
ATCP 78.24(8)(c)
(c)
Fire extinguisher maintenance. Annual maintenance shall be performed and then recorded on a tag or label attached to each fire extinguisher that indicates the month and year the maintenance was performed, the initials of the person performing the service and the name of the company performing the service.
Pf
ATCP 78.24(8)(d)
(d)
Smoke detectors. The operator shall install and maintain smoke detectors in compliance with the requirements of s.
101.145, Stats.
P
ATCP 78.24(8)(e)
(e)
Fire alarm and detection systems. When required, the operator shall install and maintain a fire alarm system in compliance with ss.
SPS 362.0907 and
314.13, as required and enforced by the Wisconsin department of safety and professional services and shall meet all of the following:
ATCP 78.24(8)(e)1.a.a. The fire alarm system shall be operational at all times that the building is occupied.
P
ATCP 78.24(8)(e)1.b.
b. A camp operator shall immediately notify the fire alarm technician or other fire inspection or testing personnel in response to any illuminated indicator for alarm, trouble or supervisory notifications on the fire alarm panel.
ATCP 78.24(8)(e)2.
2. The camp operator shall maintain documentation that verifies the fire alarm system has been inspected and tested annually by a fire alarm system service company.
Pf
ATCP 78.24(8)(e)3.
3. Documentation required in subd.
2. shall be provided to the department or its agent upon request.
Pf
ATCP 78.24 Note
Note: Documentation can include the fire alarm and emergency communication system inspection and testing form provided by the service company or the fire inspection report provided by the local fire department.
ATCP 78.24(8)(f)
(f)
Building evacuation diagrams. Building evacuation diagrams shall be prepared and posted in all buildings that have 2 or more exit doors to the outside, and shall comply with all of the following: