This is the preview version of the Wisconsin State Legislature site.
Please see http://docs.legis.wisconsin.gov for the production version.
NR 440.76(13)(h)5.d.d. Load level of the municipal waste combustion unit.
NR 440.76(13)(h)5.e.e. Temperature of the flue gases at the inlet of the particulate matter air pollution control device.
NR 440.76(13)(h)5.f.f. Carbon feed rate.
NR 440.76(13)(h)6.6. The number of hours you have excluded data from the calculation of average levels and the reasons for excluding the data. Include data for the following 6 pollutants or parameters:
NR 440.76(13)(h)6.a.a. Sulfur dioxide emissions.
NR 440.76(13)(h)6.b.b. For Class I municipal waste combustion units only, nitrogen oxides emissions.
NR 440.76(13)(h)6.c.c. Carbon monoxide emissions.
NR 440.76(13)(h)6.d.d. Load level of the municipal waste combustion unit.
NR 440.76(13)(h)6.e.e. Temperature of the flue gases at the inlet of the particulate matter air pollution control device.
NR 440.76(13)(h)6.f.f. Carbon feed rate.
NR 440.76(13)(h)7.7. A notice of your intent to begin a reduced stack testing schedule for dioxins/furans emissions during the following calendar year, if you are eligible for alternative scheduling under sub. (10) (e) 1. or 2.
NR 440.76(13)(h)8.8. A notice of your intent to begin a reduced stack testing schedule for other pollutants during the following calendar year if you are eligible for alternative scheduling under sub. (10) (e) 1.
NR 440.76(13)(h)9.9. A summary of any emission or parameter level that did not meet the limits specified in this section.
NR 440.76(13)(h)10.10. A summary of the data in subds. 1. to 4. from the year preceding the reporting year which give the department a summary of the performance of the municipal waste combustion unit over a 2-year period.
NR 440.76(13)(h)11.11. If you choose to monitor carbon dioxide instead of oxygen as a diluent gas, documentation of the relationship between oxygen and carbon dioxide, as specified in sub. (9) (g).
NR 440.76(13)(h)12.12. Documentation of periods when all certified chief facility operators and certified shift supervisors are offsite for more than 12 hours.
NR 440.76(13)(i)(i) What must I do if I am out of compliance with the requirements of this section? You shall submit a semiannual report on any recorded emission or parameter level that does not meet the requirements specified in this section.
NR 440.76(13)(j)(j) If a semiannual report is required, when must I submit it?
NR 440.76(13)(j)1.1. For data collected during the first half of a calendar year, you shall submit your semiannual report by August 1 of that year.
NR 440.76(13)(j)2.2. For data you collected during the second half of the calendar year, you shall submit your semiannual report by February 1 of the following year.
NR 440.76(13)(k)(k) What must I include in the semiannual out-of-compliance reports? You shall include the following 3 items in the semiannual report:
NR 440.76(13)(k)1.1. For any of the following 6 pollutants or parameters that exceeded the limits specified in this section, include the calendar date they exceeded the limits, the averaged and recorded data for that date, the reasons for exceeding the limits, and your corrective actions:
NR 440.76(13)(k)1.a.a. Concentration or percent reduction of sulfur dioxide emissions.
NR 440.76(13)(k)1.b.b. For Class I municipal waste combustion units only, concentration of nitrogen oxides emissions.
NR 440.76(13)(k)1.c.c. Concentration of carbon monoxide emissions.
NR 440.76(13)(k)1.d.d. Load level of your municipal waste combustion unit.
NR 440.76(13)(k)1.e.e. Temperature of the flue gases at the inlet of your particulate matter air pollution control device.
NR 440.76(13)(k)1.f.f. Average 6-minute opacity level.
NR 440.76 NoteNote: The data obtained from your continuous opacity monitoring system are not used to determine compliance with the limit on opacity emissions.
NR 440.76(13)(k)2.2. If the results of your annual stack tests, as recorded in sub. (12) (e) 1., show emissions above the limits specified in Table 1 of this section for dioxins/furans, cadmium, lead, mercury, particulate matter, opacity, hydrogen chloride or fugitive ash, include a copy of the test report that documents the emission levels and your corrective actions.
NR 440.76(13)(k)3.3. For municipal waste combustion units that apply activated carbon to control dioxins/furans or mercury emissions, include the following 2 items:
NR 440.76(13)(k)3.a.a. Documentation of all dates when the 8-hour block average carbon feed rate, calculated from the carbon injection system operating parameter, is less than the highest carbon feed rate established during the most recent mercury or dioxins/furans stack test, as specified in sub. (12) (g) 1. a. Include the following 4 items:
1) Eight-hour average carbon feed rate.
2) Reasons for occurrences of low carbon feed rates.
3) The corrective actions you have taken to meet the carbon feed rate requirement.
4) The calendar date.
NR 440.76(13)(k)3.b.b. Documentation of each quarter when total carbon purchased and delivered to the municipal waste combustion plant is less than the total required quarterly usage of carbon. If you choose to evaluate total carbon purchased and delivered on a municipal waste combustion unit basis, record the total carbon purchased and delivered for each individual municipal waste combustion unit at your plant. Include the following 5 items:
1) Amount of carbon purchased and delivered to the plant.
2) Required quarterly usage of carbon.
3) Reasons for not meeting the required quarterly usage of carbon.
4) The corrective actions you have taken to meet the required quarterly usage of carbon.
5) The calendar date.
NR 440.76(13)(L)(L) Can reporting dates be changed?
NR 440.76(13)(L)1.1. If the department agrees, you may change the semiannual or annual reporting dates.
NR 440.76(13)(L)2.2. Section NR 440.185 (3) specifies the procedures to seek approval to change your reporting date.
NR 440.76(14)(14)Air curtain incinerators that burn 100% yard waste.
NR 440.76(14)(a)(a) What are the emission limits for air curtain incinerators that burn 100% yard waste? If your air curtain incinerator combusts 100% yard waste, only the emission limits in this subsection apply.
NR 440.76(14)(a)1.1. Within 60 days after your air curtain incinerator reaches the maximum load level at which it will operate, but no later than 180 days after its initial startup, you shall meet the following 2 limits:
NR 440.76(14)(a)1.a.a. The opacity limit is 10% (6-minute average) for air curtain incinerators that can combust at least 35 tons per day of municipal solid waste and no more than 250 tons per day of municipal solid waste.
NR 440.76(14)(a)1.b.b. The opacity limit is 35% (6-minute average) during the startup period that is within the first 30 minutes of operation.
NR 440.76(14)(a)2.2. Except during malfunctions, the requirements of this subsection apply at all times. Each malfunction may not exceed 3 hours.
NR 440.76(14)(b)(b) How must I monitor opacity for air curtain incinerators that burn 100% yard waste?
NR 440.76(14)(b)1.1. You shall use Method 9 in 40 CFR part 60, Appendix A, incorporated by reference in s. NR 440.17 (1), to determine compliance with the opacity limit.
NR 440.76(14)(b)2.2. You shall conduct an initial test for opacity as specified in s. NR 440.08.
NR 440.76(14)(b)3.3. After the initial test for opacity, you shall conduct annual tests no later than 13 calendar months following the date of your previous test.
NR 440.76(14)(c)(c) What are the recordkeeping and reporting requirements for air curtain incinerators that burn 100% yard waste?
NR 440.76(14)(c)1.1. You shall provide a notice of construction that includes the following 4 items:
NR 440.76(14)(c)1.a.a. Your intent to construct the air curtain incinerator.
NR 440.76(14)(c)1.b.b. Your planned initial startup date.
NR 440.76(14)(c)1.c.c. Types of fuels you plan to combust in your air curtain incinerator.
NR 440.76(14)(c)1.d.d. The capacity of your incinerator, including supporting capacity calculations, as specified in sub. (15) (d) and (e).
NR 440.76(14)(c)2.2. You shall keep records of results of all opacity tests onsite in either paper copy or electronic format unless the department approves another format.
NR 440.76(14)(c)3.3. You shall keep all records for each incinerator for at least 5 years.
NR 440.76(14)(c)4.4. You shall make all records available for submittal to the department or for onsite review by an inspector.
NR 440.76(14)(c)5.5. You shall submit the results (each 6-minute average) of the opacity tests by February 1 of the year following the year of the opacity emission test.
NR 440.76(14)(c)6.6. You shall submit reports as a paper copy on or before the applicable submittal date. If the department agrees, you may submit reports on electronic media.
NR 440.76(14)(c)7.7. If the department agrees, you may change the annual reporting dates under s. NR 440.185 (3).
NR 440.76(14)(c)8.8. You shall keep a copy of all reports onsite for a period of 5 years.
NR 440.76(15)(15)Equations.
NR 440.76(15)(a)(a) Concentration correction to 7% oxygen. You shall correct any pollutant concentration to 7% oxygen using the following equation:
where:
C7% is the concentration corrected to 7% oxygen
Cunc is the uncorrected pollutant concentration
O2 is the concentration of oxygen, percent
NR 440.76(15)(b)(b) Percent reduction in potential mercury emissions. You shall calculate the percent reduction in potential mercury emissions (%PHg) using the following equation:
(
)
(
)
x
=
where:
%PHg is the percent reduction of potential mercury emissions
Ei is the mercury emission concentration as measured at the air pollution control device inlet, corrected to 7% oxygen, dry basis
Eo is the mercury emission concentration as measured at the air pollution control device outlet, corrected to 7% oxygen, dry basis
NR 440.76(15)(c)(c) Percent reduction in potential hydrogen chloride emissions. You shall calculate the percent reduction in potential hydrogen chloride emissions (%PHCl) using the following equation:
(
)
(
)
x
-
=
where:
%PHCl is the percent reduction of the potential hydrogen chloride emissions
Ei is the hydrogen chloride emission concentration as measured at the air pollution control device inlet, corrected to 7% oxygen, dry basis
Eo is the hydrogen chloride emission concentration as measured at the air pollution control device outlet, corrected to 7% oxygen, dry basis
NR 440.76(15)(d)(d) Capacity of a municipal waste combustion unit. For a municipal waste combustion unit that can operate continuously for 24-hour periods, you shall calculate the municipal waste combustion unit capacity based on 24 hours of operation at the maximum charge rate. To determine the maximum charge rate, use one of the following 2 methods:
NR 440.76(15)(d)1.1. For municipal waste combustion units with a design based on heat input capacity, you shall calculate the maximum charging rate based on the maximum heat input capacity and one of the following 2 heating values:
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.