DOC 346.14(2)(c)2.2. An unbreakable, institution-type mirror.
DOC 346.14(2)(c)3.3. A detention strength, metal, institution-type wash basin and toilet. The wash basin and toilet may be combined in one unit. The wash basin shall have hot and cold running water.
DOC 346.14(2)(c)4.4. A rigidly constructed shelf-type table and seat which are bracketed to the wall or bolted to the floor.
DOC 346.14(2)(c)5.5. Unless s. DOC 346.15 applies, 2 or more nonremovable, collapsible, detention strength clothing and towel hooks.
DOC 346.14(2)(c)6.6. Light fixtures of detention strength and providing at least 30 foot candles at 30 inches above the floor. Lights shall have a dimming capability or there shall be a nightlight to allow for comfortable sleeping. There shall be enough illumination for observation of juveniles during security checks.
DOC 346.14(2)(d)(d) There shall be no exposed heating pipes, radiators or controls in cells.
DOC 346.14(2)(e)(e) There shall be a release system designed to unlock cell doors individually and as a group from a single point outside the confinement area.
DOC 346.14(3)(3)Dormitories.
DOC 346.14(3)(a)(a) A juvenile detention facility may use dormitories in addition to cells for the secure detention of juveniles.
DOC 346.14(3)(b)(b) Each dormitory shall be designed for a minimum of 3 and a maximum of 8 juveniles.
DOC 346.14(3)(c)(c) If a juvenile detention facility contains one dormitory, it shall have a minimum of 2 cells designed and used for single occupancy.
DOC 346.14(3)(d)(d) If more than one dormitory is built, the number of dormitory beds may not exceed 50% of the rated bed capacity of the juvenile detention facility.
DOC 346.14(3)(e)(e) If, based on all the criteria under s. DOC 346.10, a juvenile detention facility determines that placement of a juvenile in a dormitory may jeopardize the health or safety of the juvenile, other juveniles in the facility, staff or the community, the juvenile may not be placed in a dormitory.
DOC 346.14(3)(f)(f) Each dormitory shall have all of the following:
DOC 346.14(3)(f)1.1. A minimum combined sleeping area and adjacent day room space of 70 square feet per juvenile based on rated bed capacity of the dormitory, excluding toilets, showers and lavatories.
DOC 346.14(3)(f)2.2. A minimum floor to ceiling height of 8 feet.
DOC 346.14(3)(f)3.3. Non-locking doors on sleeping rooms, if separate sleeping rooms are provided.
DOC 346.14(3)(f)4.4. Unrestricted physical access to the day room, lavatories and toilets.
DOC 346.14(3)(f)5.5. A rigidly constructed metal bed with the frame bracketed to the wall or bolted to the floor for each juvenile based on the rated bed capacity of the dormitory.
DOC 346.14(3)(f)6.6. For facilities constructed or substantially remodeled after November 1, 2010, all upper bunks equipped with an anti-rollout plate.
DOC 346.14(3)(f)7.7. Detention strength washbasins and toilets.
DOC 346.14(3)(f)8.8. Unbreakable, detention strength mirrors sufficient for the number of juveniles confined.
DOC 346.14(3)(f)9.9. Detention strength tables and seating in the day room based on the rated bed capacity of the dormitory.
DOC 346.14(3)(f)10.10. Two nonremovable, collapsible, detention strength clothing and towel hooks for each juvenile confined based on the rated bed capacity of the dormitory.
DOC 346.14(3)(f)11.11. Detention strength light fixtures that provide at least 30 foot candles at 30 inches above the floor. Lights shall have a dimming capability or there shall be a nightlight to allow for comfortable sleeping. There shall be enough illumination for observation of juveniles during security checks.
DOC 346.14(4)(4)Day room.
DOC 346.14(4)(a)(a) Each day room shall have all of the following:
DOC 346.14(4)(a)1.1. A minimum floor area of 35 square feet for each juvenile based on the rated bed capacity of the adjacent group of cells. In addition, each day room shall have a minimum of 70 square feet of unencumbered space.
DOC 346.14(4)(a)2.2. Detention strength light fixtures that provide at least 30 foot candles at 30 inches above the floor.
DOC 346.14(4)(a)3.3. Adequate furnishings and equipment for leisure time activities as required under this chapter.
DOC 346.14(4)(a)4.4. Detention strength tables and seating based on the rated bed capacity of the adjacent cells.
DOC 346.14(4)(b)(b) There shall be in the day room no exposed heating pipes, radiators or controls which are accessible to juveniles.
DOC 346.14(5)(5)Holding rooms.
DOC 346.14(5)(a)(a) Holding rooms shall be located in an area that allows continuous staff observation or electronic video surveillance of juveniles.
DOC 346.14(5)(b)(b) Each holding room shall have all of the following:
DOC 346.14(5)(b)1.1. Detention strength, rigidly constructed seats or benches bracketed to the wall or bolted to the floor or seats or benches of masonry construction of similar strength.
DOC 346.14(5)(b)2.2. A detention strength, metal, institution-type wash basin and toilet.
DOC 346.14(5)(b)3.3. A minimum floor area of 50 square feet of unencumbered space for 5 or fewer occupants and an additional 10 square feet of unencumbered space for each additional occupant.
DOC 346.14(5)(b)4.4. Detention strength light fixtures that provide at least 30 foot candles at 30 inches above the floor.
DOC 346.14(5)(c)(c) Holding rooms are not included in the rated capacity of a facility.
DOC 346.14(5)(d)(d) Juveniles may not be held in a holding room for more than 24 continuous hours.
DOC 346.14(5)(e)(e) Holding rooms outside the secure perimeter shall comply with the requirements of this section.
DOC 346.14(6)(6)Receiving cells.
DOC 346.14(6)(a)(a) All receiving cells shall be designed and used for single occupancy.
DOC 346.14(6)(b)(b) Each receiving cell shall have all of the following:
DOC 346.14(6)(b)1.1. A rigidly constructed metal bed with the frame bracketed to the wall or bolted to the floor or a bed built in masonry construction or similar strength.
DOC 346.14(6)(b)2.2. A detention strength, metal, institution-type wash basin and toilet. The wash basin and toilet may be combined in one unit. The wash basin shall have hot and cold running water.
DOC 346.14(6)(b)3.3. Detention strength light fixtures that provide at least 30 foot candles at 30 inches above the floor. Lights shall have a dimming capability or there shall be a nightlight to allow for comfortable sleeping. There shall be enough illumination for observation of juveniles during security checks.
DOC 346.14(6)(b)4.4. A minimum floor area of 35 square feet of unencumbered space. The distance between the floor and ceiling may not be less than 8 feet and the distance between opposite walls may not be less than 6 feet.
DOC 346.14(6)(c)(c) Receiving cells are not included in determining the rated capacity of a facility.
DOC 346.14(6)(d)(d) Juveniles may not be held in a receiving cell for more than 72 continuous hours.
DOC 346.14(7)(7)Natural lighting. Cells under sub. (2) and s. DOC 346.15 and dormitories under sub. (3) shall be provided with natural light in accordance with the International Building Code, s. 1204 as adopted by the department of safety and professional services under s. SPS 361.05 (1). Artificial light may not be used as an alternative to the natural light requirements under the International Building Code.
DOC 346.14(8)(8)Exterior windows.
DOC 346.14(8)(a)(a) This subsection applies to all windows that lead to the exterior of the facility or to an area outside the secure perimeter of the facility.
DOC 346.14(8)(b)(b) All exterior windows shall be translucent or shall be located to prevent persons outside the secure perimeter of the facility from observing juveniles within the facility.
DOC 346.14(8)(c)(c) Each exterior window that has an opening in any direction in excess of 5½ inches shall be covered with security steel grills to prevent escape.
DOC 346.14(8)(d)(d) If an exterior window is accessible to juveniles and opens, the window shall be mounted in a detention strength frame and shall be covered on the inside with a 1,600 pound per lineal inch tensile strength security screen of .047 mil. wire diameter to prevent the passage of contraband.
DOC 346.14(8)(e)(e) If an exterior window is not accessible to juveniles and opens, the screen shall have a tensile strength of at least 800 pounds per lineal inch and shall be made of wire of at least .028 mil. diameter.
DOC 346.14(8)(f)(f) If an exterior window does not open, whether or not it is accessible to juveniles, the security screen required under par. (d) or (e) may be omitted if the window is mounted in a detention strength frame and the pane is security glass of sufficient strength to resist breakage and prevent the passage of contraband.
DOC 346.14(9)(9)Showers. There shall be at least one shower for every 8 juveniles. There shall be an adequate supply of hot and cold water so that juveniles shall be permitted to shower on a daily basis.
DOC 346.14(10)(10)Multi-purpose space. Facilities shall contain multi-purpose space which shall have a minimum of 300 square feet of floor area or provide 35 square feet of floor area for the maximum number of juveniles expected to use the space at one time, whichever is greater.
DOC 346.14(11)(11)Classroom space. For juvenile detention facilities which are constructed or substantially remodeled after November 1, 2010, there shall be classroom space designed in conformity with local or state educational requirements.
DOC 346.14(12)(12)Health care area. If medical or dental services are provided in the facility, there shall be sufficient space, equipment, supplies and materials for the performance of primary health care delivery in a confidential and private manner. The superintendent shall consult with the health care provider to determine the adequacy of the space, equipment, supplies and materials.
DOC 346.14(13)(13)Outdoor recreation space.
DOC 346.14(13)(a)(a) If provided, there shall be a minimum of 70 square feet of outdoor recreational space per occupant.
DOC 346.14(13)(b)(b) The operational plan under s. DOC 346.04 shall contain policies and procedures for the safe and secure use of outdoor recreational space.
DOC 346.14(14)(14)Storage space.
DOC 346.14(14)(a)(a) Sufficient space shall be provided in the facility to store and issue clothing, bedding, cleaning supplies and other items for daily operations.
DOC 346.14(14)(b)(b) Space shall be provided for storing the personal property of juveniles safely and securely.
DOC 346.14(15)(15)Visiting space. Sufficient space for visitation shall be provided.
DOC 346.14 HistoryHistory: CR 09-039: cr. Register October 2010 No. 658, eff. 11-1-10; correction to numbering of (2) (c) 6. made under s. 13.92 (4) (b) 1., Stats., Register October 2010 No. 658; correction in (7) made under s. 13.92 (4) (b) 6., 7., Stats., Register January 2012 No. 673.
DOC 346.15DOC 346.15Double celling.
DOC 346.15(1)(1) A juvenile detention facility may use cells for double occupancy. This section does not apply to a juvenile portion of a county jail.
DOC 346.15(2)(2) If a juvenile detention facility determines based on all the criteria under s. DOC 346.10 that placement of a juvenile in a double cell may jeopardize the health or safety of the juvenile, other juveniles in the facility, staff or the community, the juvenile may not be placed in a double cell. If a juvenile detention facility determines based on all the criteria under s. DOC 346.10 that placement of 2 particular juveniles in a double cell may jeopardize the health or safety of either juvenile, other juveniles in the facility, staff or the community, those juveniles may not be placed together in the double cell.
DOC 346.15(3)(3) In addition to the requirements for single occupancy cells under s. DOC 346.14 (2) and before a cell may be used for double occupancy, all of the following conditions shall be met:
DOC 346.15(3)(a)(a) Minimum floor area.
DOC 346.15(3)(a)1.1. In juvenile detention facilities which were constructed or substantially remodeled between October 1, 1994 and November 1, 2010, a cell shall have a minimum floor area of 70 square feet. The distance between the floor and ceiling may not be less than 8 feet and the distance between opposite walls may not be less than 6 feet.
DOC 346.15(3)(a)2.2. In juvenile detention facilities which were constructed before October 1, 1994 and have not been substantially remodeled after October 1, 1994, a cell shall have a minimum floor area of 54 square feet. The distance between the floor and ceiling may not be less than 8 feet and the distance between opposite walls may not be less than 6 feet.
DOC 346.15(3)(a)3.3. In juvenile detention facilities which are constructed or substantially remodeled after November 1, 2010, a cell shall have a minimum floor area of 70 square feet of unencumbered space.
DOC 346.15(3)(b)(b) Receiving cells. Receiving cells may not be used for double occupancy.
DOC 346.15(3)(c)(c) Single occupancy cells. Each juvenile detention facility shall maintain a minimum of 2 cells which are designed and used for single occupancy only.
DOC 346.15(3)(d)(d) Double occupancy cells. A juvenile detention facility may not exceed 75% double occupancy of the total number of cells, excluding receiving cells and holding rooms.
DOC 346.15(3)(e)(e) Clothing hooks. Each cell shall contain a minimum of two nonremovable, collapsible, detention strength clothing and towel hooks for each occupant.
DOC 346.15(3)(f)(f) Anti-rollout plates. For facilities constructed or substantially remodeled after November 1, 2010, all upper bunks shall be equipped with an anti-rollout plate.
DOC 346.15 HistoryHistory: CR 09-039: cr. Register October 2010 No. 658, eff. 11-1-10.
DOC 346.16DOC 346.16Fire protection.
DOC 346.16(1)(1) The operational plan under s. DOC 346.04 shall contain policies and procedures relating to fire protection and evacuation, including evacuation of persons with disabilities and appropriate training of staff. The policies and procedures shall comply with local fire department recommendations.
DOC 346.16(2)(2) The evacuation plan shall be posted in a conspicuous place for staff to view.
DOC 346.16(3)(3) The facility shall have and shall properly maintain fire alarms, smoke and thermal detectors, and fire extinguishers. The facility shall place this equipment in accordance with the advice of the local fire department.