This is the preview version of the Wisconsin State Legislature site.
Please see http://docs.legis.wisconsin.gov for the production version.
ATCP 93.517(2)(b)2. 2. A description of the leak detection method used.
ATCP 93.517 Note Note: A designer of an airport hydrant leak detection system who does not have a financial interest in the airport may be considered to be the independent third party that is required in s. ATCP 93.130 (3) (b) 1. for leak detection methods.
ATCP 93.517(2)(b)3. 3. A schedule for testing the system.
ATCP 93.517(2)(b)4. 4. Any limitations of the leak detection method.
ATCP 93.517(2)(b)5. 5. An action plan in the event a leak is detected.
ATCP 93.517(2)(c) (c) Owners and operators of underground piping systems associated with airport hydrant systems shall meet leak detection requirements in accordance with s. ATCP 93.510, or use one or a combination of the following alternative methods of release detection:
ATCP 93.517(2)(c)1. 1. Perform a semiannual or annual tightness test at or above the piping operating pressure in accordance with the following system volume:
ATCP 93.517(2)(c)1.a. a. Fuel systems with less than 50,000 gallons are not to exceed one gallon per hour for semiannual testing or 0.5 gallons for annual testing.
ATCP 93.517(2)(c)1.b. b. Fuel systems with 50,000 to 75,000 gallons are not to exceed 1.5 gallons per hour for semiannual testing or 0.75 gallons for annual testing.
ATCP 93.517(2)(c)1.c. c. Fuel systems with 75,000 to 100,000 gallons are not to exceed 2.0 gallons per hour for semiannual testing or one gallon for annual testing.
ATCP 93.517(2)(c)1.d. d. Fuel systems greater than 100,000 gallons are not to exceed 3.0 gallons per hour for semiannual testing or 1.5 for annual testing.
ATCP 93.517(2)(c)2. 2. Piping segments not capable of meeting the maximum 3.0 gallon per hour leak rate for the semiannual test may be tested at a leak rate up to 6.0 gallons per hour according to the following schedule:
ATCP 93.517(2)(c)2.a. a. First test, not later than October 13, 2018, airport hydrant systems may use up to a 6.0 gallon per hour leak rate.
ATCP 93.517(2)(c)2.b. b. Second test, between October 13, 2018, and October 13, 2021, airport hydrant systems may use up to a 6.0 gallon per hour leak rate.
ATCP 93.517(2)(c)2.c. c. Third test, between October 13, 2021, and October 13, 2022, airport hydrant systems must use a 3.0 gallon per hour leak rate.
ATCP 93.517(2)(c)2.d. d. Subsequent tests, after October 13, 2022, begin using semiannual or annual line testing according to the maximum leak detection rate in par. (b).
ATCP 93.517(2)(c)3. 3. Perform inventory control in accordance with s. ATCP 93.515 (2) at least every 30 days that can detect a leak equal to or less than 0.5 percent of flow through; and
ATCP 93.517(2)(c)4. 4. Perform a line tightness test, conducted in accordance with s. ATCP 93.515 (4), at least every 2 years; or
ATCP 93.517(2)(c)5. 5. Another method approved by the implementing agency if the owner and operator can demonstrate that the method can detect a release as effectively as any of the methods allowed in this section. In comparing methods, the implementing agency shall consider the size of release that the method can detect and the frequency and reliability of detection.
ATCP 93.517(3) (3)Registration and notification.
ATCP 93.517(3)(a) (a) The owner of a newly installed airport hydrant system shall notify the implementing agency and register the system in accordance with s. ATCP 93.140.
ATCP 93.517(3)(b) (b) All owners of airport hydrant systems shall provide proof of financial responsibility in accordance with s. ATCP 93.700.
ATCP 93.517(4) (4)System requirements.
ATCP 93.517(4)(a) (a) All new airport hydrant systems shall be designed and equipped with isolation valves appropriate for leak testing.
ATCP 93.517(4)(b) (b) Any repair or upgrade to an existing airport hydrant system shall include the installation of isolation valves in the section that is repaired or upgraded.
ATCP 93.517(5) (5)Periodic inspections and walkthroughs. Owners and operators must inspect the following additional areas for airport hydrant systems at least once every 30 days if confined space entry according to the occupational safety and health administration is not required, or at least annually if confined space entry is required:
ATCP 93.517(5)(a) (a) Hydrant pits—visually check for any damage; remove any liquid or debris; and check for any leaks; and
ATCP 93.517(5)(b) (b) Hydrant piping vaults—check for any hydrant piping leaks.
ATCP 93.517 History History: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19; correction in (2) (c) 2. b., c., 4. made under s. 35.17, Stats., Register October 2019 No. 766.
ATCP 93.520 ATCP 93.520Corrosion protection.
ATCP 93.520(1)(1)General.
ATCP 93.520(1)(a)(a) Where required. Vent lines, vapor lines and any portion of a single or double-wall tank system, whether new or existing, that routinely contains product and is in contact with the ground or with water shall be protected from corrosion by one of the following methods:
ATCP 93.520(1)(a)1. 1. The tank and piping are constructed of an inherently corrosion-resistant material.
ATCP 93.520(1)(a)2.a.a. The tank and piping are installed at a site that is determined by a certified corrosion expert to be non-corrosive during the operational life of the system.
ATCP 93.520(1)(a)2.b. b. A certified corrosion expert retained for the purpose of determining a non-corrosive site shall make at least one personal visit to each tank site during the design stage.
ATCP 93.520 Note Note: See ATCP Table 93.200–5 for information on contacting NACE.
ATCP 93.520(1)(a)3. 3. The tank is a listed composite or jacketed tank designated as complying with UL 1746, and the piping is protected by one of the methods in this subsection.
ATCP 93.520 Note Note: In addition to composite and jacketed tanks, the UL 1746 standard also includes requirements for coated tanks and tanks with pre-engineered cathodic protection systems. These last 2 types of cathodic protection are not included in the blanket approval under this section.
ATCP 93.520(1)(a)4. 4. The tank and piping are protected with a sacrificial anode system in accordance with a standard developed by a nationally recognized association or independent testing laboratory that is acceptable to the department.
ATCP 93.520(1)(a)5.a.a. The tank and piping are protected with a corrosion protection system designed by a certified corrosion expert and comply with either sub. (2) or (3).
ATCP 93.520(1)(a)5.b. b. A corrosion expert retained for the purpose of designing an impressed current corrosion protections system shall make at least one personal visit to each tank site during the design stage.
ATCP 93.520(1)(b) (b) Design and construction.
ATCP 93.520(1)(b)1.1. To allow for periodic testing, new and replacement factory- or field-installed corrosion protection systems shall have appropriate connections, insulated lead wires and accessible test stations, including as specified in subds. 2. and 3.
ATCP 93.520(1)(b)2. 2. All lead wires connected to a tank, anode, reference electrode, or other component associated with the corrosion protection system shall terminate at a test station.
ATCP 93.520(1)(b)3. 3. The termination of each lead wire at a test station shall be clearly labeled or coded to identify the specific component to which it is connected.
ATCP 93.520(1)(b)4. 4. Impressed current systems shall be designed to prevent stray current conditions that may negatively impact other underground structures, utility lines, or cable anchors, or any impressed current systems protecting those items.
ATCP 93.520(1)(b)5. 5. Local utilities shall be notified by the contractor when impressed current systems are installed, repaired, or adjusted, including where an increase in rectifier amperage or voltage output occurs.
ATCP 93.520(1)(c) (c) Operation and maintenance.
ATCP 93.520(1)(c)1.1. Operation and maintenance of corrosion protection systems shall be in accordance with national standards acceptable to the department.
ATCP 93.520(1)(c)2. 2. All new and existing corrosion protection systems shall be operated and maintained to continuously provide corrosion protection for the life of the tank system.
ATCP 93.520(1)(c)3. 3. For impressed current systems, operation and maintenance practices and procedures shall be evaluated, and conducted in a manner that minimizes direct current interference to or from any underground structure, utility line, or cable anchors in the area.
ATCP 93.520(1)(d) (d) Periodic testing requirements.
ATCP 93.520(1)(d)1.a.a. All new and existing corrosion protection for UST systems shall be tested within 6 months of installation or repair and at least annually, except as provided in subd. 3.
ATCP 93.520(1)(d)1.b. b. For sacrificial anode systems, structure-to-soil potential readings shall be conducted with a minimum of one local potential measurement near the UST center and away from the anodes and one remote potential measurement. Alternatively, a minimum of three potential measurements, one at each of the UST ends and one near the center of the UST, may be taken.
ATCP 93.520 Note Note: This requirement is from NACE standard TM-0101.
ATCP 93.520(1)(d)1.bm. bm. For impressed current systems, structure-to-soil potential readings shall be conducted with a minimum of three potential measurements, one at each of the UST ends and one near the center of the UST.
ATCP 93.520 Note Note: This requirement is from NACE standard TM-0101.
ATCP 93.520(1)(d)1.c. c. For each product line, structure-to-soil potentials shall be taken above the piping, at the ends and middle, away from the anode locations. Piping runs over 50 feet shall have additional readings taken every 25 feet.
ATCP 93.520(1)(d)1.d. d. For impressed current systems, the annual test shall include instant-off potentials.
ATCP 93.520(1)(d)2. 2. In addition to the requirements in subd. 1., impressed current corrosion protection systems shall be inspected and evaluated by the site operator at least every 60 days to ensure the equipment is providing adequate current in accordance with its design.
ATCP 93.520(1)(d)3. 3. Tanks designated as sti-P3® equipped with a preinstalled sacrificial anode system and test station shall be tested in accordance with all of the following:
ATCP 93.520(1)(d)3.a. a. Testing shall occur within 6 months of installation and at least every 3 years thereafter until the tank is 10 years old.
ATCP 93.520(1)(d)3.b. b. Testing shall occur annually in accordance with subd. 1. after the tank is 10 years old.
ATCP 93.520(1)(d)4. 4. The results of the inspections, evaluations and testing under this paragraph shall be summarized on the department's form, TR-WM-141, and retained at the site in accordance with s. ATCP 93.500 (9).
ATCP 93.520 Note Note: Form TR-WM-141, UST Corrosion Protection Test/Survey Report, is available from the Bureau of Weights and Measures, PO Box 8911, Madison, WI 53708-8911, or at telephone (608) 224-4942, or from the Bureau's Web site at https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanks.aspx.
ATCP 93.520 Note Note: Section ATCP 93.500 (9) specifies retention requirements for testing and repair records of corrosion protection systems.
ATCP 93.520(1)(e) (e) Certifications for corrosion protection.
ATCP 93.520(1)(e)1. 1. A certified cathodic protection tester shall be on the site to supervise and monitor the initial post-installation start-up of impressed current corrosion protection systems.
ATCP 93.520 Note Note: NACE requires a person with Senior Corrosion Technologist certification or higher for corrosion protection system commissioning.
ATCP 93.520(1)(e)2. 2. A certified cathodic protection tester shall perform or supervise the performance of reinstallation or replacement of anodes.
ATCP 93.520 Note Note: NACE requires a person with Level 1 Cathodic Protection Tester certification or higher for reinstallation or replacement of anodes.
ATCP 93.520(1)(e)3.a.a. All new and existing corrosion protection for UST systems shall be tested by a certified cathodic protection tester, except as provided in subd. 3. b.
ATCP 93.520 Note Note: NACE requires a person with corrosion technologist certification or higher or a person with corrosion technician certification who is directly supervised by a certified corrosion technologist or higher to perform work as a state-certified cathodic protection tester.
ATCP 93.520(1)(e)3.b. b. Tanks designated as sti-P3® shall be tested by a person holding a certification from the Steel Tank Institute or one of the certifications in subd. 3. a.
ATCP 93.520 Note Note: Additional information on corrosion protection certifications is available from the department's Web site at https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanks.aspx.
ATCP 93.520(2) (2)Sacrificial anode systems.
ATCP 93.520(2)(a) (a) General. All new and existing sacrificial anode systems shall maintain the standard protection threshold reading of at least negative 850 millivolts or shall comply with the requirements of par. (b).
ATCP 93.520(2)(b) (b) Failing sacrificial anode systems.
ATCP 93.520(2)(b)1.1. Unless arrangements are made with the authorized agent or the department to conduct follow-up testing, the cause of the failure shall be investigated and repaired within 90 days of the failed reading; or the entire tank system shall be emptied within 90 days of the failed reading and shall remain empty until the repair is completed.
ATCP 93.520(2)(b)2. 2. If more than 2 years have elapsed since the previous corrosion protection test, or if the corrosion protection system has been inoperative for 2 years or more, an internal inspection shall be performed by a third party in accordance with one of the following standards:
ATCP 93.520(2)(b)2.a. a. For lined tanks, the internal inspection shall be in accordance with API 1631 or KWA.
ATCP 93.520(2)(b)2.b. b. For unlined tanks, the internal inspection shall be in accordance with ASTM G158 Method B.
ATCP 93.520(2)(b)3. 3. If the tank fails the internal inspection, one of the following shall occur:
ATCP 93.520(2)(b)3.a. a. The tank system shall be permanently closed.
ATCP 93.520(2)(b)3.b. b. The tank system shall be lined or any present lining shall be repaired in accordance with API 1631, and an impressed current corrosion protection system shall be installed.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.