This is the preview version of the Wisconsin State Legislature site.
Please see http://docs.legis.wisconsin.gov for the production version.
NR 811.47(7)(f)(f) Tube or plate settlers. Proposals for settler unit clarification shall include pilot plant or a full scale demonstration or both satisfactory to the department prior to the preparation of final plans and specifications for approval. Settler units consisting of variously shaped tubes or plates which are installed in multiple layers and at an angle to the flow, may be used for sedimentation, following flocculation. Tube or plate settler installations shall meet the following:
NR 811.47(7)(f)1.1. ‘Inlet and outlet considerations.’ Design the inlets and outlets to maintain velocities suitable for settling in the basin and to minimize short-circuiting.
NR 811.47(7)(f)2.2. ‘Drainage.’ Drain piping from the settler units shall be sized to facilitate a quick flush of the settler units and to prevent flooding other portions of the plant.
NR 811.47(7)(f)3.3. ‘Protection from freezing.’ Units shall be located within a plant or within a covered basin.
NR 811.47(7)(f)4.4. ‘Application rate for tubes.’ A maximum application rate of 2 gallons per minute per square foot of cross-sectional area, unless higher rates are successfully shown through pilot plant or in-plant demonstration studies and are approved by the department.
NR 811.47(7)(f)5.5. ‘Application rate for plates.’ A maximum plate loading rate of 0.5 gallons per minute per square foot, based on 80 percent of the projected horizontal plate area.
NR 811.47(7)(f)6.6. ‘Flushing lines.’ Flushing lines shall be provided to facilitate maintenance and shall be properly protected against backflow or back siphonage.
NR 811.47(7)(f)7.7. ‘Placement.’ Modules shall be placed in zones of stable hydraulic conditions and in areas nearest effluent launders for basins not completely covered by the modules.
NR 811.47(7)(f)8.8. ‘Inlets and outlets.’ Inlets and outlets shall conform with par. (d) 2. and 3.
NR 811.47 HistoryHistory: CR 09-073: cr. Register November 2010 No. 659, eff. 12-1-10; CR 22-074: am. (intro.), (7) (b) 1. Register January 2024 No. 817, eff. 2-1-24.
NR 811.48NR 811.48Chlorination. Chlorine installations shall meet the following requirements:
NR 811.48(1)(1)Chlorination equipment.
NR 811.48(1)(a)(a) Type. The following types of chemical feed equipment may be used to feed chlorine:
NR 811.48(1)(a)1.1. Solution-feed-gas-type chlorinators.
NR 811.48(1)(a)2.2. Positive displacement diaphragm type pumps.
NR 811.48(1)(a)3.3. Digitally controlled constant stroke length positive displacement type pumps.
NR 811.48(1)(a)4.4. Peristaltic type pumps.
NR 811.48(1)(a)5.5. Tablet chlorinator type.
NR 811.48(1)(b)(b) Capacity. The chlorinator capacity shall be such that a free chlorine dose of at least 2 mg/L can be attained when maximum flow rates coincide with anticipated maximum chlorine demands. Liquid chemical feed equipment shall be designed to operate in accordance with the requirements under s. NR 811.39 (2) (c). Solution-feed-gas-type chlorination chemical feed equipment shall be designed to operate between 10 percent and 70 percent of the rotameter capacity. This may require that 2 rotameters be provided, one for normal feed rates and one for emergency feed rates. For all chemical feed systems, the emergency feeder setting shall be designed to provide a minimum of 2 mg/L of chlorine.
NR 811.48(1)(c)(c) Standby equipment. Where chlorination is necessary for protection of the water supply, standby equipment of sufficient capacity shall be available to replace the largest unit during shut-downs. Spare parts shall be made available to replace parts subject to scaling, wear, and breakage.
NR 811.48(1)(d)(d) Automatic proportioning. Automatic proportioning chlorinators shall be required where the rate of flow of the water is not reasonably constant or where the rate of flow of the water is not manually controlled.
NR 811.48(2)(2)Point of application. Chlorine application points shall meet the following requirements:
NR 811.48(2)(a)(a) Chlorine shall be applied at a point which will provide the maximum contact time. Provisions shall be made to minimize short-circuiting.
NR 811.48(2)(b)(b) At plants treating surface water, piping provisions shall be made for applying chlorine to the raw water, settled or clarified water, filtered water, and the plant effluent.
NR 811.48(2)(c)(c) At plants treating groundwater, provision shall be made for applying chlorine to the raw water, the clearwell inlet, and the discharge piping as applicable.
NR 811.48(2)(d)(d) At plants treating groundwater where CT is required by the department, provision shall be made for applying chlorine to the raw water, at the inlet to all CT reservoir detention basins, and the high-lift pump discharge piping as required by the department.
NR 811.48(3)(3)Residual testing equipment. Chlorine residual testing equipment shall meet the following requirements:
NR 811.48(3)(a)(a) Chlorine residual testing methodology shall be as specified in s. NR 809.563 (2), Table R. The equipment shall enable measurement of residuals to the nearest 0.1 mg/1 in the range below 0.5 mg/1 and to the nearest 0.2 mg/1 between 0.5 mg/1 to 2.0 mg/1.
NR 811.48 NoteNote: It is recommended that all systems, at a minimum, use an instrument using the DPD colorimetric method with a digital readout and a self contained light source. Automatic chlorine residual pacers and recorders are recommended where the chlorine demand varies appreciably over a short period of time.
NR 811.48(3)(b)(b) Water systems that rely on chlorination for inactivation of bacteria or other microorganisms present in the source water shall have continuous chlorine residual analyzers and other equipment that automatically shut down the facility when the chlorine residuals required by the department are not met. The department may approve less than continuous monitoring for municipal water systems serving 3,300 or fewer people and other-than-municipal water systems on a case-by-case basis provided that replacement measures or practices are implemented to provide comparable public health protection.
NR 811.48(4)(4)Gas chlorinator piping. The water supply piping shall be designed to prevent contamination of the treated water supply by sources of impure or unknown quality. Pipes carrying elemental liquid or dry gaseous chlorine under pressure shall be Schedule 80 seamless steel tubing or other materials recommended by the Chlorine Institute. PVC pipe may not be used. Chlorine solution piping and fittings shall be rubber, PVC, polyethylene, or other materials recommended by the Chlorine Institute.
NR 811.48(5)(5)Chlorine gas housing. Chlorine gas feed and storage installations shall meet the following requirements:
NR 811.48(5)(a)(a) Chlorine gas feed and storage installations shall be separated from other operating areas by gas-tight rooms or enclosures in order to prevent injury to personnel and damage to equipment.
NR 811.48(5)(b)(b) Chlorine gas rooms shall be provided with a safety glass inspection window installed in an interior wall or exterior door to permit viewing of the interior of the room and the equipment.
NR 811.48(5)(c)(c) Chlorine gas rooms shall be provided with a minimum of one door having emergency or panic hardware opening outward to the building exterior. Rooms may have additional doors to the building exterior.
NR 811.48(5)(d)(d) Chlorine gas rooms shall be heated to prevent freezing and insure proper operation of the equipment.
NR 811.48(5)(f)(f) Full and empty cylinders of chlorine gas shall be:
NR 811.48(5)(f)1.1. Isolated from operating areas.
NR 811.48(5)(f)2.2. Restrained in position to prevent movement of the cylinders.
NR 811.48(5)(f)3.3. Stored in rooms separate from ammonia storage.
NR 811.48(5)(f)4.4. Stored in areas not in direct sunlight or exposed to excessive heat.
NR 811.48(5)(g)(g) Pressurized chlorine feed lines may not carry chlorine gas beyond the chlorine room. Vacuum chlorine feed lines may carry gas beyond the chlorine room if the chlorine lines are either schedule 40 polyethylene tubing or schedule 80 PVC pipe. Polyethylene tubing shall be enclosed in a protective conduit running from the chlorine room to a point near the ejector. The end of the conduit in the chlorine room shall be sealed. Polyethylene tubing connections shall be made using tube adaptors especially designed for this purpose. PVC pipe joints may be socket welded using PVC cement or threaded using polytetrafluoroethylene pipe joint tape.
NR 811.48(5)(h)(h) Premanufactured chlorine cabinets may be used for retrofit situations only. These cabinets shall have an observation window, fan, air intake, and light as required in par. (b) and sub. (6) for normal chlorine gas rooms.
NR 811.48 NoteNote: It is recommended that these cabinets not be placed on the sunny side of the building.
NR 811.48(6)(6)Ventilation of chlorine gas rooms. Ventilation of chlorine gas rooms shall meet the following requirements:
NR 811.48(6)(a)(a) One complete air change per minute shall be provided when the room is occupied.
NR 811.48(6)(b)(b) The exhaust fan suction shall be within 12 inches of the floor as far as practical from the door and air inlet, with the point of discharge located to avoid contamination of air inlets to other rooms and structures, and to avoid being blocked by snow or other obstructions.
NR 811.48(6)(c)(c) Air inlets shall be located near the ceiling and controlled to prevent adverse temperature variations.
NR 811.48(6)(d)(d) Louvers for the chlorine room air intake and exhaust shall be corrosion resistant and shall facilitate airtight closure.
NR 811.48(6)(e)(e) The exhaust fan switch shall be located outside the entrance to the chlorine room with a signal light indicating fan operation when the fan can be controlled from more than one point. Outside switches shall be protected from vandalism. As an alternative, the fan may be controlled by an automatic door switch with manual shut-off.
NR 811.48 NoteNote: It is recommended that switches for fans and lights be interlocked for simultaneous operation.
NR 811.48(6)(f)(f) Vent lines from feeders and storage shall discharge to the outside atmosphere, above grade, in a downward direction, be screened, and be located as required in par. (b). In addition, vent lines shall conform with the manufacturer’s installation recommendations.
NR 811.48(7)(7)Safety equipment. The following safety equipment shall be provided when chlorine gas is used:
NR 811.48(7)(a)(a) Respiratory protection equipment, known as gas masks, meeting the requirements of the National Institute for Occupational Safety and Health (NIOSH) shall be available where chlorine gas is handled, and shall be stored at a convenient heated location, but not inside any room where chlorine is used or stored. The gas masks shall use compressed air, have at least a 30-minute capacity, and be compatible with or exactly the same as the gas masks used by the fire department responsible for the plant. The gas masks shall be available at all installations where chlorine gas is handled and shall be placed outside every room where chlorine gas is used or stored. At installations utilizing 150-pound, or less, cylinders, an agreement with the local fire department that has an approved type of gas mask for the fire department to handle water system chlorine gas leaks may be approved by the department. Instructions for using, testing and replacing gas mask parts shall be posted. Other protective clothing shall be provided as necessary.
NR 811.48(7)(b)(b) A bottle of concentrated ammonium hydroxide, 56 percent ammonia solution, shall be available for chlorine leak detection.
NR 811.48(7)(c)(c) If pressurized chlorine gas is present, continuous chlorine leak detection equipment shall be installed and equipped with both an audible alarm and a warning light. Automatic emergency chlorine cylinder shutdown valves shall also be provided.
NR 811.48(7)(d)(d) If ton cylinders are used, leak repair kits, approved by the Chlorine Institute, shall be available at the waterworks or a nearby fire department.
NR 811.48(8)(8)Ammonia. Ammonia chemical feed installations shall meet all of the following requirements:
NR 811.48(8)(a)(a) Gaseous ammonia. Housing and ventilation for ammoniation shall meet the requirements under subs. (5) and (6) for chlorine, except that the exhaust fan inlet shall be within 12 inches of the ceiling and the fresh air inlet shall be within 12 inches of the floor. Ammonia storage and feed facilities shall be separate from chlorine facilities because of the combustion hazard. A plastic bottle of hydrochloric acid shall be available and used for leak detection.
NR 811.48(8)(b)(b) Ammonium sulfate. Ammonium sulfate chemical feed installation shall meet the chemical storage requirements under s. NR 811.40.
NR 811.48(8)(c)(c) Aqua ammonia. Aqua ammonia installation shall meet all of the following requirements:
NR 811.48(8)(c)1.1. An aqua ammonia chemical feed and storage system shall be installed in its own dedicated room.
NR 811.48(8)(c)2.2. Bulk liquid storage tanks and day tanks shall be vented to the outside of the building and discharge downward facing with a 24-mesh corrosion resistant screen a minimum of 24 inches above grade. The chemical tank vents shall be provided with inert liquid traps.
NR 811.48(8)(c)3.3. An incompatible connector or lockout provisions shall be provided to prevent accidental addition of other chemical to the bulk liquid storage tanks.
NR 811.48(8)(c)4.4. The bulk liquid storage tanks shall be designed to avoid temperature increases that cause the ammonia vapor pressure over the aqua ammonia to exceed atmospheric pressure. The provisions shall include a means of external cooling or dilution and mixing of the contents with water without opening the bulk liquid storage tank.
NR 811.48(8)(c)5.5. An exhaust fan shall be installed to withdraw air from high points in the room and makeup air shall be allowed to enter at a low point.
NR 811.48(8)(c)6.6. The aqua ammonia feed pump, regulators, and lines shall be fitted with pressure relief vents discharging outside the building away from any air intake and with water purge lines leading back to the headspace of the bulk storage tanks.
NR 811.48(8)(c)7.7. The aqua ammonia shall be conveyed directly from a day tank to the treated water stream injector without the use of a carrier water stream unless the carrier stream is softened.
NR 811.48(9)(9)Calcium hypochlorite tablet chlorinators. Calcium hypochlorite tablet chlorinators shall meet the following design requirements:
NR 811.48(9)(a)(a) Calcium hypochlorite solution formation. The calcium hypochlorite solution shall be produced by dissolving tablets with a department approved feed water source using an erosion chamber or an upward directed spray system. The department may approve other methods or technology for producing calcium hypochlorite solution after the submittal of data from a department-approved pilot program.
NR 811.48(9)(b)(b) Tablets. The calcium hypochlorite tablets used in the chlorinator shall be supplied by the manufacturer of the tablet chlorinator equipment. The supplier of the calcium hypochlorite tablets shall have obtained NSF/ANSI Standard 60 certification for the tablets in accordance with s. NR 810.09.
NR 811.48(9)(c)(c) Tablet hoppers.
NR 811.48(9)(c)1.1. The tablet hopper shall be sized to provide a minimum of 2 days of supply assuming average day consumption of the tablets.
NR 811.48(9)(c)2.2. Load cells shall be provided on the hopper so that the weight of the tablets consumed in a 24-hour period can be determined. The design shall allow for collection of the data necessary to determine the theoretical daily chlorine usage. The design shall allow any solution to be drained out of the hopper before weighing the tablets. The load cell equipment shall be capable of providing an alarm when the weight of the tablets approaches a one day supply based upon an average day use. The alarm signal shall be automatically annunciated by the water system controls. A local alarm shall be sounded or signaled by an exterior red light at the pump station if the operation of the pump station is not remotely controlled.
NR 811.48(9)(c)3.3. The tablet hopper shall include a screened air-vacuum relief device if the possibility of a vacuum condition could develop during the operation of the tablet chlorinator.
NR 811.48(9)(d)(d) Solution tank.
NR 811.48(9)(d)1.1. The open area for any pipe penetration through the walls of the solution tank shall be sealed sanitarily so that insects and foreign material cannot contaminate the chlorine solution.
NR 811.48(9)(d)2.2. The on and off operation of the process to produce chlorine solution from the tablets shall be controlled by float switches or sensors located in the solution tank.
NR 811.48(9)(d)3.3. Float switches or sensors shall be installed and wired to provide automatic shut-off and operator alarms for low and high solution level conditions. The shut-off and alarm signals shall be automatically annunciated by the water system controls. A local alarm shall be sounded or signaled by an exterior red light at the pump station if the operation of the pump station is not remotely controlled.
NR 811.48(9)(d)4.4. The tank shall be capable of being drained for maintenance purposes.
NR 811.48(9)(d)5.5. The solution tank shall be sized to keep an adequate supply of calcium hypochlorite in the tank at all times based upon the capabilities of the tablet chlorinator to produce solution and the chemical feed pump withdrawal rates necessary to achieve the required dosages.
NR 811.48(9)(e)(e) Feed water piping requirements.
NR 811.48(9)(e)1.1. The flow rate and pressure of the feed water piping shall be regulated so as to meet the design flow requirements provided by the supplier of the equipment. A shut-off valve, flow meter, and pressure gauge shall be installed on the feed water piping.
NR 811.48(9)(e)2.2. Pre-treatment devices shall be installed as necessary if the feed water does not meet the water quality requirements designated for the tablet chlorinator. Any pre-treatment device shall be compatible for use in a potable water system and shall not be used unless approved by the department. A strainer-filter shall be installed on the feed water piping, if necessary.
NR 811.48(9)(e)3.3. A check valve shall be installed on the feed water piping upstream of any treatment equipment, control valve, or solenoid valve.
NR 811.48(9)(e)4.4. A solenoid valve shall be installed on the feed water piping to control the flow of water into the tablet chlorinator. The operation of the solenoid valve shall be controlled based upon float switches or sensors located in the solution tank.
NR 811.48(9)(e)5.5. Erosion type tablet chlorinators shall be provided with a control valve capable of regulating the flow of water through the erosion cell. The submittal for review to the department for an erosion-type tablet chlorinator shall include the chlorine delivery rate versus flow rate curve for the specified model.
NR 811.48(9)(f)(f) Chemical feed pumps.
NR 811.48(9)(f)1.1. The chemical feed pump shall be wired to operate in association with the well or service pump as required by s. NR 811.39 (4).
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.