SPS 382.21(2)(g)1. 1. If applied to the entire system, all openings in the piping shall be tightly closed, except the highest opening, and the system shall be filled with water to the point of overflow. If the system is tested in sections, each opening shall be tightly plugged except the highest opening of the section under test, and each section shall be filled with water, but a section shall not be tested with less than a 10 foot head of water. In testing successive sections, at least the upper 10 feet of the next preceding section shall be tested, so that no joint or pipe in the building, except the uppermost 10 feet of the system, is subjected to a test of less than a 10 foot head of water. The water shall be kept in the system or in the portion under test for at least 15 minutes before inspection starts. The system shall then be tight at all points.
SPS 382.21(2)(g)2. 2. The air test shall be made by attaching an air compressor testing apparatus to any suitable opening, and, after closing all other inlets and outlets to the system, forcing air into the system until there is a uniform gauge pressure of 5 pounds per square inch or sufficient to balance a column of mercury 10" in height. This pressure shall be held without introduction of additional air for a period of at least 15 minutes.
SPS 382.21(2)(h) (h) Final test. Where required by the local plumbing inspector, after the plumbing fixtures have been installed and the traps filled with water, the connections shall be tested and proved gas and watertight by either one of the methods specified in subd. 1. or 2.
SPS 382.21(2)(h)1. 1. The smoke test shall be made by introducing a pungent, thick smoke, produced by one or more smoke machines, into the completed system. When the smoke appears at stack openings on the roof, the openings shall be closed and a pressure equivalent to a one inch water column shall be built and maintained for the period of the inspection.
SPS 382.21(2)(h)2. 2. The air test shall be made by attaching a gauge to any suitable opening and, after closing all other inlets and outlets in the system, adding air into the system until a pressure equivalent to a one inch water column exists. The pressure shall remain constant for at least a 5-minute test period without the introduction of additional air.
SPS 382.21 History History: Cr. Register, February, 1985, No. 350, eff. 3-1-85; r. and recr. (1) (d) 5., am. (1) (d) 7. intro., Register, May, 1988, No. 389, eff. 6-1-88; correction in (1) (c) made under s. 13.93 (2m) (b) 7., Stats., Register, May, 1988, No. 389; renum. (1) (a) and (2) (b) to (i) to be (1) (a) 1. and (2) (a) to (h), r. (2) (a), cr. (1) (a) 2. and (3), r. and recr. (1) (d) 1. (intro.), am. (1) (d) 2. (intro.), Register, February, 1994, No. 458, eff. 3-1-94; am. (3) (b) 3., Register, October, 1996, No. 490, eff. 11-1-96; am. (3), Register, February, 1997, No. 494, eff. 3-1-97; r. and recr. (2) (a) and (3), cr. Table 82.21-1, Register, December, 2000, No. 540, eff. 1-1-01; CR 02-002: r. and recr. (1) (b) 4. b. and (2) (d), am. (1) (d) 8. b. Register April 2003 No. 568, eff. 5-1-03; CR 04-035: am. Table 82.21-1 Register November 2004 No. 587, eff. 12-1-04; CR 08-055: am. (title) and (1) (intro.), r. and recr. (1) (b) 1. b., r. (2) and Table 82.21-1, renum. (1) (d) and (3) to be (2) and Comm 82.22 (9) Register February 2009 No. 638, eff. 3-1-09; corrections in (1) (b) 4. b., (2) (a) 2., (b) (intro.), (c), (d), (g) (intro.) and (h) (intro.) made under s. 13.92 (4) (b) 7., Stats., Register February 2009 No. 638; CR 10-064: renum. (1) (b) 1. b. to be (1) (b) 1. c., cr. (1) (b) 1. b., (d) Register December 2010 No. 660, eff. 1-1-11; correction in (1) (a) 2. b., (c), (d) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 23-006: am. (1) Register September 2023 No. 813, eff. 10-1-23.
SPS 382.22 SPS 382.22Maintenance and repairs.
SPS 382.22(1)(1)General.
SPS 382.22(1)(a)(a) All plumbing systems, both existing and new, and all parts thereof, shall be maintained in a safe and sanitary condition.
SPS 382.22(1)(b) (b) All devices or safeguards that are required by this chapter shall be maintained in good working order.
SPS 382.22(1)(c) (c) The owner shall maintain plumbing systems.
SPS 382.22(2) (2)Existing systems.
SPS 382.22(2)(a) (a) Except as specified in par. (b), any existing plumbing system may remain and maintenance continue if the maintenance is in accordance with the original system design and any of the following:
SPS 382.22(2)(a)1. 1. The plumbing system was installed in accordance with the code in effect at the time of installation.
SPS 382.22(2)(a)2. 2. The plumbing system conforms to the present code.
SPS 382.22(2)(b) (b) When a hazard to life, health or property exists or is created by an existing system, that system shall be repaired or replaced.
SPS 382.22 Note Note: A cross connection is considered a health hazard by the department.
SPS 382.22(2)(c) (c) Existing sewers and water services may only be connected to new buildings when determined by examination and test to conform to the requirements of this chapter.
SPS 382.22(3) (3)Fixtures replaced.
SPS 382.22(3)(a) (a) When a fixture, appliance or section of pipe is replaced, the replacement fixture, appliance or pipe shall conform to the provisions of this chapter.
SPS 382.22(3)(b) (b) Where the existing drain or vent piping does not conform to the current provisions of this chapter, the department may require the new fixtures to be provided with deep seal traps.
SPS 382.22(4) (4)Plumbing reused.
SPS 382.22(4)(a)1.1. Except as provided in par. (b) plumbing materials, fixtures or devices removed and found to be in good condition may be reused if such reuse is approved by the department or a local plumbing inspector.
SPS 382.22(4)(a)2. 2. The owner of the building or facility in which the reused materials are to be installed shall provide written consent.
SPS 382.22(4)(b) (b) Water supply piping materials may only be reused when the intended use involves an equal or higher degree of hazard than the previous use as specified in Table 382.70–1.
SPS 382.22(5) (5)Repairs. All repairs to fixtures, devices or piping shall be completed in conformance with the provisions of this chapter, except repair clamps or bands may be used for emergency situations.
SPS 382.22(6) (6)Demolition of structures. When a structure is demolished or removed, all sanitary sewer, storm sewer and water supply connections shall be sealed and plugged in a safe manner.
SPS 382.22(7) (7)Dead ends. If a dead end is created in the removal of any part of a drain system, all openings in the drain system shall be properly sealed in accordance with s. SPS 384.40.
SPS 382.22(8) (8)Testing of cross connection control assemblies.
SPS 382.22(8)(a)(a) The performance testing requirements of this subsection apply to all cross connection control assemblies regardless of date of installation.
SPS 382.22 Note Note: For further clarification see Table 382.22–1.
SPS 382.22(8)(b)1.1. A performance test shall be conducted for the assemblies listed in Table 382.22–1 at all of the following intervals:
SPS 382.22(8)(b)1.a. a. At the time of installation.
SPS 382.22(8)(b)1.b. b. Immediately after repairs or alterations to the assembly have occurred.
SPS 382.22(8)(b)1.c. c. At least annually.
SPS 382.22(8)(b)2. 2. The performance test shall be conducted using the appropriate test standard for the assembly as specified in Table 382.22–1.
SPS 382.22(8)(b)3. 3. A cross connection assembly performance test shall be conducted by an individual registered by the department in accordance with s. SPS 305.99.
SPS 382.22(8)(b)4.a.a. The results of the cross connection control assembly performance test shall be submitted as specified in Table 382.22–1 in a format prescribed by the department accompanied by a filing fee as specified in s. SPS 302.645 (2).
SPS 382.22(8)(b)4.b. b. As specified in Table 382.22–1, the results of the cross connection assembly performance test shall be submitted to the department and purveyor within 60 days of completion of the test.
SPS 382.22(8)(b)5. 5. The results of performance tests for the assemblies listed in Table 382.22–1 shall be made available upon request to the department, its agent or the local government unit.
Table 382.22-1
Testing and Submitting Requirements for Cross Connection Control Assemblies - See PDF for table PDF
SPS 382.22 History History: CR 08-055: cr. (1) to (8) and Table 82.22-1, (9) renum. from Comm 82.21 (3) Register February 2009 No. 638, eff. 3-1-09; correction to numbering in (3) made under s. 13.92 (4) (b) 1., Stats., Register February 2009 No. 638; CR 09-050: am. (8) (b) 4. a. and Table 82.22-1, r. (9) Register December 2009 No. 648, eff. 1-1-10; correction in (4) (b), (8) (b) 1. (intro.), 2., 3., 4. a., b., 5. made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 23-006: am. (7), Table 382.22-1 Register September 2023 No. 813, eff. 10-1-23.
subch. III of ch. SPS 382 Subchapter III — Drain and Vent Systems
SPS 382.30 SPS 382.30Sanitary drain systems.
SPS 382.30(1)(1)Scope. The provisions of this section set forth the requirements for the design and installation of sanitary drain systems, including building drains and building sewers.
SPS 382.30 Note Note: The provisions for storm and clear water drain systems are specified in s. SPS 382.36.
SPS 382.30(2) (2)Materials. All sanitary drain systems shall be constructed of approved materials in accordance with ch. SPS 384.
SPS 382.30(3) (3)Load on drain piping.
SPS 382.30(3)(a) (a) Intermittent flow.
SPS 382.30(3)(a)1.1. `Fixture.' The load factor on drain piping shall be computed in terms of drainage fixture unit values specified in Table 382.30–1 for the corresponding listed fixture.
SPS 382.30(3)(a)2. 2. `Devices.' Drainage fixture unit values for intermittent flow devices not listed in Table 382.30–1 shall be computed on the basis of one fixture unit equalling one gallon per minute of flow.
SPS 382.30 Note Note: Equipment with a timed discharge cycle(s) of 2 minutes or less may be considered as an intermittent flow device.
SPS 382.30(3)(b) (b) Continuous flow devices. Drainage fixtures unit values for continuous flow devices such as pumps, ejectors, air conditioning equipment or similar devices that discharge continuously shall be computed on the basis of 2 fixture units for each one gallon per minute of flow.
SPS 382.30(4) (4)Size of drain piping.
SPS 382.30(4)(a) (a) Maximum loading.
SPS 382.30(4)(a)1.1. The total drainage load in any portion of drain piping may not exceed the limits specified in Tables 382.30-2 and 382.30-3, but may be less than the limits specified in Tables 382.30-2 and 382.30-3 based on an approved alternate standard consistent with s. SPS 381.20 (2) or an analysis provided by a Wisconsin registered architect, registered professional engineer, or permitted designer of engineering systems – plumbing.
SPS 382.30(4)(a)2. 2. The drainage fixture unit values assigned to a receptor may be less than the limits specified in Tables 382.30-2 and 382.30-3 based on an approved alternate standard consistent with s. SPS 381.20 (2) or an analysis provided by a Wisconsin registered architect, registered professional engineer, or permitted designer of engineering systems – plumbing.
SPS 382.30 Note Note: See s. SPS 382.31 (17) for sizing requirements of combination drain and vent systems.
SPS 382.30 Note Note: See ch. SPS 382 Appendix for further explanatory material.
SPS 382.30(4)(b) (b) Minimum size of building sewers.
SPS 382.30(4)(b)1.1. `Gravity flow sewers.' The minimum size of a gravity flow sanitary building sewer shall be 4 in diameter. A municipality or sanitary district by ordinance may require that portion of the building sewer between the lot line and the public sewer to be larger than 4" in diameter.
SPS 382.30(4)(b)2. 2. `Pressurized sewers.'
SPS 382.30(4)(b)2.a.a. Sewers pressurized through the use of sewage ejectors, sewage pumps or sewage grinder pumps shall be sized to maintain a minimum flow velocity of 2 feet per second and shall be in accordance with the ejector or pump manufacturer's recommendations.
SPS 382.30(4)(b)2.b. b. Pressurized building sewers shall be sized not less than 2" in diameter for sewage ejectors and sewage pumps, and 1¼ " in diameter for all sewage grinder pumps.
SPS 382.30(4)(c) (c) Minimum size of private interceptor main sewers.
SPS 382.30(4)(c)1.1. Except as provided in subd. 3., the minimum size of a gravity flow private interceptor main sewer shall be 4" in diameter.
SPS 382.30(4)(c)2. 2. Except as provided in subd. 3., the minimum size of pressurized private interceptor main sewer shall be such so as to maintain a minimum flow velocity of 2 feet per second.
SPS 382.30(4)(c)3. 3. A municipality or a sanitary district may by ordinance, require the minimum size of a private interceptor main sewer to be larger than 4" in diameter.
SPS 382.30(4)(c)4. 4. Private interceptor main sewers 6" or less in diameter may not exceed the drainage fixture limits in Table 382.30-3.
SPS 382.30(4)(c)5. 5. Private interceptor main sewers 8" or larger in diameter shall conform with the design criteria specified in s. NR 110.13.
SPS 382.30 Note Note: See ch. SPS 382 Appendix A-382.30 (4) for further explanatory material.
SPS 382.30(4)(d) (d) Future fixtures. Where provisions are made for the future installation of fixtures, the drainage fixture unit values of such fixtures shall be considered in determining the required sizes of drain and vent pipes. Construction to provide for future installations shall be terminated with a plugged fitting or fittings. - See PDF for table PDF - See PDF for table PDF - See PDF for table PDF - See PDF for table PDF - See PDF for table PDF - See PDF for table PDF - See PDF for table PDF - See PDF for table PDF
SPS 382.30 Note Note: For further explanatory material see ch. SPS 382 Appendix A-382.30 (4).
SPS 382.30(5) (5)Pitch of horizontal drain piping. All horizontal drain piping 4" or larger in diameter shall be installed at a pitch which produces a computed velocity of at least 2 feet per second when flowing half full.
SPS 382.30(5)(a) (a) Horizontal branch drains.
SPS 382.30(5)(a)1.1. The minimum pitch of horizontal branch drains 2" or less in diameter shall be 1/4" per foot.
SPS 382.30(5)(a)2. 2. The minimum pitch of horizontal branch drains larger than 2 in diameter shall be 1/ 8" per foot.
SPS 382.30(5)(b) (b) Building drains and building sewers.
SPS 382.30(5)(b)1.1. The minimum pitch of building drains shall be in accordance with Table 382.30-3.
SPS 382.30(5)(b)2.a.a. The minimum pitch of building sewers 10" or less in diameter shall be in accordance with Table 382.30-3.
SPS 382.30(5)(b)2.b. b. The minimum pitch of building sewers 12" or larger in diameter shall conform with the minimum pitch specified for municipal sewers in s. NR 110.13.
SPS 382.30 Note Note: See also s. SPS 382.30 (4) (c) 5. for further explanatory material.
SPS 382.30(5)(c) (c) Private interceptor main sewers.
SPS 382.30(5)(c)1.1. The minimum pitch of private interceptor main sewers 6" or less in diameter shall be in accordance with Table 382.30-3.
SPS 382.30(5)(c)2. 2. The minimum pitch of private interceptor main sewers 8" or larger in diameter shall conform with the minimum pitch specified for municipal sewers in s. NR 110.13.