NR 811.77 Common casing crossings. NR 811.78 Water loading stations. Subchapter XI — Water Pressure Booster Stations
NR 811.81 Pumps and pressures. NR 811.82 Storage requirements. NR 811.83 Emergency power requirements. NR 811.84 Station requirements. Subchapter XII — Waste Disposal
NR 811.851 Sanitary wastes. NR 811.852 Floor drainage. NR 811.853 Backwash wastewater from iron and manganese filters. NR 811.854 Brine wastes from ion exchange plants. NR 811.855 Wastewater from reverse osmosis plants. NR 811.856 Water treatment plant wastewater radionuclide content compliance with the unity equation. NR 811.857 Backwash wastewater from lime softening water treatment plants. NR 811.858 Lime softening sludge. NR 811.860 Backwash wastewater from surface water treatment plants. NR 811.861 Alum or other coagulant sludge. NR 811.862 Recycling backwash wastewater. Subchapter XIII — Aquifer Storage Recovery
NR 811.88 ASR well performance requirements. NR 811.89 Well construction requirements for ASR wells. NR 811.90 Equipment, appurtenances and piping for ASR wells and ASR systems. NR 811.91 ASR system pilot studies. NR 811.92 ASR system development testing. NR 811.93 Operating an ASR system. Ch. NR 811 NoteNote: Chapter NR 111 as it existed on April 30, 1992 was repealed and a new chapter NR 811 was created effective May 1, 1992. Chapter NR 811 as it existed on November 30, 2010, was repealed and a new chapter NR 811 was created effective December 1, 2010.
NR 811.01NR 811.01 Applicability. This chapter governs the general operation, design and construction of community water systems and the construction of any water system serving 7 or more single family homes, 10 or more duplex living units, 10 or more mobile homes, 10 or more condominium units or 10 or more apartment units. One duplex equals 2 living units. The standards for design and construction shall be considered minimum standards for new facilities and the minimum standards to which existing facilities shall be upgraded when improvements are undertaken at those facilities except for systems where all of the living units are owned by a single owner and the owner provides information indicating that less than 25 year-round residents will be served. These standards may be imposed on a case-by-case basis to existing facilities when the department determines that a health risk exists due to the water system. The owner shall be responsible for ensuring that the requirements of this chapter are met. NR 811.01 NoteNote: The authority to promulgate and enforce these rules is contained in chs. 280 and 281, Stats. Pursuant to s. 299.97, Stats., any person who violates this chapter shall forfeit not less than $10 nor more than $5,000 for each violation. Each day of continued violation is a separate offense. NR 811.02NR 811.02 Definitions. In this chapter: NR 811.02(1g)(1g) “Air gap” means the unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank or plumbing fixture and the flood level rim or spill level of the receptacle. NR 811.02(1r)(1r) “ANSI” means the American National Standards Institute. NR 811.02 NoteNote: The ANSI address is 25 West 43rd St, New York, NY 10036.
NR 811.02(2)(2) “API” means the American Petroleum Institute. NR 811.02 NoteNote: The API address is 1220 L Street NW, Washington DC 20005-4070.
NR 811.02(3)(3) “Approval” means the written approval of the department for any project requiring approval pursuant to s. 281.41, Stats., and s. NR 108.03 for community systems. NR 811.02(4)(4) “Aquifer storage recovery” or “ASR” means placement of treated drinking water underground through a well for the purpose of storing and later recovering the water through the same well for potable use. NR 811.02 NoteNote: Underground placement of water for the purpose of restoring an aquifer is not included in the definition of “aquifer storage recovery” or “ASR.”
NR 811.02(5)(5) “ASR system” means all of the ASR wells, ASR monitoring wells and related appurtenances within a municipal water system and any interconnected public water system served by the municipal water system. NR 811.02(6)(6) “ASTM” or “ASTM International” means the organization formerly knows as the American Society for Testing and Material. NR 811.02 NoteNote: The ASTM or ASTM International address is 100 Barr Harbor Drive, PO Box C700, West Conshohocken, Pennsylvania 19148-2959.
NR 811.02(7)(7) “AWWA” means the American Water Works Association. NR 811.02 NoteNote: The AWWA address is 6666 West Quincy Avenue, Denver, Colorado 80235.
NR 811.02(8)(8) “Blackwater” means wastewater contaminated by human body waste, toilet paper and any other material intended to be deposited in a receptor designed to receive urine or feces. NR 811.02(9)(9) “Building” means a structure for support, shelter, or enclosure of persons or property. NR 811.02(10)(10) “Building drain” means horizontal piping within or under a building, installed below the lowest fixture or the lowest floor level from which fixtures can drain by gravity to the building sewer. NR 811.02(11)(11) “Building drain, storm” means a building drain which conveys storm water, clear water, or both. NR 811.02(12)(12) “Building sewer” means that part of the drain system not within or under a building which conveys its discharge to a public sewer, private interceptor main sewer, private onsite wastewater treatment system or other point of discharge or dispersal. NR 811.02(13)(13) “Building sewer, sanitary” means a building sewer which conveys wastewater consisting in part of domestic wastewater. NR 811.02(14)(14) “Building sewer, storm” means a building sewer which conveys storm water, clear water, or both. NR 811.02(15)(15) “Chlorine Institute” means the Chlorine Institute, Inc. NR 811.02 NoteNote: The Chlorine Institute address is 1300 Wilson Boulevard, Arlington, VA 22209.
NR 811.02(16)(16) “Community water system” means a public water system which serves at least 15 service connections used by year-round residents or regularly serves at least 25 year-round residents. Any water system serving 7 or more single family homes, 10 or more mobile homes, 10 or more apartment units, 10 or more duplex living units or 10 or more condominium units shall be considered a community water system unless information is provided by the owner indicating that 25 year-round residents will not be served. NR 811.02(17)(17) “Cross connection” means a connection or potential connection between any part of a water supply system and another environment containing substances in a manner that, under any circumstances, would allow the substances to enter the water supply system by means of back siphonage or back pressure. NR 811.02(18)(18) “CT” or “CT calc” is the product of the “residual disinfectant concentration” (C) in mg/l determined before or at the first customer, and the corresponding “disinfectant contact time” (T) in minutes, i.e., “C” x “T”. If a public water system applies disinfectants at more than one point prior to the first customer, the public water system owner or operator shall determine the CT of each disinfectant sequence before or at the first customer, to determine the total percent inactivation or “total inactivation ratio.” The inactivation ratio for a single disinfectant sequence is: where “CTtable” is the CT value required for the target organism and the target level of inactivation. The sum of the inactivation ratios, or total inactivation ratio for a series of disinfection sequences is:
and is calculated by adding together the inactivation ratio for each disinfection sequence. In determining the total inactivation ratio, the public water system owner or operator shall determine the residual disinfectant concentration of each sequence and corresponding contact time before any subsequent disinfection application points. A total inactivation ratio equal to or greater than 1.0 is assumed to provide the target level of disinfection of the target organism.
NR 811.02(19)(19) “Department” means the department of natural resources. NR 811.02(19m)(19m) “Dimension ratio” means the specified outside diameter of the pipe divided by the specified minimum wall thickness. NR 811.02(20)(20) “Disinfectant contact time” (“T” in CT calculations) means the time in minutes that it takes for water to move from the point of disinfectant application or the previous point of disinfectant residual measurement to a point before or at the point where residual disinfectant concentration (“C”) is measured. Where only one “C” is measured, “T” is the time in minutes that it takes for water to move from the point of disinfectant application to a point before or where residual disinfectant concentration (“C”) is measured. Where more than one “C” is measured, “T” is determined as follows: NR 811.02(20)(a)(a) For the first measurement of “C”, the time in minutes that it takes for water to move from the first or only point of disinfectant application to a point before or at the point where the first “C” is measured. NR 811.02(20)(b)(b) For subsequent measurements of “C”, the time in minutes that it takes for water to move from the previous “C” measurement point to the “C” measurement point for which the particular “T” is being calculated. Disinfectant contact time in pipelines shall be calculated based on “plug flow” by dividing the internal volume of the pipe by the maximum hourly flow rate through the pipe. Disinfectant contact time within mixing basins and storage reservoirs shall be determined by tracer studies or other department approved equivalent demonstration. NR 811.02(21)(21) “Disinfection profile” means a summary of daily Giardia lamblia inactivation through the treatment plant. The procedure for developing a disinfection profile is contained in s. NR 810.34. NR 811.02(22)(22) “Displacement zone” means the 3-dimensional subsurface region surrounding an aquifer storage recovery well into which treated drinking water is placed for storage and later recovery. NR 811.02(23)(23) “Distribution system” means all pipes or conduits by which water is delivered to consumers except piping and fixtures inside buildings served, water services and private water mains as defined in ch. SPS 381. NR 811.02(25)(25) “Dry land access” means a vehicular access route which is above the regional flood elevation and which connects land located in the floodplain to land outside the floodplain. NR 811.02(26)(26) “Energy efficient” means that the proposed improvement will consume the minimum amount of energy to meet operational performance requirements throughout the life of the facility or system. NR 811.02(27)(27) “Entry point” means a location in the water system after treatment or chemical addition, if any, but prior to the distribution system. A sample collected in the distribution system may be considered an entry point sample if the department has determined it is more representative of the water sources. NR 811.02(28)(28) “Filtration” means a process for removing particulate matter from water by passage through porous media. NR 811.02(29)(29) “Flocculation” means a process to enhance agglomeration or collection of smaller floc particles into larger, more easily settleable or filterable particles through gentle stirring by hydraulic or mechanical means. NR 811.02(29m)(29m) “Frazil ice” means ice formed in supercooled water as small particles moving turbulently enough to prevent the formation of a sheet of ice. NR 811.02(30)(30) “French drain” means a buried dry well or sump that receives building domestic or floor drain wastewater or both. NR 811.02(31)(31) “Graywater” means wastewater contaminated by waste materials, exclusive of urine, feces or industrial waste, deposited into plumbing drain systems. NR 811.02(32)(32) “Groundwater” means any of the waters of the state, as defined in s. 281.01 (18), Stats., occurring in a saturated subsurface geological formation of rock or soil. NR 811.02(33)(33) “Groundwater source” means a source of groundwater obtained from horizontal collectors, infiltration lines, springs, and dug, drilled or other types of wells. NR 811.02(34)(34) “Groundwater under the direct influence of surface water” (GWUDI) means any water beneath the surface of the ground with either of the following: