This is the preview version of the Wisconsin State Legislature site.
Please see http://docs.legis.wisconsin.gov for the production version.
ATCP 93.300(3)(b) (b) If the fill opening is located outdoors, the opening shall be located in a watertight enclosure of noncombustible construction.
ATCP 93.300(3)(c)1.1. Each tank shall have a means of overfill prevention that consists of either a visual gauge, an audible or visual alarm, or a pump shutdown which activates at 90 percent of the tank's capacity, except as provided in subd. 2.
ATCP 93.300(3)(c)2.a.a. If the fill point is remote from the tank or if the delivery person cannot readily observe the tank gauge, an overfill alarm shall be provided at the fill point unless a pump shutdown is provided that activates at 90 percent of the tank's capacity.
ATCP 93.300(3)(c)2.b. b. All overfill alarms shall be readily audible or visible at the fill point and shall alert the delivery person when the tank is 90 percent full.
ATCP 93.300(3)(c)3. 3. All overfill alarms shall be labeled as such.
ATCP 93.300(4) (4)Signage. All tanks, whether new or existing, shall be provided with a permanent and durable sign installed at the used oil handler site or facility that includes all of the following:
ATCP 93.300(4)(a) (a) “NO SMOKING.”
ATCP 93.300(4)(b) (b) “USED OIL COLLECTION ONLY.”
ATCP 93.300(4)(c) (c) “DEPOSITING OTHER MATERIAL IS PROHIBITED.”
ATCP 93.300(5) (5)Vehicle collision protection. Vehicle collision protection shall be provided for aboveground tanks in accordance with s. ATCP 93.430 unless the authorized agent or the department determines the tank system is not subject to vehicle collision.
ATCP 93.300(6) (6)Secondary containment.
ATCP 93.300(6)(a) (a) Aboveground tanks located outdoors shall have secondary containment that complies with s. ATCP 93.420 (1) to (4).
ATCP 93.300(6)(b) (b) Tanks located inside a building shall have secondary containment for 100 percent of the tank capacity if a leak from the storage tank could reach a floor drain, the exterior of the building, or areas that pose an ignition hazard.
ATCP 93.300 Note Note: An oil-water separator connected to a floor drain may be used for all or a portion of the required secondary containment, depending on the system capacity.
ATCP 93.300(7) (7)Underground tanks.
ATCP 93.300(7)(a) (a) General. Underground tanks for used-oil storage shall comply with the applicable portions of NFPA 30 and this section.
ATCP 93.300(7)(b) (b) Spill protection. For underground tanks that store used oil, spill protection is not required at any point other than the fill point, if the tank meets all of the following conditions:
ATCP 93.300(7)(b)1. 1. The tank receives used oil in batches of 25 gallons or less by manual transfer.
ATCP 93.300(7)(b)2. 2. The tank is emptied only by suction transfer.
ATCP 93.300(7)(c) (c) Corrosion protection. Corrosion protection shall be provided in accordance with s. ATCP 93.520 except this protection is not required for piping that is associated with an underground tank which stores used oil, provided the tank and piping meet all of the following conditions:
ATCP 93.300(7)(c)1. 1. The tank receives used oil in batches of 25 gallons or less by manual transfer.
ATCP 93.300(7)(c)2. 2. All piping that is underground is sloped at an angle of at least 30 degrees from horizontal between the point at which it enters the ground and the tank, to allow for the free flow of oil.
ATCP 93.300 Note Note: This section does not exempt the tank itself from corrosion protection requirements.
ATCP 93.300(7)(d) (d) Leak detection. Leak detection shall be provided in accordance with ss. ATCP 93.510 and 93.515.
ATCP 93.300(8) (8)Tank closure and general administrative requirements.
ATCP 93.300(8)(a)(a) Aboveground tanks. Aboveground tanks that store used oil shall comply with ss. ATCP 93.440 to 93.470.
ATCP 93.300 Note Note: Sections ATCP 93.440 to 93.470 address: inspections; seldom-used and temporarily out of service tanks; change in service to store a non-regulated substance; tank closures; tank-system site assessments; and confirming and responding to leaks, spills, overfills and releases.
ATCP 93.300(8)(b) (b) Underground tanks. Underground tanks that store used oil shall comply with ss. ATCP 93.545 to 93.585.
ATCP 93.300 Note Note: Sections ATCP 93.545 to 93.585 address: seldom-used and temporarily out of service tanks; change in service to store a non-regulated substance; tank system closures; conditions indicating releases; tank-system integrity assessments; tank-system site assessments; and responding to leaks, spills, overfills and releases.
ATCP 93.300(9) (9)Scrap recycling and automobile recycling facilities. Subsections (1) (a), (2) (a), (2) (c) to (h), (3) to (5), (6) (a), and (8) do not apply to a new or existing aboveground tank which contains used oil and which is located at a scrap recycling or automobile recycling facility adequately participating in a cooperative compliance program approved by the department of natural resources, provided all of the following requirements are met:
ATCP 93.300(9)(a) (a) The tank is constructed of a durable material acceptable to the department.
ATCP 93.300(9)(b) (b) If located outside of a building, the tank has secondary containment acceptable to the department.
ATCP 93.300(9)(c) (c) If located inside a building, the tank has venting and fire prevention features acceptable to the department.
ATCP 93.300 History History: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19.
ATCP 93.305 ATCP 93.305Public used oil collection centers.
ATCP 93.305(1)(1)General. Public used oil collection centers shall comply with s. ATCP 93.300 and this section.
ATCP 93.305 Note Note: Also see ch. NR 679 for additional rules pertaining to used oil collection centers, such as operational criteria.
ATCP 93.305(2) (2)Tank construction. The tank shall be constructed to one of the recognized design standards in NFPA 30 chapter 21 unless otherwise accepted by the department.
ATCP 93.305 Note Note: Design standards recognized by NFPA 30 chapter 21 include API 12B, API 12D, API 12F, API 650, UL 58, UL 80, UL 142, UL 1316, UL 1746, UL 2080 and UL 2085.
ATCP 93.305(3) (3)Tank size and installation requirements.
ATCP 93.305(3)(a) (a) The tank may be of any size.
ATCP 93.305(3)(b) (b) Tanks located outdoors shall comply with the setback requirements of NFPA 30 Tables 22.4.1.1 (a) and (b) for a Class IIIA liquid.
ATCP 93.305(3)(c) (c) Tanks located inside a building shall have venting that terminates outdoors.
ATCP 93.305(4) (4)Diking.
ATCP 93.305(4)(a)(a) A single-wall tank shall be placed within a diked area that complies with s. ATCP 93.420.
ATCP 93.305(4)(b) (b) A tank of double-wall construction, that is accessible to the public, shall be placed within secondary containment which meets all of the following requirements:
ATCP 93.305(4)(b)1. 1. Any curb shall have a height of at least 4 inches.
ATCP 93.305(4)(b)2. 2. The containment shall extend at least 2 feet beyond the greatest tank dimension in all directions.
ATCP 93.305(4)(c) (c) The tank shall be set back from the curb or dike wall such that an overflow of the tank will be contained within the diked or curbed area.
ATCP 93.305(4)(d) (d) The fill opening with spill containment shall be located within the diked or curbed area.
ATCP 93.305 History History: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19.
ATCP 93.310 ATCP 93.310Heating fuel storage.
ATCP 93.310(1)(1)Scope. This section applies to any new or existing aboveground or underground tank that is used to supply liquid fuel to a heating device, including a used oil burner, if the device and the fuel have the following characteristics:
ATCP 93.310(1)(a) (a) The heating device is used for space heating, processing or manufacturing.
ATCP 93.310(1)(b) (b) The fuel is consumed on the premises where stored.
ATCP 93.310 Note Note: Number 5 and 6 fuel oil do not meet the criteria for a liquid and therefore are not regulated by this chapter.
ATCP 93.310(2) (2)Installation, use and maintenance.
ATCP 93.310(2)(a) (a) Tanks that supply oil-burning equipment shall be installed, used and maintained in accordance with NFPA 31 and this section.
ATCP 93.310(2)(b) (b) Tanks used to store heating fuel shall be installed by or under the direct supervision of a certified installer.
ATCP 93.310 Note Note: Tanks installed at 1- or 2-family dwellings are not required to have plan review under s. ATCP 93.100, and aboveground tanks that have a capacity of less than 1,100 gallons are not required to have registration under s. ATCP 93.140.
ATCP 93.310 Note Note: Devices that burn used oil are regulated by the Commercial Building Code, chs. SPS 361 to 366, and the Fire Prevention Code, ch. SPS 314. The tank that stores the oil is regulated by this chapter.
ATCP 93.310(3) (3)Underground tanks that have a capacity of less than 4,000 gallons. Underground heating oil storage tank systems that have a capacity of less than 4,000 gallons shall have all of the following:
ATCP 93.310(3)(a) (a) Overfill prevention equipment that notifies the person filling the tank, with either an audible or a visual signal, that the liquid level has reached 90 percent of the tank's capacity.
ATCP 93.310(3)(b) (b) Corrosion protection that complies with s. ATCP 93.520, except this requirement does not apply to tanks that were installed before November 1, 1994.
ATCP 93.310(3)(c)1.1. Precision tightness testing every 2 years or leak detection in accordance with s. ATCP 93.510, except this requirement does not apply to residential tanks which have a capacity of less than 1,100 gallons and which were installed before October 29, 1999, for consumptive use on the property where stored.
ATCP 93.310(3)(c)2. 2. The tightness testing or leak detection methods used to comply with subd. 1. shall be specifically approved for use with the specific type of heating oil in accordance with s. ATCP 93.130.
ATCP 93.310(4) (4)Underground tanks that have a capacity of 4,000 gallons or more. Underground heating oil storage tank systems that have a capacity of 4,000 gallons or more shall have secondary containment which complies with s. ATCP 93.500 (1) if the system is either new or a replacement, leak detection which complies with s. ATCP 93.510 and corrosion protection which complies with s. ATCP 93.520.
ATCP 93.310(5) (5)Spill and overfill prevention.
ATCP 93.310(5)(a) (a) Spill and overfill prevention for aboveground tanks shall be provided in accordance with s. ATCP 93.300 (3).
ATCP 93.310(5)(b) (b) Spill and overfill prevention for underground tanks shall be provided in accordance with s. ATCP 93.505, except this requirement does not apply to residential tanks that have a capacity of less than 1,100 gallons containing fuel oil for consumptive use on the property.
ATCP 93.310(5)(c) (c) Fill pipes for used-oil tanks that are part of a heating system may be located inside a building.
ATCP 93.310(6) (6)Tank closure and general administrative requirements.
ATCP 93.310(6)(a)(a) Aboveground tanks. Aboveground tanks that store heating oil shall comply with ss. ATCP 93.440 to 93.470.
ATCP 93.310 Note Note: Sections ATCP 93.440 to 93.470 address inspections; seldom-used and temporarily out of service tanks; change in service to store a non-regulated substance; tank closures; tank system site assessments; and confirming and responding to leaks, spills, overfills and releases.
ATCP 93.310(6)(b) (b) Underground tanks. Underground tanks that store heating oil shall comply with ss. ATCP 93.545 to 93.585.
ATCP 93.310 Note Note: Sections ATCP 93.545 to 93.585 address seldom-used and temporarily out of service tanks; change in service to store a non-regulated substance; tank system closures; conditions indicating releases; tank system integrity assessments; tank system site assessments; and responding to leaks, spills, overfills and releases.
ATCP 93.310 History History: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19.
ATCP 93.315 ATCP 93.315Heating oil tanks that are removed from service.
ATCP 93.315(1)(1)Application. This section applies to aboveground heating oil storage tanks which are connected to heating appliances and which store heating oil that is consumed on the premises.
ATCP 93.315(2) (2)General. Placing a heating oil storage tank out of service for any reason other than immediate repair or replacement shall follow the procedure in either par. (a) or (b):
ATCP 93.315(2)(a) (a) The tank and all connected piping, including the vent and fill piping, shall be emptied, cleaned and removed from the premises.
ATCP 93.315(2)(b)1.1. The tank and all connected piping shall be emptied and purged of all vapors.
ATCP 93.315(2)(b)2. 2. If the tank is not removed, the tank vent shall be left intact and open.
ATCP 93.315(2)(b)3. 3. If the fill pipe is not removed, it shall be filled to the top with concrete and capped.
ATCP 93.315(2)(b)4. 4. Any piping that is not removed, other than a tank vent, shall be capped or otherwise sealed.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.