NR 661.1035(3)(b)(b) Identification of operating parameter, description of monitoring device, and diagram of monitoring sensor location or locations used to comply with s. NR 661.1033 (6) (a) and (b). NR 661.1035(3)(d)(d) Date, time, and duration of each period that occurs while the control device is operating when any monitored parameter exceeds the value established in the control device design analysis as follows: NR 661.1035(3)(d)1.1. For a thermal vapor incinerator designed to operate with a minimum residence time of 0.50 second at a minimum temperature of 760°C, the period when the combustion temperature is below 760°C. NR 661.1035(3)(d)2.2. For a thermal vapor incinerator designed to operate with an organic emission reduction efficiency of 95 weight percent or greater, the period when the combustion zone temperature is more than 28 °C below the design average combustion zone temperature established as a requirement under sub. (2) (d) 3. a. NR 661.1035(3)(d)3.3. For a catalytic vapor incinerator, the period when any of the following occur: NR 661.1035(3)(d)3.a.a. Temperature of the vent stream at the catalyst bed inlet is more than 28°C below the average temperature of the inlet vent stream established as a requirement under sub. (2) (d) 3. b. NR 661.1035(3)(d)3.b.b. Temperature difference across the catalyst bed is less than 80 percent of the design average temperature difference established as a requirement under sub. (2) (d) 3. b. NR 661.1035(3)(d)4.4. For a boiler or process heater, the period when any of the following occur: NR 661.1035(3)(d)4.b.b. Position changes where the vent stream is introduced to the combustion zone from the location established as a requirement under sub. (2) (d) 3. c. NR 661.1035(3)(d)6.6. For a condenser that complies with s. NR 661.1033 (6) (b) 6. a., the period when the organic compound concentration level or readings of organic compounds in the exhaust vent stream from the condenser are more than 20 percent greater than the design outlet organic compound concentration level established as a requirement under sub. (2) (d) 3. e. NR 661.1035(3)(d)7.a.a. Temperature of the exhaust vent stream from the condenser is more than 6°C above the design average exhaust vent stream temperature established as a requirement under sub. (2) (d) 3. e. NR 661.1035(3)(d)7.b.b. Temperature of the coolant fluid exiting the condenser is more than 6°C above the design average coolant fluid temperature at the condenser outlet established as a requirement under sub. (2) (d) 3. e. NR 661.1035(3)(d)8.8. For a carbon adsorption system such as a fixed-bed carbon adsorber that regenerates the carbon bed directly on-site in the control device and complies with s. NR 661.1033 (6) (b) 7. a., period when the organic compound concentration level or readings of organic compounds in the exhaust vent stream from the carbon bed are more than 20 percent greater than the design exhaust vent stream organic compound concentration level established as a requirement under sub. (2) (d) 3. f. NR 661.1035(3)(d)9.9. For a carbon adsorption system such as a fixed-bed carbon adsorber that regenerates the carbon bed directly on-site in the control device and complies with s. NR 661.1033 (6) (b) 7. b., period when the vent stream continues to flow through the control device beyond the predetermined carbon bed regeneration time established as a requirement under sub. (2) (d) 3. f. NR 661.1035(3)(e)(e) Explanation for each period recorded under par. (d) of the cause for control device operating parameter exceeding the design value and the measures implemented to correct the control device operation. NR 661.1035(3)(f)(f) For a carbon adsorption system operated subject to requirements specified in s. NR 661.1033 (7) or (8) (b), the date when existing carbon in the control device is replaced with fresh carbon. NR 661.1035(3)(g)1.1. Date and time when control device is monitored for carbon breakthrough and the monitoring device reading. NR 661.1035(3)(g)2.2. Date when existing carbon in the control device is replaced with fresh carbon. NR 661.1035(3)(i)(i) A remanufacturer or other person that stores or treats the hazardous secondary material designating any components of a closed-vent system as unsafe to monitor pursuant to s. NR 661.1033 (15) shall record in a log that is kept at the facility the identification of closed-vent system components that are designated as unsafe to monitor in accordance with the requirements under s. NR 661.1033 (15), an explanation for each closed-vent system component stating why the closed-vent system component is unsafe to monitor, and the plan for monitoring each closed-vent system component. NR 661.1035(3)(j)1.1. The instrument identification number, the closed-vent system component identification number, and the operator name, initials, or identification number. NR 661.1035(3)(j)2.2. Date the leak was detected and the date of first attempt to repair the leak. NR 661.1035(3)(j)4.4. Maximum instrument reading measured by Method 21 in appendix A of 40 CFR part 60, incorporated by reference in s. NR 660.11, after it is successfully repaired or determined to be nonrepairable. NR 661.1035(3)(j)5.5. The words “Repair delayed” and the reason for the delay if the leak was not repaired within 15 calendar days after discovery of the leak. Documentation of the delay may include: NR 661.1035(3)(j)5.a.a. The remanufacturer or other person that stores or treats the hazardous secondary material may develop a written procedure that identifies the conditions that justify a delay of repair. In such cases, reasons for delay of repair may be documented by citing the relevant sections of the written procedure. NR 661.1035(3)(j)5.b.b. If delay of repair was caused by depletion of stocked parts, the remanufacturer or other person that stores or treats the hazardous secondary material shall document that the spare parts were sufficiently stocked on-site before depletion and the reason for depletion. NR 661.1035(4)(4) Records of the monitoring, operating, and inspection information required under sub. (3) (c) to (j) shall be maintained by the remanufacturer or other person for at least 3 years following the date of each occurrence, measurement, maintenance, corrective action, or record. NR 661.1035(5)(5) For a control device other than a thermal vapor incinerator, catalytic vapor incinerator, flare, boiler, process heater, condenser, or carbon adsorption system, the remanufacturer or other person shall record monitoring and inspection information indicating proper operation and maintenance of the control device in the facility operating record. NR 661.1035(6)(6) Up-to-date information and data used to determine whether or not a process vent is subject to the requirements in s. NR 661.1032 including supporting documentation as required by s. NR 661.1034 (4) (b) when application of the knowledge of the nature of the hazardous secondary material stream or the process by which it was produced is used, shall be recorded by the remanufacturer or other person in a log that is kept at the facility. NR 661.1035 HistoryHistory: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20; correction in (2) (d) 3. made under s. 35.17, Stats., Register August 2020 No. 776; correction in (2) (a) made under s. 13.92 (4) (b) 7., Stats., Register April 2021 No. 784. NR 661.1050NR 661.1050 Applicability. The regulations in this subchapter apply to equipment that contains hazardous secondary material excluded under the remanufacturing exclusion under s. NR 661.0004 (1) (za), unless the equipment operations are subject to the requirements of an applicable Clean Air Act regulation codified under 40 CFR part 60, 61, or 63, or subject to ch. NR 440, subchs. III and IV of ch. NR 446, or chs. NR 447 to 469. NR 661.1050 HistoryHistory: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20; correction in numbering made under s. 13.92 (4) (b) 1., Stats., and correction made under s. 35.17, Stats., Register August 2020 No. 776; correction made under ss. 13.92 (4) (b) 7. and 35.17, Stats., Register April 2021 No. 784. NR 661.1051 HistoryHistory: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20. NR 661.1052NR 661.1052 Standards: pumps in light liquid service. NR 661.1052(1)(a)(a) Except as provided in subs. (4) to (6), the remanufacturer or other person shall monitor each pump in light liquid service monthly to detect leaks by the methods specified in s. NR 661.1063 (2). NR 661.1052(1)(b)(b) The remanufacturer or other person shall check each pump in light liquid service by visual inspection each calendar week for indications of liquids dripping from the pump seal. NR 661.1052(2)(a)(a) If an instrument reading of 10,000 ppm or greater is measured, a leak is detected. NR 661.1052(2)(b)(b) If there are indications of liquids dripping from the pump seal, a leak is detected. NR 661.1052(3)(a)(a) When a leak is detected, it shall be repaired as soon as practicable, but not later than 15 calendar days after it is detected, except as provided in s. NR 661.1059. NR 661.1052(3)(b)(b) A first attempt at repair, such as tightening the packing gland, shall be made no later than 5 calendar days after each leak is detected. NR 661.1052(4)(4) Each pump equipped with a dual mechanical seal system that includes a barrier fluid system is exempt from the requirements under sub. (1), provided all of the following requirements are met: NR 661.1052(4)(a)1.1. Operated with the barrier fluid at a pressure that is at all times greater than the pump stuffing box pressure. NR 661.1052(4)(a)2.2. Equipped with a barrier fluid degassing reservoir that is connected by a closed-vent system to a control device that complies with the requirements specified in s. NR 661.1060. NR 661.1052(4)(a)3.3. Equipped with a system that purges the barrier fluid into a hazardous secondary material stream with no detectable emissions to the atmosphere. NR 661.1052(4)(b)(b) The barrier fluid system may not be a hazardous secondary material with organic concentrations 10 percent or greater by weight. NR 661.1052(4)(c)(c) Each barrier fluid system shall be equipped with a sensor that will detect failure of the seal system, the barrier fluid system, or both. NR 661.1052(4)(d)(d) Each pump shall be checked the remanufacturer or other person by visual inspection, each calendar week, for indications of liquids dripping from the pump seals. NR 661.1052(4)(e)1.1. Each sensor as described in par. (c) shall be checked by the remanufacturer or other person daily or be equipped with an audible alarm that shall be checked monthly to ensure that it is functioning properly. NR 661.1052(4)(e)2.2. A remanufacturer or other person that stores or treats the hazardous secondary material shall determine, based on design considerations and operating experience, a criterion that indicates failure of the seal system, the barrier fluid system, or both. NR 661.1052(4)(f)1.1. If there are indications of liquids dripping from the pump seal or the sensor indicates failure of the seal system, the barrier fluid system, or both based on the criterion determined in par. (e) 2., a leak is detected. NR 661.1052(4)(f)2.2. When a leak is detected, it shall be repaired as soon as practicable, but not later than 15 calendar days after it is detected, except as provided in s. NR 661.1059. NR 661.1052(4)(f)3.3. A first attempt at repair, such as relapping the seal, shall be made no later than 5 calendar days after each leak is detected. NR 661.1052(5)(5) Any pump that is designated, as described in s. NR 661.1064 (7) (b), for no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, is exempt from the requirements under subs. (1), (3), and (4) if the pump meets all of the following requirements: NR 661.1052(5)(b)(b) Operates with no detectable emissions as indicated by an instrument reading of less than 500 ppm above background as measured by the methods specified in s. NR 661.1063 (3). NR 661.1052(5)(c)(c) Is tested for compliance with par. (b) initially upon designation, annually, and at other times as requested by the department. NR 661.1052(6)(6) If any pump is equipped with a closed-vent system capable of capturing and transporting any leakage from the seal or seals to a control device that complies with the requirements specified in s. NR 661.1060, it is exempt from the requirements specified in subs. (1) to (5). NR 661.1052 HistoryHistory: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20. NR 661.1053(1)(1) Each compressor shall be equipped with a seal system that includes a barrier fluid system and that prevents leakage of total organic emissions to the atmosphere, except as provided in subs. (8) and (9). NR 661.1053(2)(2) Each compressor seal system as required under sub. (1) shall meet one of the following conditions: NR 661.1053(2)(a)(a) Operate with the barrier fluid at a pressure that is at all times greater than the compressor stuffing box pressure. NR 661.1053(2)(b)(b) Be equipped with a barrier fluid system that is connected by a closed-vent system to a control device that complies with the requirements specified in s. NR 661.1060. NR 661.1053(2)(c)(c) Be equipped with a system that purges the barrier fluid into a hazardous secondary material stream with no detectable emissions to atmosphere. NR 661.1053(3)(3) The barrier fluid may not be a hazardous secondary material with organic concentrations 10 percent or greater by weight. NR 661.1053(4)(4) Each barrier fluid system as described in subs. (1) to (3) shall be equipped with a sensor that will detect failure of the seal system, barrier fluid system, or both. NR 661.1053(5)(a)(a) Each sensor as required in sub. (4) shall be checked by the remanufacturer or other person daily or shall be equipped with an audible alarm that shall be checked monthly to ensure that it is functioning properly unless the compressor is located within the boundary of an unmanned plant site, in which case the sensor shall be checked daily. NR 661.1053(5)(b)(b) The remanufacturer or other person that stores or treats the hazardous secondary material shall determine, based on design considerations and operating experience, a criterion that indicates failure of the seal system, the barrier fluid system, or both. NR 661.1053(6)(6) If the sensor indicates failure of the seal system, the barrier fluid system, or both based on the criterion determined under sub. (5) (b), a leak is detected. NR 661.1053(7)(a)(a) When a leak is detected, it shall be repaired as soon as practicable, but not later than 15 calendar days after it is detected, except as provided under s. NR 661.1059. NR 661.1053(7)(b)(b) A first attempt at repair, such as tightening the packing gland, shall be made no later than 5 calendar days after each leak is detected. NR 661.1053(8)(8) A compressor is exempt from the requirements under subs. (1) and (2) if it is equipped with a closed-vent system capable of capturing and transporting any leakage from the seal to a control device that complies with the requirements specified in s. NR 661.1060, except as provided in sub. (9).
/exec_review/admin_code/nr/600/661
true
administrativecode
/exec_review/admin_code/nr/600/661/aa/1035/3/j/4
Department of Natural Resources (NR)
Chs. NR 600-699; Environmental Protection – Hazardous Waste Management
administrativecode/NR 661.1035(3)(j)4.
administrativecode/NR 661.1035(3)(j)4.
section
true