SPS 362.3002(4)(b)3.a. a. 30 gpm in a hoistway with one elevator.
SPS 362.3002(4)(b)3.b. b. 50 gpm in a hoistway with two or three elevators.
SPS 362.3002(4)(b)3.c. c. 80 gpm in a hoistway with four elevators.
SPS 362.3002 Note Note: See s. SPS 382.36 for the width or diameter and depth of a sump pump located in an elevator pit.
SPS 362.3002 History History: CR 10-103: cr. Register August 2011 No. 668, eff. 9-1-11; CR 14-020: r. and recr. (3) Register August 2014 No. 704, eff. 9-1-14; CR 16-094: renum 362.3002 to (1), r. and recr. (title), renum. 362.3004 (1) to (3) to (2) to (4) and am., Register April 2018 No. 748 eff. 5-1-18.
SPS 362.3003 SPS 362.3003Standardized fire service elevator keys. Substitute the following for the requirements in IBC section 3003.3. All elevators shall be equipped to operate with a standardized fire service elevator key in accordance with ch. SPS 318.
SPS 362.3003 History History: CR 16-094: cr., Register April 2018 No. 748 eff. 5-1-18.
SPS 362.3005 SPS 362.3005Machine rooms.
SPS 362.3005(1)(1)Scope. This is a department rule in addition to the requirements in IBC section 3005: This section applies to elevator machine rooms, machinery spaces, control rooms, and control spaces not within the hoistway.
SPS 362.3005(2) (2) Access. This is a department informational note to be used under IBC section 3005.1: Note: See ch. SPS 318 for additional requirements, including a prohibition against accessing elevator machine rooms, machinery spaces, control rooms, or control spaces through a toilet room, sleeping room or other private space; and a prohibition against accessing spaces, machinery or equipment not related to a conveyance through machine rooms, machinery spaces, control rooms, control spaces, or hoistways.
SPS 362.3005(3) (3) Temperature and humidity. Substitute the following wording for the requirements in IBC section 3005.2: Elevator machine rooms that contain solid-state equipment for elevator operation shall be provided with an independent means to control the temperature and humidity in the machine room.
SPS 362.3005 Note Note: See IBC section 3003.1.4 and ASME A17.1 section 2.7.9.2 for additional requirements that may apply.
SPS 362.3005(4) (4) Pressurization. This is a department exception to the requirements in IBC section 3005.3: An elevator machine room which serves a pressurized elevator hoistway and which is not directly connected to the pressurized elevator shaft is not required to be pressurized.
SPS 362.3005(4m) (4m) Shunt trip. The following is an exception to IBC section 3005.5. A sprinkler of a sidewall type installed 24 inches or less above the elevator pit floor may not require a heat detector or other means to disconnect the main line power supply.
SPS 362.3005(5) (5) Plumbing systems. Substitute the following wording for the requirements in IBC section 3005.6: Plumbing systems not used in connection with the operation of the elevator may not be located in elevator equipment rooms.
SPS 362.3005 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 01-111: renum. (1) and (2) to be (2) and (3) and cr. (1) Register June 2002 No. 558, eff. 7-1-02; CR 04-016: renum. (3) to be (4), cr. (3) Register December 2004 No. 588, eff. 1-1-05; CR 14-020: renum. (1), (2), (4) to (2), (4), (5), cr. (1), (r) (3), cr. (3) Register August 2014 No. 704, eff. 9-1-14; (1) (title), (3) (title) added under s. 13.92 (4) (b) 2., Stats., Register August 2014 No. 704; CR 16-094: renum. 362.3006 to 362.3005 and am., cr. (4m), Register April 2018 No. 748 eff. 5-1-18; correction in (4) and (5) made under s. 13.92 (4) (b) 7., Stats., Register April 2018 No. 748.
SPS 362.3100 SPS 362.3100Special construction. These are department rules in addition to the requirements in IBC chapter 31: Mausoleum structures shall be designed, constructed, and maintained in accordance with chs. SPS 361 to 366. Mausoleums shall be classified as a Group S-1 storage occupancy and shall be constructed of reinforced concrete or other materials of similar durability.
SPS 362.3100 Note Note: Section 157.12 (2) (d), Stats., reads as follows: “A mausoleum shall be constructed to last as long as possible, taking into consideration the technology and economics applicable to mausoleum construction at the time of construction."
SPS 362.3100 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 01-139: am., cr. (2) Register June 2002 No. 558, eff. 7-1-02; CR 06-120: r. (1), renum. (2) to be Comm 62.3100 Register February 2008 No. 626, eff. 3-1-08; CR 16-094: am., Register April 2018 No. 748 eff. 5-1-18.
SPS 362.3102 SPS 362.3102Membrane structures and blower equipment.
SPS 362.3102(1) (1)Temporary structures. This is a department exception to the requirements in IBC section 3102.1: Membrane structures that are seasonal recreational and educational camp buildings erected on balconies, decks, or other permanent raised platforms no more than 36” above grade at any point shall comply with the International Fire Code.
SPS 362.3102(2) (2)Blower equipment. Substitute the following wording for requirement 2 in IBC section 3102.8.1.2: Blowers shall be provided with inlet screens, belt guards and other protective devices as required to provide protection from injury.
SPS 362.3102 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 06-120: am. Register February 2008 No. 626, eff. 3-1-08; CR 22-069: r. and recr. Register July 2023 No. 811, eff. 8-1-23.
SPS 362.3103 SPS 362.3103Temporary structures. This is a department rule in addition to the requirements in IBC section 3103: Under IBC sections 3103.1.2 and 3103.2, the requirements for permits and construction documents for temporary structures are at the option of the local code official.
SPS 362.3103 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 16-094: am., Register April 2018 No. 748 eff. 5-1-18.
SPS 362.3104 SPS 362.3104Pedestrian walkways and tunnels. Substitute the following wording for the requirements and exception in IBC section 3104.2: Buildings that are connected in accordance with IBC section 3104 shall be considered to be separate structures.
SPS 362.3104 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 06-120: r. (1) (title) and (2), renum. (1) to be Comm 62.3104 Register February 2008 No. 626, eff. 3-1-08.
SPS 362.3109 SPS 362.3109Swimming pool enclosures. Substitute the following informational note for the requirements in IBC section 3109. Note: See ch. SPS 390 for requirements for swimming pool enclosures.
SPS 362.3109 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02.
SPS 362.3200 SPS 362.3200Encroachments into the public right-of-way. The requirements in IBC chapter 32 are not included as part of chs. SPS 361 to 366.
SPS 362.3200 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 16-094: am., Register April 2018 No. 748 eff. 5-1-18.
SPS 362.3300 SPS 362.3300Safeguards during construction. Except for the requirements in IBC sections 3302.1 and 3303.5, the requirements in IBC chapter 33 are not included as part of this code.
SPS 362.3300 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 01-139: renum. (1) to be Comm 62.3300 and renum. (2) to be Comm 62.3307 Register June 2002 No. 558, eff. 7-1-02.
SPS 362.3307 SPS 362.3307Protection of adjoining property. This is a department informational note to be used under IBC chapter 33: Note: Sections 101.111 (1) to (6), Stats., read as follows:
SPS 362.3307 Text “(1) DEFINITION. In this section `excavator' means any owner of an interest in land making or causing to be made an excavation.
SPS 362.3307 Text (2) CAVE-IN-PREVENTION. Any excavator shall protect the excavation site in such a manner so as to prevent the soil of adjoining property from caving in or settling.
SPS 362.3307 Text (3) LIABILITY FOR UNDERPINNING AND FOUNDATION EXTENSIONS. (a) If the excavation is made to a depth of 12 feet or less below grade, the excavator may not be held liable for the expense of any necessary underpinning or extension of the foundations of buildings on adjoining properties.
SPS 362.3307 Text (b) If the excavation is made to a depth in excess of 12 feet below grade, the excavator shall be liable for the expense of any necessary underpinning or extension of the foundations of any adjoining buildings below the depth of 12 feet below grade. The owners of adjoining buildings shall be liable for the expense of any necessary underpinning or extension of the foundations of their buildings to the depth of 12 feet below grade.
SPS 362.3307 Text (4) NOTICE. Unless waived by adjoining owners, at least 30 days prior to commencing the excavation the excavator shall notify, in writing, all owners of adjoining buildings of his or her intention to excavate. The notice shall state that adjoining buildings may require permanent protection. The owners of adjoining property shall have access to the excavation site for the purpose of protecting their buildings.
SPS 362.3307 Text (5) EMPLOYEES NOT LIABLE. No worker who is an employee of an excavator may be held liable for his or her employer's failure to comply with this section.
SPS 362.3307 Text (6) FAILURE TO COMPLY; INJUNCTION. If any excavator fails to comply with this section, any aggrieved person may commence an action to obtain an order under ch. 813 directing such excavator to comply with this section and restraining the excavator from further violation thereof. If the aggrieved person prevails in the action, he or she shall be reimbursed for all his or her costs and disbursements together with such actual attorney fees as may be approved by the court."
SPS 362.3307 History History: CR 01-139: renum. from Comm 62.3300 (2) Register June 2002 No. 558, eff. 7-1-02.
SPS 362.3500 SPS 362.3500Referenced standards.
SPS 362.3500(1)(1)Introduction. Substitute the following wording for the introductory paragraph in IBC chapter 35: This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard. The application of the referenced standards shall be as specified in s. SPS 361.03 (1) (b) and (3) (a).
SPS 362.3500(3) (3) Addition. This is a department rule in addition to the requirements in IBC chapter 35: NFPA 45-2015, Standard on Fire Protection for Laboratories Using Chemicals, is incorporated by reference into chs. SPS 361 to 366.
SPS 362.3500 Note Note: NFPA standards may be viewed online free of charge at NFPA.org or purchased from the National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.
SPS 362.3500 Note Copies of the standard adopted under this chapter are on file in the offices of the department and the legislative reference bureau.
SPS 362.3500 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 01-139: am. Register June 2002 No. 558, eff. 7-1-02; CR 04-016: r. and recr. Register December 2004 No. 588, eff. 1-1-05; CR 06-120: am. (1), r. (2) and (3) (a), renum. (3) (b) to (e) to be (3) (a) to (d) and am. (3) (c) Register February 2008 No. 626, eff. 3-1-08; EmR0826: emerg. cr. (3) (e), eff. 10-1-08; CR 08-085: cr. (3) (e) and (f) Register May 2009 No. 641, eff. 6-1-09; CR 10-103: r. (3) (a), am. (3) (b), (d) Register August 2011 No. 668, eff. 9-1-11; correction in (1) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 16-094: renum. (3) (intro.) to (3) and am., r. (3) (b) to (f), Register April 2018 No. 748 eff. 5-1-18; correction in (3) under s. 35.17, Stats., Register April 2018 No. 748.
SPS 362.3600 SPS 362.3600Appendices.
SPS 362.3600(1)(1)Exclusions. The provisions in IBC Appendices A, B, D, F to K, and M are not included as part of chs. SPS 361 to 366.
SPS 362.3600(2) (2) Appendix C. The provisions in IBC Appendix C apply to Group U agricultural buildings, as described in IBC section C 101.1, that are not exempt from chs. SPS 361 to 366 as outlined in ss. SPS 361.01 and 361.02 (2) and (3).
SPS 362.3600 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 04-016: am. (1) Register December 2004 No. 588, eff. 1-1-05; CR 06-120: am. (1) Register February 2008 No. 626, eff. 3-1-08; correction in (2) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 16-094: am. (1), (2), Register April 2018 No. 748 eff. 5-1-18.