A PARTIAL TABLE FOR THE SELECTION OF BACKFLOW PROTECTION * - See PDF for table PDF
*Any situation may be subject to an alternate approval.
1 If less than 15 pounds steam or 30 pounds water and nontoxic chemicals.
2 If greater than 15 pounds steam or 30 pounds water and toxic chemicals.
3 Requires backflow protection even if there is a plain end spout.
4 Requires separate water supply terminating without a hose thread, or the manufacturer must provide a bleed device to connect to the janitor sink faucet spout.
5 Or, provide bottled water conversion unit.
6 For outlets other than the required ASSE 1019 hydrants.
7 If provided with hose threads or serrated nipple.
8 Faucet meeting ASME A112.18.1M that includes backflow protection requirements.
9 Hydrants that bleed into the ground and hydrants that are flush with the grade are prohibited.
A-382.41 (5) (f)-1. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-2. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-3. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-4. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.41 (5) (f)-5. CROSS CONNECTION CONTROL ASSEMBLY INSTALLATION.
A-382.50 (3) (b) 5. OPTIONS FOR TEMPERATURE CONTROL IN HEALTH CARE FACILITIES. The following sketches provide options for fail safe installations at the bathing and shower fixture and temperature control at handwashing fixtures.
Option 1. Fail safe solenoid provided at main mixer meeting ASSE 1017, pressure balanced tub/shower valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
  Option 2. Fail safe solenoid provided at main mixer meeting ASSE 1017, pressure balanced tub/shower valve meeting ASSE 1016 and thermostatic mixer meeting ASSE 1016 at lavatory and kitchen sink faucets.
Option 3. Fail safe solenoid provided at main mixer meeting ASSE 1017, thermostatic tub/shower valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
Option 4. Fail safe solenoid provided at main mixer meeting ASSE 1017, combination thermostatic/pressure balance mixing valve meeting ASSE 1016 and limit stop faucets at lavatory and kitchen sink.
Option 5. Fail safe solenoid, combination pressure balanced/thermostatic tub/shower valve meeting ASSE 1016 and thermostatic mixer meeting ASSE 1016 at lavatory and kitchen sink faucets.
A-382.51 (3) MOBILE HOME SITES AND PARKS. Mobile home building sewer and water service connections.