(4)Water service connections. The plumbing system for the water service and water distribution system for a toilet building, shower building, food facility or other buildings supplied with water shall comply with chs. SPS 382 and 384, as enforced by the Wisconsin department of safety and professional services.
Note: To minimize the risk of Legionella growth and other diseases associated with water, adequate provisions should be made to ensure that all water systems including sink faucets, drinking fountains, and showers are safe particularly with regard to any water aged over 3 weeks that is at greater risk for proliferation of Legionella. It is strongly advised that each camp develop and implement a water management program as recommended by the United States centers for disease control water management program toolkit.
(5)Containers for transporting drinkable water.
(a) Labeling and construction. Containers shall meet all of the following requirements for transporting water for human consumption and be:
1. Labeled and easily distinguishable from other containers.
2. Constructed of a food grade material that does not allow the migration of deleterious substances to the water or impart colors, odors or tastes. P
3. Easily cleanable.
(b) Containers cleaned and sanitized. Water containers shall be cleaned and sanitized between uses. P
(6)Drinking facilities.
(a) General. Water shall be provided to campers using any of the following methods:
1. An approved drinking fountain as required pursuant to s. SPS 362.2902. P
2. Individual disposable drinking cups. Pf
3. Personal water containers. Pf
(b) Water containers for reuse. Reusable individual water containers shall be cleaned as often as necessary or when returning from primitive camping trips.
(c) Prohibition. Common drinking cups are prohibited. P
History: CR 21-109: cr. Register June 2023 No. 810, eff. 9-24-23; correction in (2) (b) 1., (3) (b) made under s. 35.17, Stats., Register June 2023 No. 810.
ATCP 78.19Sewage disposal system.
(1)Sewage. Sewage, including all liquid and water-carried wastes from sinks, bathing and toilet facilities, may not discharge onto the ground surface. P
(2)Plumbing fixtures. Plumbing fixtures shall meet all of the following:
(a) Connection. Connected to the building drainage system. P
(b) Discharge. Discharge to a public sewer or private sewage disposal system. P
(3)Public sewer. When a public sewer facility is available to the camp, connection to, and use of, that facility are required.
Note: See s. SPS 383.03 (2), Public Sewer Connection.
(4)POWTS disposal.
(a) Designed, constructed and operated.
1. Any POWTS system used by a camp under this chapter shall be located, designed, constructed and operated in accordance with chs. SPS 382, 383 and 384, as enforced by the Wisconsin department of safety and professional services. P
2. The operator shall ensure that access opening covers to a POWTS remain locked or secured, except for inspection, evaluation, maintenance, or servicing purposes. P
Note: See s. 145.195, Stats., regarding building on unsewered property.
(b) Failing private sewage system. A failing private sewage system shall be brought into compliance, replaced or its use discontinued. In this subsection, “failing private sewage system” has the meaning given in s. 145.245 (4), Stats. P
(c) Required approvals. A camp shall submit plan and installation details for the design and construction, alteration or extension of a private sewage disposal system to the Wisconsin department of safety and professional services or its designated agent for approval and shall acquire a sanitary permit before altering or extending the private sewage disposal system. Pf
Note: Local jurisdictions may require additional approvals.
History: CR 21-109: cr. Register June 2023 No. 810, eff. 9-24-23; correction in (4) (b) made under s. 35.17, Stats., Register June 2023 No. 810.
ATCP 78.20Toilet and shower facilities.
(1)Requirements.
(a) Toilet facilities. Toilet facilities construction shall comply with State Building code as enforced by the Wisconsin department of safety and professional services.
(b) Ratio.
1. A camp shall provide a minimum of one toilet and one handwash facility for every 10 campers and staff or fraction thereof.
2. The camp operator shall designate toilet facilities based on the attendance at the camp.
(c) Lighting. Toilet facilities shall be provided with adequate artificial lighting.
(d) Location. Toilet facilities shall be located within 400 feet of lodging units.
(e) Operation. Toilet facilities shall meet all of the following requirements and be:
1. Equipped with a functional privacy lock for each stall.
2. Provided with exterior self-closing doors.
3. Maintained in a pest-proof condition.
4. Effectively screened. Pf
5. Maintained in clean and good repair.
6. Provided with a supply of toilet paper in each stall.
(f) Privies. Privies shall meet the following requirements:
1. Constructed in accordance with chs. SPS 361 to 365 and 391, as enforced by the Wisconsin department of safety and professional services.
2. Maintained in good repair.
3. Not be located within 15 feet of a building used for human occupancy. Pf
4. Obtain approval by the department for a distance between 15 and 75 feet for other approved privy or toilet types.
(g) Shower ratio. A minimum of one shower or bathtub shall be provided for every 20 campers and staff or fraction thereof.
(h) Handwashing sinks. Handwashing sinks shall be provided in all rooms having flush toilets and shower facilities Pf and be provided with all of the following:
1. Tempered water Pf
2. A supply of soap. Pf
3. Single-use toweling or a hand drying device in locations that are accessible to all campers, staff and visitors. Pf
4. A waste receptacle.
(i) Flooring surfaces.
1. Carpeting is prohibited in toilet rooms and shower and bathing facilities.
2. Shower area floors and bathtubs shall be provided with an anti-slip surface or matting. P
3. Flooring shall be nonabsorbent and easily cleanable.
4. Flooring shall be maintained in good repair.
(2)Toilets and bathing facilities for people with physical disabilities. The construction and accessibility of toilets, toilet rooms, toilet buildings, and bathing facilities shall comply with s. SPS 362.1210 (1m), as enforced by the Wisconsin department of safety and professional services.
History: CR 21-109: cr. Register June 2023 No. 810, eff. 9-24-23.
ATCP 78.21Camper sleeping quarters.
(1)Permanent. This section applies to structures that are enclosed and are permanent in nature, including buildings, cabins, dorms, yurts, covered wagons or tents covering a non-collapsible framework, and that are used as sleeping quarters for more than 30 consecutive days.
(a) Layout. Camper sleeping quarters shall meet all of the following requirements:
1. An individual bed is provided for each camper. Pf
2. A ceiling height of at least 7 feet is provided.
3. Camper sleeping arrangement shall be head to toe or in a bed layout configuration that provides at least 6 feet horizontally between the heads of sleepers. Pf
4. When beds are arranged side by side there shall be at least 3 feet between beds to provide an aisle for emergency egress and to help prevent transmission of respiratory illnesses. Pf
5. L-shaped or end to end bed configurations are acceptable if the heads of sleepers are positioned to meet the requirements pursuant to subds. 3 and 4. Pf
(b) Platform tents. Platforms constructed to provide a solid, level floor for the tent shall not exceed 3 feet in height above the ground. Pf
(c) Bunk beds. When a bunk bed is provided by the camp for campers, the operator shall ensure all of the following requirements are met:
1. No more than 2 beds may be stacked vertically. P
2. There shall be a vertical separation of at least 2 1/2 feet measured from the top of the lower mattress to the bottom of the frame of the upper bed. Pf
3. A free space of at least 2 1/2 feet shall be provided above the mattress of the upper bed. Pf
4. Bunk beds shall be located away from potential hazards, including heat sources, ceiling fans, or other ceiling protrusions. Pf
5. When campers sleep in upper bunks, guards shall be installed to prevent occupants from rolling out and shall meet all of the following:P
a. The top of the rail shall be at least 5 inches above the top of the mattress. Pf
b. The bottom of the rail shall be no more than 3 and a half inches above the top of the bed frame. Pf
(d) Screening. A camp shall use one of the following screening methods:
1. 16 mesh wire or other effective screening kept in good repair shall be provided on all openings in sleeping quarters to prevent the entry of pests. Pf
2. Individual camper mosquito-type netting shall be provided. Pf
(e) Linens and bedding.
1. If provided, pillowslips, sheets, towels, and washcloths shall be washed at least once a week and before being assigned to a different camper.
2. Blankets, spreads, mattresses, sleeping bags and pillows shall be kept clean and free of pest infestation.
3. Mattresses shall meet all of the following: