This is the preview version of the Wisconsin State Legislature site.
Please see http://docs.legis.wisconsin.gov for the production version.
NR 811.48(8)(c)6.6. The aqua ammonia feed pump, regulators, and lines shall be fitted with pressure relief vents discharging outside the building away from any air intake and with water purge lines leading back to the headspace of the bulk storage tanks.
NR 811.48(8)(c)7.7. The aqua ammonia shall be conveyed directly from a day tank to the treated water stream injector without the use of a carrier water stream unless the carrier stream is softened.
NR 811.48(9)(9)Calcium hypochlorite tablet chlorinators. Calcium hypochlorite tablet chlorinators shall meet the following design requirements:
NR 811.48(9)(a)(a) Calcium hypochlorite solution formation. The calcium hypochlorite solution shall be produced by dissolving tablets with a department approved feed water source using an erosion chamber or an upward directed spray system. The department may approve other methods or technology for producing calcium hypochlorite solution after the submittal of data from a department-approved pilot program.
NR 811.48(9)(b)(b) Tablets. The calcium hypochlorite tablets used in the chlorinator shall be supplied by the manufacturer of the tablet chlorinator equipment. The supplier of the calcium hypochlorite tablets shall have obtained NSF/ANSI Standard 60 certification for the tablets in accordance with s. NR 810.09.
NR 811.48(9)(c)(c) Tablet hoppers.
NR 811.48(9)(c)1.1. The tablet hopper shall be sized to provide a minimum of 2 days of supply assuming average day consumption of the tablets.
NR 811.48(9)(c)2.2. Load cells shall be provided on the hopper so that the weight of the tablets consumed in a 24-hour period can be determined. The design shall allow for collection of the data necessary to determine the theoretical daily chlorine usage. The design shall allow any solution to be drained out of the hopper before weighing the tablets. The load cell equipment shall be capable of providing an alarm when the weight of the tablets approaches a one day supply based upon an average day use. The alarm signal shall be automatically annunciated by the water system controls. A local alarm shall be sounded or signaled by an exterior red light at the pump station if the operation of the pump station is not remotely controlled.
NR 811.48(9)(c)3.3. The tablet hopper shall include a screened air-vacuum relief device if the possibility of a vacuum condition could develop during the operation of the tablet chlorinator.
NR 811.48(9)(d)(d) Solution tank.
NR 811.48(9)(d)1.1. The open area for any pipe penetration through the walls of the solution tank shall be sealed sanitarily so that insects and foreign material cannot contaminate the chlorine solution.
NR 811.48(9)(d)2.2. The on and off operation of the process to produce chlorine solution from the tablets shall be controlled by float switches or sensors located in the solution tank.
NR 811.48(9)(d)3.3. Float switches or sensors shall be installed and wired to provide automatic shut-off and operator alarms for low and high solution level conditions. The shut-off and alarm signals shall be automatically annunciated by the water system controls. A local alarm shall be sounded or signaled by an exterior red light at the pump station if the operation of the pump station is not remotely controlled.
NR 811.48(9)(d)4.4. The tank shall be capable of being drained for maintenance purposes.
NR 811.48(9)(d)5.5. The solution tank shall be sized to keep an adequate supply of calcium hypochlorite in the tank at all times based upon the capabilities of the tablet chlorinator to produce solution and the chemical feed pump withdrawal rates necessary to achieve the required dosages.
NR 811.48(9)(e)(e) Feed water piping requirements.
NR 811.48(9)(e)1.1. The flow rate and pressure of the feed water piping shall be regulated so as to meet the design flow requirements provided by the supplier of the equipment. A shut-off valve, flow meter, and pressure gauge shall be installed on the feed water piping.
NR 811.48(9)(e)2.2. Pre-treatment devices shall be installed as necessary if the feed water does not meet the water quality requirements designated for the tablet chlorinator. Any pre-treatment device shall be compatible for use in a potable water system and shall not be used unless approved by the department. A strainer-filter shall be installed on the feed water piping, if necessary.
NR 811.48(9)(e)3.3. A check valve shall be installed on the feed water piping upstream of any treatment equipment, control valve, or solenoid valve.
NR 811.48(9)(e)4.4. A solenoid valve shall be installed on the feed water piping to control the flow of water into the tablet chlorinator. The operation of the solenoid valve shall be controlled based upon float switches or sensors located in the solution tank.
NR 811.48(9)(e)5.5. Erosion type tablet chlorinators shall be provided with a control valve capable of regulating the flow of water through the erosion cell. The submittal for review to the department for an erosion-type tablet chlorinator shall include the chlorine delivery rate versus flow rate curve for the specified model.
NR 811.48(9)(f)(f) Chemical feed pumps.
NR 811.48(9)(f)1.1. The chemical feed pump shall be wired to operate in association with the well or service pump as required by s. NR 811.39 (4).
NR 811.48(9)(f)2.2. A tablet chlorinator producing calcium hypochlorite solution shall use a chemical feed pump installed in compliance with s. NR 811.39 (2), or a centrifugal pump.
NR 811.48(9)(f)3.3. Centrifugal pumps shall be sized to match or exceed the maximum head condition at the point of injection.
NR 811.48(9)(f)4.4. Flow paced chemical feed pumps installed in compliance with s. NR 811.39 (2) or centrifugal pumps with variable speed motors shall be incorporated into the design if the flow rate of the water being treated may vary based upon automatic control of the well or service pump. The requirements of s. NR 811.39 (2) (d) shall be met.
NR 811.48(9)(g)(g) Chemical injection location.
NR 811.48(9)(g)1.1. Tablet chlorinator chemical feed pumps shall discharge at locations and in a manner that complies with the installation requirements of s. NR 811.39 (2) (f).
NR 811.48(9)(g)2.2. When a centrifugal pump will discharge at a point not under continuous positive pressure, the outlet piping between the centrifugal pump and the point of chemical injection shall be installed with a vertical pipe loop that will extend to a height that is a minimum of 12 inches above the top of the solution tank and the location of the chemical addition pipe connection with the water system piping. A vacuum relief valve shall be installed on the top of the pipe loop. As an alternative to the installation of a vertical pipe loop, an electrically operated shut-off valve on the outlet piping, wired to operate in series with the operation of the well or service pump motor and the chemical feed pump, may be installed.
NR 811.48(9)(h)(h) Centrifugal pump discharge piping. The outlet piping of a centrifugal pump shall also be provided with a check valve and a manually operated shut-off valve. These valves shall be installed upstream of any pipe loop or electrically operated shut-off valve as required by par. (g) 2.
NR 811.48(10)(10)Sodium chlorite for chlorine dioxide generation. Proposals for the storage and use of sodium chlorite shall be submitted to the department for approval. Department approval shall be obtained prior to the preparation of final plans and specifications. Provision shall be made for proper storage and handling of sodium chlorite to eliminate any danger of fire or explosion.
NR 811.48(10)(a)(a) Storage.
NR 811.48(10)(a)1.1. Sodium chlorite shall be stored by itself in a separate room and preferably shall be stored in an outside building detached from the water treatment facility. Sodium chlorite shall be stored away from organic materials with which it could react violently.
NR 811.48(10)(a)2.2. Storage structures shall be constructed of noncombustible materials.
NR 811.48(10)(a)3.3. If the storage structure is located in an area where a fire may occur, water shall be available to keep the sodium chlorite area cool enough to prevent heat induced explosive decomposition of the sodium chlorite.
NR 811.48(10)(b)(b) Handling.
NR 811.48(10)(b)1.1. Care shall be taken to prevent spillage of sodium chlorite.
NR 811.48(10)(b)2.2. An emergency plan of operation shall be available for the clean up of any spillage.
NR 811.48(10)(b)3.3. Storage drums containing sodium chlorite shall be thoroughly flushed and the waste shall be discharged to an acceptable location prior to recycling or disposal.
NR 811.48(10)(c)(c) Feeders.
NR 811.48(10)(c)1.1. Chemical feed pumps shall meet the requirements of s. NR 811.39 (2).
NR 811.48(10)(c)2.2. Tubing for conveying sodium chlorite or chlorine dioxide solutions shall be Type 1 PVC, polyethylene or materials recommended by the manufacturer.
NR 811.48(10)(c)3.3. Chemical feeders may be installed in chlorine gas rooms if sufficient space is provided or in separate rooms meeting the requirements of subs. (5) and (6).
NR 811.48(10)(c)4.4. Feed lines shall be installed in a manner to prevent formation of gas pockets and shall terminate at a point of positive pressure.
NR 811.48(10)(c)5.5. Check valves shall be provided to prevent the backflow of chlorine into the sodium chlorite line.
NR 811.48 HistoryHistory: CR 09-073: cr. Register November 2010 No. 659, eff. 12-1-10; CR 22-074: am. (1) (a) 2. to 4., (b), (4) (title), (5) (title), r. (5) (e), am. (6) (b), (7) (a), r. and recr. (8) Register January 2024 No. 817, eff. 2-1-24.
NR 811.49NR 811.49Filtration — gravity. The application of any type of gravity filter and media shall be supported by water quality data representing a period of use sufficient to characterize any variations in water quality. Experimental or pilot plant treatment studies may be required to demonstrate the applicability of the method or rate of filtration proposed. Pressure filters will not be approved for surface water applications. The following specific requirements shall be met:
NR 811.49(1)(1)Rapid rate gravity filters.
NR 811.49(1)(a)(a) Pretreatment. Rapid rate gravity filters may only be utilized after coagulation, flocculation and sedimentation.
NR 811.49(1)(b)(b) Number. At least 2 filter units or cells shall be provided. Provisions shall be made to meet the plant design capacity at the approved filtration rate with one filter out of service. If only 2 units or cells are provided, each shall be capable of meeting the plant design capacity, normally the projected maximum daily demand.
NR 811.49(1)(c)(c) Rate of filtration. The permissible rate of filtration shall be determined after consideration of factors such as raw water quality, degree of pretreatment provided, filter media, water quality control parameters, competency of operating personnel, and other factors required by the department. If effective coagulation, flocculation, sedimentation, and filtration processes are to be utilized with relatively clean water sources, the following filtration rates may be approved:
In all cases, the filtration rate shall be proposed and justified by the design engineer and shall be approved by the department prior to the preparation of final plans and specifications. The department may approve higher rates than indicated in this paragraph with sufficient justification by the design engineer or through pilot testing under s. NR 811.44.
NR 811.49(1)(d)(d) Structural details and hydraulics. The filter structure shall be designed to provide:
NR 811.49(1)(d)1.1. Vertical walls within the filter.
NR 811.49(1)(d)2.2. No protrusion of the filter walls or other structures into the filter media or the area between the top of the media and the high water line during backwashing.
NR 811.49(1)(d)3.3. Cover by superstructure.
NR 811.49(1)(d)4.4. Head room to permit normal inspection and operation.
NR 811.49(1)(d)5.5. Minimum filter box depth of 8.5 feet.
NR 811.49(1)(d)6.6. Minimum water depth over the surface of the media of 3 feet.
NR 811.49(1)(d)7.7. Trapped effluent pipe to prevent backflow of air to the bottom of the filters.
NR 811.49(1)(d)8.8. Prevention of floor drainage to the filter with a minimum 4-inch curb around the filters.
NR 811.49(1)(d)9.9. Prevention of flooding by providing an overflow if this is not provided in a pretreatment unit.
NR 811.49(1)(d)10.10. Maximum velocity of treated water in the pipe and conduits to the filter of 2 feet per second.
NR 811.49(1)(d)11.11. Cleanouts and straight alignment for influent pipes or conduits where solids loading is heavy or following lime-soda softening.
NR 811.49(1)(d)12.12. Washwater drain capacity to carry maximum backwash flow.
NR 811.49(1)(d)13.13. Walkways around filters not less than 24 inches wide.
NR 811.49(1)(d)14.14. Safety handrails or walls around the filter areas adjacent to walkways.
NR 811.49(1)(d)15.15. Construction to prevent cross connections and common walls between potable and nonpotable water.
NR 811.49(1)(d)16.16. Washwater troughs.
NR 811.49(1)(e)(e) Washwater troughs. Washwater troughs shall be designed to provide:
NR 811.49(1)(e)1.1. A bottom elevation above the maximum level of expanded media during washing.
NR 811.49(1)(e)2.2. A 2-inch freeboard at the maximum rate of wash.
NR 811.49(1)(e)3.3. A top or edge which is all at the same elevation.
NR 811.49(1)(e)4.4. Spacing so that each trough serves the same number of square feet of filter area.
NR 811.49(1)(e)5.5. A maximum horizontal travel of suspended particles not exceeding 3 feet in reaching the trough.
NR 811.49(1)(f)(f) Filter material. The media shall be clean silica sand or other natural or synthetic media approved by the department and shall meet the following general requirements: a depth of not less than 24 inches; an effective size of the smallest material no greater than 0.45 mm to 0.55 mm, depending upon the quality of the raw water; a uniformity coefficient of the smallest material not greater than 1.65; a minimum of 12 inches of media with an effective size range no greater than 0.45 mm to 0.55 mm; and a specific gravity greater than other filtering materials within the filter. The following specific requirements shall be met:
NR 811.49(1)(f)1.1. ‘Sand.’ Sand shall have an effective size of 0.45 mm to 0.55 mm, a uniformity coefficient of not greater than 1.65, specific gravity greater than 2.5 and an acid solubility less than 5 percent.
NR 811.49(1)(f)2.2. ‘Anthracite.’ Filter anthracite shall consist of clean, hard, and durable anthracite coal particles of various sizes. Non-anthracite material may not be blended. Anthracite used as the only media shall have an effective size from 0.45 mm to 0.55 mm and a uniformity coefficient not greater than 1.65. Anthracite used to cap sand filters shall have an effective size from 0.8 mm to 1.2 mm and a uniformity coefficient not greater than 1.7. Effective size of anthracite for iron and manganese removal from potable groundwater shall be a maximum of 0.8 mm. Effective sizes greater than 0.8 mm may be approved by the department based upon onsite pilot plant studies. Anthracite shall have a specific gravity greater than 1.4 and an acid solubility less than 5%.
NR 811.49(1)(f)3.3. ‘Granular activated carbon (GAC).’
NR 811.49(1)(f)3.a.a. Granular activated carbon as a single media may be considered only after pilot or full scale testing and with prior approval of the department.
NR 811.49(1)(f)3.b.b. The media shall meet the basic specifications for filter media as provided in this paragraph except that larger size media may be allowed by the department where full scale tests have demonstrated that treatment goals can be met under all conditions.
NR 811.49(1)(f)3.c.c. There shall be provisions for a free chlorine residual and adequate contact time in the water following the filters and prior to distribution.
NR 811.49(1)(f)3.d.d. There shall be means for periodic treatment of filter material for control of bacterial and other growth.
NR 811.49(1)(f)3.e.e. Provisions shall be made for frequent replacement or regeneration of granular activated carbon if used for filtration.
NR 811.49(1)(f)4.4. ‘High density sand.’ High density sand shall consist of hard durable, and dense grain garnet, ilmenite, hematite, magnetite, or associated minerals of those ores that will resist degradation during handling and use and shall meet all of the following:
NR 811.49(1)(f)4.a.a. Contain at least 95% of the associated material with a specific gravity of 3.8 or higher.
NR 811.49(1)(f)4.b.b. Have an effective size of 0.2 to 0.3 mm.
NR 811.49(1)(f)4.c.c. Have a uniformity coefficient of not greater than 1.65.
NR 811.49(1)(f)4.d.d. Have an acid solubility less than 5%.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.