SPS 390.14(13)(d)6. 6. Where automatic skimming devices are used as the sole overflow system, at least one surface skimming device shall be provided for each 500 square feet or fraction thereof of water surface area.
SPS 390.14(13)(d)7. 7. Circulation systems shall be designed to carry 100 percent of the rated circulation volume through the skimmers.
SPS 390.14(13)(d)8. 8. The flow rate through automatic skimmers shall be no less than 3 gallons per minute per inch of skimmer weir width.
SPS 390.14 Note Note: The maximum flow rate through skimmers is determined by the ANSI/NSF 50 rating.
SPS 390.14(13)(d)9. 9. Acceptable options for surface skimming systems shall be in accordance with Table 390.14-3.
Table 390.14-3
Acceptable Surface Skimming Systems - See PDF for table PDF
SPS 390.14(13)(d)10. 10. When a gutter skimming system is used, the system shall be connected to a circulation system with an adequate surge capacity to permit all phases of operation.
SPS 390.14(13)(d)11.a.a. Except as provided in subd. 11. b., a zero-depth trench shall extend continuously from within 3 feet of one wall of the basin to within 3 feet of the opposite wall of the basin.
SPS 390.14(13)(d)11.b. b. Where the entire perimeter of the basin consists of a zero-depth entry, 50 percent shall be evenly-distributed zero-depth trench.
SPS 390.14 History History: CR 08-056: cr. Register February 2009 No. 638, eff. 3-1-09; correction in (10) (a) made under s. 13.92 (4) (b) 7., Stats., Register February 2009 No. 638; correction in (1), (11) (a) 2., (13) (d) 9. made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; correction in (10) (a) made under s. 13.92 (4) (b) 7., Stats., Register February 2017 No. 734.
SPS 390.16 SPS 390.16Mechanical systems.
SPS 390.16(1) (1)Electrical. Electrical components shall comply with the requirements of ch. SPS 316.
SPS 390.16(2) (2)Water heaters.
SPS 390.16(2)(a)(a) Water heating equipment shall comply with chs. SPS 364 and 365.
SPS 390.16(2)(b) (b) A thermometer accurate to within plus or minus 2°F of the operating range shall be installed in the circulation piping.
SPS 390.16(2)(c) (c) The thermometer required in par. (b) shall be accessible for reading.
SPS 390.16(2)(d) (d) The use of a toxic solution, such as, but not limited to, heat transfer fluid in a single-wall heat exchanger, is prohibited.
SPS 390.16(2)(e) (e) Water heaters and hot water storage tanks shall be equipped with temperature and pressure relief valves in accordance with ch. SPS 384.
SPS 390.16(3) (3)Illumination.
SPS 390.16(3)(a)(a) Artificial lighting shall be provided so that all areas of the pool, including the bottom, shall be visible when the pool or water attraction is used during periods of low illumination.
SPS 390.16(3)(b) (b) For outdoor facilities, overhead lighting shall provide a minimum of 3 footcandles of illumination at the water surface and on the deck.
SPS 390.16(3)(c) (c) For indoor facilities, overhead lighting shall provide a minimum of 10 footcandles at the water surface and on the deck.
SPS 390.16(3)(d)1.1. Except as permitted in subd. 2., underwater lighting shall provide a minimum of ½-watt incandescent light per square foot of water surface area or equivalent.
SPS 390.16(3)(d)2. 2. If overhead lighting provides a minimum of 15 footcandles illumination at the water surface, no underwater lighting is required.
SPS 390.16(3)(e) (e) For exterior facilities, areas that are designed to operate during periods of low illumination shall be provided with sufficient emergency lighting to permit evacuation of the facility.
SPS 390.16(3)(f) (f) For exterior facilities, emergency lighting shall activate within 10 seconds of lighting failure.
SPS 390.16(4) (4)Water supply.
SPS 390.16(4)(a)(a) Water quality. The water supply for all public swimming pools and water attractions shall meet the water quality requirements as listed in ch. SPS 382, Table 382.70-1.
SPS 390.16 Note Note: Refer to Appendix A-390.16 (4) for s. SPS 382.70 Table 382.70-1.
SPS 390.16(4)(b) (b) Cross connection control. Protection of the potable water supply shall comply with s. SPS 382.41.
SPS 390.16(4)(c) (c) Makeup water quality. Makeup water to maintain the water level in all public swimming pools and water attractions and water used as a vehicle for disinfectants or other pool chemicals, for pump priming or for other such additions, shall meet the requirements listed in ch. SPS 382, Table 382.70-1.
SPS 390.16 Note Note: Refer to Appendix A-390.16 (4) for s. SPS 382.70 Table 382.70-1.
SPS 390.16(4)(d) (d) Spray feature water. Water used for spray features or water falling onto patrons shall be disinfected if supplied from a whirlpool or wading pool basin.
SPS 390.16(5) (5)Wastewater disposal. Wastewater discharges shall be in accordance with ss. SPS 382.38 Table 382.38-1 and 382.33.
SPS 390.16 Note Note: See ch. SPS 390 Appendix for a reprint of Table 382.38-1.
SPS 390.16(6) (6)Equipment room.
SPS 390.16(6)(a)(a) An equipment room or equipment enclosure shall be provided to serve all public swimming pools and water attractions.
SPS 390.16(6)(a)1. 1. An equipment room shall be ventilated in accordance with ch. SPS 364.
SPS 390.16(6)(a)2. 2. An equipment room shall be drained.
SPS 390.16(6)(a)3. 3. An equipment room shall be accessible for operation and maintenance of equipment.
SPS 390.16(6)(b) (b) The doors to all rooms in which a chlorine gas feeder is located or a cylinder of compressed chlorine gas is located or stored shall be labeled “DANGER-CHLORINE GAS" in clearly readable letters.
SPS 390.16 History History: CR 08-056: cr. Register February 2009 No. 638, eff. 3-1-09; correction in (1), (2) (a), (e), (4) (a), (b), (c), (5), (6) (a) 1. made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672.
SPS 390.17 SPS 390.17Sanitizing equipment.
SPS 390.17(1) (1)Equipment standards.
SPS 390.17(1)(a)(a) Sanitizing equipment shall be certified to comply with the requirements of NSF/ANSI 50.
SPS 390.17(1)(b) (b) A chemical system that provides the residual required by ch. ATCP 76 shall be installed when an alternative means of disinfection is proposed.
SPS 390.17 Note Note: Alternative disinfection systems include ultraviolet light, ozone and electrolytic chlorine generation, but are not limited to those systems.
SPS 390.17(1)(c) (c) Sanitizing equipment shall be capable of introducing a sufficient quantity of a U.S. EPA-approved sanitizer for normal operating procedures.
SPS 390.17 Note Note: See ch. ATCP 76 for disinfectant concentration and efficacy requirements.
SPS 390.17(1)(d) (d) Sanitizing equipment shall be certified by a nationally recognized testing laboratory.
SPS 390.17(2) (2)Sanitizing equipment.
SPS 390.17(2)(a)(a) Skimmer baskets may not be used as chemical feeders.
SPS 390.17(2)(b) (b) An automatic controller for controlling the sanitizing equipment shall be installed on all public swimming pools and water attractions.
SPS 390.17(2)(c) (c) The automatic controller shall include a flow sensor installed so that the chemical feed pump will not operate without a return flow to disburse the chemical.
SPS 390.17(2)(d) (d) The automatic controller shall be electrically interlocked with the circulation pump control circuit.
SPS 390.17 Note Note: Pool operation requirements are found in ch. ATCP 76, Wis. Adm. Code.
SPS 390.17(2)(e) (e) The automatic controller and circulation pump shall have separate disconnect switches.
SPS 390.17 History History: CR 08-056: cr. Register February 2009 No. 638, eff. 3-1-09; correction in (1) (b) made under s. 13.92 (4) (b) 7., Stats., Register February 2009 No. 638; correction in (1) (b) made under s. 13.92 (4) (b) 7., Stats., Register February 2017 No. 734.
SPS 390.18 SPS 390.18Safety features.
SPS 390.18(1) (1)Rope and float lines.
SPS 390.18(1)(a)1.1. Except as permitted in subd. 2., a rope and float line shall be provided in all basins:
SPS 390.18(1)(a)1.a. a. To separate activity areas, such as plunge areas, climbing walls, pad walks and other areas where patron activity may harm others.
SPS 390.18(1)(a)1.b. b. To restrict access to the caisson wall in wave pools.
SPS 390.18(1)(a)1.c. c. To identify water depth greater than 5.5 feet in combination pools and activity pools.
SPS 390.18(1)(a)2. 2. Rope and float lines are not required in areas where the department determines that the installation of the rope and float line would constitute a safety hazard.
SPS 390.18(1)(b) (b) For water depth, the rope and float line shall be located one foot toward the shallow end for each location where the purpose of the rope and float line is to mark a depth change.
SPS 390.18(1)(c) (c) A 4-inch-wide boundary line of contrasting color shall be installed on the basin walls and floor corresponding to the location of the rope and float line.
SPS 390.18(1)(d) (d) For wave generators, the rope and float line shall be located a minimum of 5 feet from the caisson wall.
SPS 390.18(1)(e) (e) The rope and float lines shall be securely fastened to wall anchors.
SPS 390.18(1)(f) (f) Rope and float lines shall be of sufficient size and strength so as to provide temporary support for a pool patron in the water.
SPS 390.18(1)(g) (g) Rope and float lines shall be installed with limited slack so as to provide temporary support for a pool patron in the water.
SPS 390.18(2) (2)Depth markers.
SPS 390.18(2)(a)(a) Depth markers shall be installed on all public swimming pools and water attractions that incorporate a water depth over 6 inches.
SPS 390.18(2)(b) (b) Depth markers shall be installed at the maximum and minimum water depths and at all points of slope change.
SPS 390.18(2)(c)1.1. Except as provided in subd. 2., water depth markers shall be installed around the perimeter of the basin at intervals no greater than 25 feet and at lesser intervals when indicating a change in water depth not to exceed 2 feet.
SPS 390.18(2)(c)2. 2. Water depth markers for leisure rivers shall be located every 25 feet on alternate side walls and at all entry points.
SPS 390.18(2)(d)1.1. Depth markers shall be indicated in feet, inches or feet and inches and when abbreviated so indicated as “FT" or “IN."
SPS 390.18(2)(d)2. 2. Depth markers shall be plainly and conspicuously installed at all of the following locations:
SPS 390.18(2)(d)2.a. a. On the vertical basin wall except where no portion of the basin wall is visible and above the waterline.
SPS 390.18(2)(d)2.b. b. On the top of the coping or edge of the deck next to the basin.
SPS 390.18 Note Note: Additional depth markings may also be indicated in metric.
SPS 390.18(2)(e) (e) When additional depth markers are indicated in metric, “meters" shall be abbreviated as “M."
SPS 390.18(2)(f) (f) All water depths indicated on depth markers shall be the depth at the location of the depth marker.