This is the preview version of the Wisconsin State Legislature site.
Please see http://docs.legis.wisconsin.gov for the production version.
NR 219.04(3)(3)Temperature reporting procedures. Samples cooled with ice packs or not in direct contact with ice during shipping shall be cooled to less than or equal to 6° C prior to shipping, and a temperature blank shall be submitted with the samples. Samples cooled during shipping with ice packs may not be recorded as received on ice. Samples may be recorded as received on ice only if solid ice is present in the cooler at the time the samples are received. If the samples are not received on ice, the laboratory shall record one of the following at the time of receipt:
NR 219.04(3)(a)(a) The temperature of an actual sample.
NR 219.04(3)(b)(b) The temperature of a temperature blank shipped with the samples.
NR 219.04(3)(c)(c) The temperature of the melt water in the shipping container.
NR 219.04(4)(4)Incorporation by reference. The materials in this section are incorporated by reference for the purposes of the permit program under ch. 283, Stats.
NR 219.04 NoteNote: Copies of the publications referenced in Tables A-H are available for inspection at the offices of the department of natural resources and the legislative reference bureau. Many of these materials are also available through inter-library loan.
NR 219.04 HistoryHistory: Cr. Register, June, 1986, No. 366, eff. 7-1-86; r. and recr. Tables B and E, Register, April, 1988, No. 388, eff. 5-1-88; am.; r. and recr. Tables A to F, Register, November, 1992, No. 443, eff. 12-1-92; am. (1), am. Tables A to F, Register, April, 1994, No. 460, eff. 5-1-94; am. (1) and (2), Tables A to F, cr. (3), Register, February, 1996, No. 482, eff. 3-1-96; CR 02-019: am. Table B Register October 2002 No. 562, eff. 11-1-02; CR 04-033: r. and recr. Table A, Table B, Table BM, Table C, Table D, Table E, Table EM, and Table F, cr. Table ES Register November 2004 No. 587, eff. 12-1-04; CR 04-101: am. Table A Note 29 Register May 2005 No. 593, eff. 6-1-05; CR 08-076: am. (2) and (3) (intro.), cr. (4), r. and recr. Table A, B, C to EM and F Register May 2009 No. 641, eff. 6-1-09; correction to Table B Parameter No. 41 made under s. 13.92 (4) (b) 7., Stats., Register September 2009 No. 645; correction to Table B Parameter No. 15 made under s. 13.92 (4) (b) 7., Stats., Register April 2010 No. 652; CR 13-112: am. (1) and (2), r. and recr. Table A, B, r. Table BM, r. and recr. Table C to F, cr. Tables G and H, Register May 2015 No. 713, eff. 6-1-15; correction in Table C footnote 11 made under s. 13.92 (4) (b) 6., Stats., Register July 2015 No. 715, eff. 8-1-15; CR 19-014: r. and recr. Table A and Notes, am. Table EM, r. and recr. Table EM Notes 8, 11, cr. Table EM Notes 16 to 23, r. and recr. Table H and Notes Register April 2020 No. 772, eff. 5-1-20; correction in (2) made under s. 35.17, Stats., Register July 2020 No. 775; CR 17-046: am. (1) Register February 2021 No. 782, eff. 6-29-21; republished to correct an error in transcription in Table F Note 1 Register January 2022 No. 793; correction in (2), Table EM Note 1 made under s. 35.17, Stats., Register June 2022 No. 798; CR 21-083: am. Table F Register July 2022 No. 799, eff. 8-1-22; correction in Table EM Note 1 made under s. 35.17, Stats., Register July 2022 No. 799.
NR 219.04 Text1 The method must be specified when results are reported.
NR 219.04 Text2 A 0.45-mm membrane filter (MF) or other pore size certified by the manufacturer to fully retain organisms to be cultivated and to be free of extractables which could interfere with their growth.
NR 219.04 Text3 Microbiological Methods for Monitoring the Environment, Water, and Wastes, EPA/600/8-78/017. 1978. U.S. EPA.
NR 219.04 Text4 U.S. Geological Survey Techniques of Water-Resource Investigations, Book 5, Laboratory Analysis, Chapter A4, Methods for Collection and Analysis of Aquatic Biological and Microbiological Samples. 1989. USGS.
NR 219.04 Text5 Because the MF technique usually yields low and variable recovery from chlorinated wastewaters, the Most Probable Number method will be required to resolve any controversies.
NR 219.04 Text6 Tests must be conducted to provide organism enumeration (density). Select the appropriate configuration of tubes/filtrations and dilutions/volumes to account for the quality, character, consistency, and anticipated organism density of the water sample.
NR 219.04 Text7 When the MF method has been used previously to test waters with high turbidity, large numbers of noncoliform bacteria, or samples that may contain organisms stressed by chlorine, a parallel test should be conducted with a multiple-tube technique to demonstrate applicability and comparability of results.
NR 219.04 Text8 To assess the comparability of results obtained with individual methods, it is suggested that side-by-side tests be conducted across seasons of the year with the water samples routinely tested in accordance with the most current Standard Methods for the Examination of Water and Wastewater or EPA alternate test procedure (ATP) guidelines.
NR 219.04 Text9 Annual Book of ASTM Standards-Water and Environmental Technology, Section 11.02. 2000, 1999, 1996. ASTM International.
NR 219.04 Text10 Official Methods of Analysis of AOAC International. 16th Edition, 4th Revision, 1998. AOAC International.
NR 219.04 Text11 Recommended for enumeration of target organism in sewage sludge.
NR 219.04 Text12 The multiple-tube fermentation test is used in 9221B.2-2014. Lactose broth may be used in lieu of lauryl tryptose broth (LTB), if at least 25 parallel tests are conducted between this broth and LTB using the water samples normally tested, and this comparison demonstrates that the false-positive rate and false-negative rate for total coliform using lactose broth is less than 10 percent. No requirement exists to run the completed phase on 10 percent of all total coliform-positive tubes on a seasonal basis.
NR 219.04 Text13 These tests are collectively known as defined enzyme substrate tests.
NR 219.04 Text14 After prior enrichment in a presumptive medium for total coliform using 9221B.2-2014, all presumptive tubes or bottles showing any amount of gas, growth or acidity within 48 h ± 3 h of incubation shall be submitted to 9221F-2014. Commercially available EC-MUG media or EC media supplemented in the laboratory with 50 mg/mL of MUG may be used.
NR 219.04 Text15 Method 1680: Fecal Coliforms in Sewage Sludge (Biosolids) by Multiple-Tube Fermentation Using Lauryl-Tryptose Broth (LTB) and EC Medium, EPA-821-R-14-009. September 2014. U.S. EPA.
NR 219.04 Text16 Samples shall be enumerated by the multiple-tube or multiple-well procedure. Using multiple-tube procedures, employ an appropriate tube and dilution configuration of the sample as needed and report the Most Probable Number (MPN). Samples tested with Colilert® may be enumerated with the multiple-well procedures, Quanti-Tray®, Quanti-Tray®/2000 and the MPN calculated from the table provided by the manufacturer.
NR 219.04 Text17 Colilert-18® is an optimized formulation of the Colilert® for the determination of total coliforms and E. coli that provides results within 18 h of incubation at 35°C rather than the 24 h required for the Colilert® test and is recommended for marine water samples.
NR 219.04 Text18 Descriptions of the Colilert®, Colilert-18®, Quanti-Tray®, and Quanti-Tray®/2000 may be obtained from IDEXX Laboratories, Inc.
NR 219.04 Text19 A description of the mColiBlue24® test, is available from Hach Company.
NR 219.04 Text20 Method 1681: Fecal Coliforms in Sewage Sludge (Biosolids) by Multiple-Tube Fermentation using A-1 Medium, EPA-821-R-06-013. July 2006. U.S. EPA.
NR 219.04 Text21 Method 1603: Escherichia coli (E. coli) in Water by Membrane Filtration Using Modified Membrane-Thermotolerant Escherichia coli Agar (modified mTEC), EPA-821-R-14-010. September 2014. U.S. EPA.
NR 219.04 Text22 Method 1682: Salmonella in Sewage Sludge (Biosolids) by Modified Semisolid Rappaport-Vassiliadis (MSRV) Medium, EPA-821-R-14-012. September 2014. U.S. EPA.
NR 219.04 Text23 A description of the Enterolert® test may be obtained from IDEXX Laboratories Inc.
NR 219.04 Text24 Method 1600: Enterococci in Water by Membrane Filtration Using membrane-Enterococcus Indoxyl-b-D-Glucoside Agar (mEI), EPA-821-R-14-011. September 2014. U.S. EPA.
NR 219.04 Text25 Standard Methods for the Examination of Water and Wastewater, Joint Editorial Board, American Public Health Association, American Water Works Association, and Water Pollution Control Federation, 23rd Edition (2017), 22nd Edition (2012), 21st Edition (2005), 20th Edition (1998), 19th Edition (1995), and 18th Edition (1992).
NR 219.04 Text26 Standard Methods for the Analysis of Water and Wastewater. With the promulgation of Federal Register /Vol. 77, No. 97 / Friday, May 18, 2012, the EPA lists only the most recently EPA-approved version of a Standard Method (regardless of the printed or online edition) in 40 CFR Part 136, with few exceptions, to identify the method with the year of Standard Methods approval or adoption designated by the last four digits in the method number (e.g., Standard Method 3113B–2004). This approach clearly identifies the version of the standard method approved under Part 136 and no longer ties it to a particular compendium printing or edition of Standard Methods. Methods can be purchased at www.standardmethods.org.
NR 219.04 Text27 Compliance monitoring must be performed in accordance with the specifications in the “State of Wisconsin Aquatic Life Toxicity Testing Methods Manual, 2nd Edition,” Wisconsin Department of Natural Resources, 2004. This publication is available for inspection at the offices of the Department of Natural Resources and the Legislative Reference Bureau. Copies are available from the Department of Natural Resources, Bureau of Science Services, P.O. Box 7921, Madison, WI 53707.
NR 219.04 Text28 To use Colilert-18® to assay for fecal coliforms, the incubation temperature is 44.5 ± 0.2 °C, and a water bath incubator is used.
NR 219.04 Text29 On a monthly basis, at least ten blue colonies from positive samples must be verified using lauryl tryptose broth and EC broth, followed by count adjustment based on these results; and representative non-blue colonies should be verified using lauryl tryptose broth. Where possible, verifications should be done from randomized sample sources.
NR 219.04 Text30 On a monthly basis, at least ten sheen colonies from positive samples must be verified using lauryl tryptose broth and brilliant green lactose bile broth, followed by count adjustment based on these results; and representative non-sheen colonies should be verified using lauryl tryptose broth. Where possible, verifications should be done from randomized sample sources.
NR 219.04 Text31 Subject coliform positive samples determined by 9222 B-2015 or other membrane filter procedure to 9222 I-2015 using NA-MUG media.
NR 219.04 Text32 Verification of colonies by incubation of BHI agar at 10 ± 0.5 °C for 48 ± 3 h is optional. As per the Errata to the 23rd Edition of Standard Methods for the Examination of Water and Wastewater, “Growth on a BHI agar plate incubated at 10 ± 0.5 °C for 48 ± 3 h is further verification that the colony belongs to the genus Enterococcus.”
NR 219.04 Text33 9221 F. 2-2014: This procedure allows for simultaneous detection of E. coli and thermotolerant coliforms by adding inverted vials to EC-MUG; the inverted vials collect gas produced by thermotolerant coliforms.
NR 219.04 Text1 Methods for Chemical Analysis of Water and Wastes, EPA-600/4-79-020. Revised March 1983 and 1979, where applicable. U.S. EPA. Available from: National Technical Information Service, 5285 Port Royal Road, Springfield, Virginia 22161.
NR 219.04 Text2 Methods for Analysis of Inorganic Substances in Water and Fluvial Sediments, Techniques of Water-Resource Investigations of the U.S. Geological Survey, Book 5, Chapter A1., unless otherwise stated. 1989. USGS.
NR 219.04 Text3 Official Methods of Analysis of the Association of Official Analytical Chemists, Methods Manual, Sixteenth Edition, 4th Revision, 1998. AOAC International.
NR 219.04 Text4 For the determination of total metals (which are equivalent to total recoverable metals) the sample is not filtered before processing. A digestion procedure is required to solubilize analytes in suspended material and to break down organic-metal complexes (to convert the analyte to a detectable form for colorimetric analysis).
NR 219.04 TextFor non-platform graphite furnace atomic absorption determinations a digestion using nitric acid (as specified in Section 4.1.3 of Methods for the Chemical Analysis of Water and Wastes) is required prior to analysis. The procedure used should subject the sample to gentle, acid refluxing and at no time should the sample be taken to dryness.
NR 219.04 TextFor direct aspiration flame atomic absorption determinations (FLAA) a combination acid (nitric and hydrochloric acids) digestion is preferred prior to analysis. The approved total recoverable digestion is described as Method 200.2 in Supplement I of “Methods for the Determination of Metals in Environmental Samples” EPA/600R-94/111, May, 1994, and is reproduced in EPA Methods 200.7, 200.8, and 200.9 from the same Supplement. However, when using the gaseous hydride technique or for the determination of certain elements such as antimony, arsenic, selenium, silver, and tin by non-EPA graphite furnace atomic absorption methods, mercury by cold vapor atomic absorption, the noble metals and titanium by FLAA, a specific or modified sample digestion procedure may be required and in all cases the referenced method write-up should be consulted for specific instruction and/or cautions.
NR 219.04 TextFor analyses using inductively coupled plasma-atomic emission spectrometry (ICP-AES), the direct current plasma (DCP) technique or the EPA spectrochemical techniques (platform furnace AA, ICP-AES, and ICP-MS) use EPA Method 200.2 or an approved alternate procedure (e.g., CEM microwave digestion, which may be used with certain analytes as indicated in Table IB); the total recoverable digestion procedures in EPA Methods 200.7, 200.8, and 200.9 may be used for those respective methods. Regardless of the digestion procedure, the results of the analysis after digestion procedure are reported as “total” metals.
NR 219.04 Text5 Copper sulfate or other catalysts that have been found suitable may be used in place of mercuric sulfate.
NR 219.04 Text6 Manual distillation is not required if comparability data on representative effluent samples are on file to show that this preliminary distillation step is not necessary: however, manual distillation will be required to resolve any controversies. In general, the analytical method should be consulted regarding the need for distillation. If the method is not clear, the laboratory may compare a minimum of 9 different sample matrices to evaluate the need for distillation. For each matrix, a matrix spike and matrix spike duplicate are analyzed both with and without the distillation step. (A total of 36 samples, assuming 9 matrices). If results are comparable, the laboratory may dispense with the distillation step for future analysis. Comparable is defined as < 20% RPD for all tested matrices). Alternatively the two populations of spike recovery percentages may be compared using a recognized statistical test.
NR 219.04 Text7 Industrial Method Number 379-75 WE Ammonia, Automated Electrode Method, Technicon Auto Analyzer II. February 19, 1976. Bran & Luebbe Analyzing Technologies Inc.
NR 219.04 Text8 The approved method is that cited in Methods for Determination of Inorganic Substances in Water and Fluvial Sediments, Techniques of Water-Resources Investigations of the U.S. Geological Survey, Book 5, Chapter A1. 1979. USGS.
NR 219.04 Text9 American National Standard on Photographic Processing Effluents. April 2, 1975. American National Standards Institute (ANSI), 25 West 43rd St., New York, NY 10036.
NR 219.04 Text10 In-Situ Method 1003-8-2009, Biochemical Oxygen Demand (BOD) Measurement by Optical Probe. 2009. In-Situ Incorporated.
NR 219.04 Text11 The use of normal and differential pulse voltage ramps to increase sensitivity and resolution is acceptable.
NR 219.04 Text12 Carbonaceous biochemical oxygen demand (CBOD5) must not be confused with the traditional BOD5test method which measures “total BOD.” The addition of the nitrification inhibitor is not a procedural option, but must be included to report the CBOD5parameter. A discharger whose permit requires reporting the traditional BOD5may not use a nitrification inhibitor in the procedure for reporting the results. Only when a discharger’s permit specifically states CBOD5is required can the permittee report data using a nitrification inhibitor.
NR 219.04 Text13 OIC Chemical Oxygen Demand Method. 1978. Oceanography International Corporation. 512 West Loop, P.O. Box 2980, College Station, TX 77840.
NR 219.04 Text14 Method 8000, Chemical Oxygen Demand, Hach Handbook of Water Analysis, 1979. Hach Company. P.O. Box 389, Loveland, CO 80537. Available on-line at http:/www.hach.com.
NR 219.04 Text15 The back titration method will be used to resolve controversy.
NR 219.04 Text16 Orion Research Instruction Manual, Residual Chlorine Electrode Model 97-70. Thermo Scientific, 81 Wyman Street, Waltham, MA 02454. 1977. Orion Research Incorporated. The calibration for the Orion residual chlorine method must be derived using at least three standard solutions, prepared from a 0.00281 N potassium iodate solution.
NR 219.04 Text17 Method 245.7, Mercury in Water by Cold Vapor Atomic Fluorescence Spectrometry, EPA-821-R-05-001. Revision 2.0, February 2005. US EPA., available from the U.S. EPA Sample Control Center (operated by CSC), 6101 Stevenson Avenue, Alexandria, VA 22304.
NR 219.04 Text18 National Council of the Paper Industry for Air and Stream Improvement (NCASI) Technical Bulletin 253, December 1971.
NR 219.04 Text19 Method 8506, Biocinchoninate Method for Copper, Hach Handbook of Water Analysis. 1979. Hach Company. P.O. Box 389, Loveland, CO 80537. Available on-line at http:/www.hach.com.
NR 219.04 Text20 When using a method with block digestion, this treatment is not required.
NR 219.04 Text21 Industrial Method Number 378-75WA, Hydrogen ion (pH) Automated Electrode Method, Bran & Luebbe (Technicon) Autoanalyzer II. October 1976. Bran & Luebbe Analyzing Technologies. Elmsford, NY 10523.
NR 219.04 Text22 Method 8008, 1,10-Phenanthroline Method using FerroVer Iron Reagent for Water. 1980. Hach Company P.O. Box 389, Loveland, CO 80537. Available on-line at http:/www.hach.com.
NR 219.04 Text23 Method 8034, Periodate Oxidation Method for Manganese, Hach Handbook of Wastewater Analysis. 1979. Hach Company Loveland, CO 80537. Available on-line at http:/www.hach.com.
NR 219.04 Text24 Methods for Analysis of Organic Substances in Water and Fluvial Sediments, Techniques of Water-Resources Investigations of the U.S. Geological Survey, Book 5, Chapter A3, (1972 Revised 1987) p. 14. 1987. USGS. Available from: U.S. Geological Survey, 604 S. Pickett Street, Alexandria, VA 22304.
NR 219.04 Text25 Method 8507, Nitrogen, Nitrite-Low Range, Diazotization Method for Water and Wastewater. 1979. Hach Company P.O. Box 389, Loveland, CO 80537. Available on-line at http:/www.hach.com.
NR 219.04 Text26 Just prior to distillation, adjust the sulfuric-acid-preserved sample to pH 4 with 1 + 9 NaOH.
NR 219.04 Text27 The colorimetric reaction must be conducted at a pH of 10.0 ± 0.2.
NR 219.04 Text28 Addison, R.F., and R.G. Ackman. 1970. Direct Determination of Elemental Phosphorus by Gas-Liquid Chromatography,Journal of Chromatography, 47(3):421-426. Available in most public libraries. Back volumes of the Journal of Chromatography are available from: Elsevier/North-Holland, Inc., Journal Information Centre, 52 Vanderbilt Avenue, New York, NY 10164.
NR 219.04 Text29 Approved methods for the analysis of silver in industrial wastewaters at concentrations of 1 mg/L and above are inadequate where silver exists as an inorganic halide. Silver halides such as the bromide and chloride are relatively insoluble in reagents such as nitric acid but are readily soluble in an aqueous buffer of sodium thiosulfate and sodium hydroxide to pH of 12. Therefore, for levels of silver above 1 mg/L, 20 mL of sample should be diluted to 100 mL by adding 40 mL each of 2 M Na2S2O3 and NaOH. Standards should be prepared in the same manner. For levels of silver below 1 mg/L the approved method is satisfactory.
NR 219.04 Text30 The use of EDTA decreases method sensitivity. Analysts may omit EDTA or replace with another suitable complexing reagent provided that all method specified quality control acceptance criteria are met.
NR 219.04 Text31 For samples known or suspected to contain high levels of silver (e.g., in excess of 4 mg/L), cyanogen iodide should be used to keep the silver in solution for analysis. Prepare a cyanogen iodide solution by adding 4.0 mL of concentrated NH4OH, 6.5 g of KCN, and 5.0 mL of a 1.0 N solution of I2 to 50 mL of reagent water in a volumetric flask and dilute to 100.0 mL. After digestion of the sample, adjust the pH of the digestate to >7 to prevent the formation of HCN under acidic conditions. Add 1 mL of the cyanogen iodide solution to the sample digestate and adjust the volume to 100 mL with reagent water (NOT acid). If cyanogen iodide is added to sample digestates, then silver standards must be prepared that contain cyanogen iodide as well. Prepare working standards by diluting a small volume of a silver stock solution with water and adjusting the pH>7 with NH4OH. Add 1 mL of the cyanogen iodide solution and let stand 1 hour. Transfer to a 100-mL volumetric flask and dilute to volume with water.
NR 219.04 Text32 “Water Temperature-Influential Factors, Field Measurement and Data Presentation,” Techniques of Water-Resources Investigations of the U.S. Geological Survey, Book 1, Chapter D1. 1975. USGS. Available from: U.S. Geological Survey, 604 S. Pickett Street, Alexandria, VA 22304.
NR 219.04 Text33 Method 8009, Zincon Method for Zinc, Hach Handbook of Water Analysis, 1979. Hach Company. Loveland, CO 80537. Available on-line at http:/www.hach.com.
NR 219.04 Text34 Method AES0029, Direct Current Plasma (DCP) Optical Emission Spectrometric Method for Trace Elemental Analysis of Water and Wastes. 1986-Revised 1991. Thermo Jarrell Ash Corporation. Available from: Thermo Scientific, 81 Wyman Street, Waltham, MA 02454.
NR 219.04 Text35 In-Situ Method 1004-8-2009, Carbonaceous Biochemical Oxygen Demand (CBOD) Measurement by Optical Probe. 2009. In-Situ Incorporated.
NR 219.04 Text36 Microwave-assisted digestion may be employed for this metal, when analyzed by this methodology. Closed Vessel Microwave Digestion of Wastewater Samples for Determination of Metals. April 16, 1992. CEM Corporation, P.O. Box 200, Matthews, NC 28106–0200.
NR 219.04 Text37 When determining boron and silica, only plastic, PTFE, or quartz laboratory ware may be used from start until completion of analysis.
NR 219.04 Text38 Only use n-hexane (n-Hexane—85% minimum purity, 99.0% min. saturated C6 isomers, residue less than 1 mg/L) extraction solvent when determining Oil and Grease parameters—Hexane Extractable Material (HEM), or Silica Gel Treated HEM (analogous to EPA Methods 1664 Rev. A and 1664 Rev. B). Use of other extraction solvents is prohibited.39 Method PAI-DK01, Nitrogen, Total Kjeldahl, Block Digestion, Steam Distillation, Titrimetric Detection. Revised December 22, 1994. OI Analytical/ALP- KEM, P.O. Box 9010, College Station, TX 77842.
NR 219.04 Text40 Method PAI-DK02, Nitrogen, Total Kjeldahl, Block Digestion, Steam Distillation, Colorimetric Detection. Revised December 22, 1994. OI Analytical.
NR 219.04 Text41 Method PAI-DK03, Nitrogen, Total Kjeldahl, Block Digestion, Automated FIA Gas Diffusion. Revised December 22, 1994. OI Analytical/ALPKEM, P.O. Box 9010, College Station, TX 77842.
NR 219.04 Text42 Method 1664 Rev. B is the revised version of EPA Method 1664 Rev. A. U.S. EPA. February 1999, Revision A. Method 1664, n-Hexane Extractable Material (HEM; Oil and Grease) and Silica Gel Treated n-Hexane Extractable Material (SGT-HEM; Non-polar Material) by Extraction and Gravimetry. EPA-821-R-98-002. U.S. EPA. February 2010, Revision B. Method 1664, n-Hexane Extractable Material (HEM; Oil and Grease) and Silica Gel Treated n-Hexane Extractable Material (SGT-HEM; Non-polar Material) by Extraction and Gravimetry. EPA-821-R-10-001. Available at NTIS, PB–121949, U.S. Department of Commerce, 5285 Port Royal, Springfield, VA 22161.
NR 219.04 Text43 Method 1631, Mercury in Water by Oxidation, Purge and Trap, and Cold Vapor Atomic Fluorescence Spectrometry, EPA-821-R-02-019. Revision E. August 2002, U.S. EPA. The application of clean techniques described in EPA’s Method 1669:Sampling Ambient Water for Trace Metals at EPA Water Quality Criteria Levels,EPA-821-R-96-011, are recommended to preclude contamination at low-level, trace metal determinations. Available at NTIS, PB-121949, U.S. Department of Commerce, 5285 Port Royal, Springfield, Virginia 22161.
NR 219.04 Text44 Method OIA-1677-09, Available Cyanide by Ligand Exchange and Flow Injection Analysis (FIA). 2010. OI Analytical/ALPKEM, P.O. Box 9010, College Station, TX 77842.
NR 219.04 Text45 Open File Report 00-170, Methods of Analysis by the U.S. Geological Survey National Water Quality Laboratory—Determination of Ammonium Plus Organic Nitrogen by a Kjeldahl Digestion Method and an Automated Photometric Finish that Includes Digest Cleanup by Gas Diffusion. 2000. USGS.
NR 219.04 Text46 Open File Report 93-449, Methods of Analysis by the U.S. Geological Survey National Water Quality Laboratory—Determination of Chromium in Water by Graphite Furnace Atomic Absorption Spectrophotometry. 1993. USGS.
NR 219.04 Text47 Open File Report 97-198, Methods of Analysis by the U.S. Geological Survey National Water Quality Laboratory—Determination of Molybdenum by Graphite Furnace Atomic Absorption Spectrophotometry. 1997. USGS.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.