SPS 382.40(8)(i)3. 3. The department may require a water quality analysis to be done for a new or repaired water supply system. The analysis shall be performed in accordance with acceptable nationally recognized laboratory practices. If the water supply system has been disinfected, water samples for the analysis may not be taken sooner than 24 hours after disinfection.
SPS 382.40 Note Note: See s. SPS 384.30 (1) regarding the bending of pipe and protection from puncture.
SPS 382.40(8)(i)4. 4. New or repaired combination water services or combination private water mains shall be flushed and disinfected prior to use in accordance with NFPA 24.
SPS 382.40(8)(j) (j) Water softeners. Ion exchange water softeners used primarily for water hardness reduction that, during regeneration, discharge a brine solution shall be of a demand initiated regeneration type equipped with a water meter or a sensor unless a wastewater treatment system downstream of the water softener specifically documents the reduction of chlorides.
SPS 382.40(8)(k) (k) Locating requirements.
SPS 382.40(8)(k)1.1. A means to locate buried non-metallic water services and private water mains connected to municipal supply systems shall be provided in accordance with the options under s. SPS 382.30 (11) (h), except as provided in subds. 2. and 3.
SPS 382.40(8)(k)2. 2. Tracer wire insulation color for non-metallic, potable water pipe shall be blue.
SPS 382.40(8)(k)3. 3. Tracer wire insulation color for non-metallic, non-potable water pipe shall be purple.
SPS 382.40 History History: 1-2-56; r. and recr. Register, November, 1972, No. 203, eff. 12-1-72; r. and recr. Register, February, 1979, No. 278, eff. 3-1-79; renum. from H 62.13, Register, July, 1983, No. 331, eff. 8-1-83; renum. from ILHR 82.13 and r. and recr. (2) (b) and (4) (d) 1., am. (4) (c) 3. and (6) (a) (intro.), cr. (6) (b), Register, February, 1985, No. 350, eff. 3-1-85; r. and recr. Register, May, 1988, No. 389, eff. 6-1-88; am. (5) (d) 5. a., r. and recr. (7) (h) 1. and (8) (c), renum. (8) (c) 2. to 6. to be (8) (b) 4. to 8. and am. (8) (b) 4. c., Register, August, 1991, No. 428, eff. 9-1-91; am. (8) (b) 1. and 2., Register, April, 1992, No. 436, eff. 5-1-92; renum. (3) (c) and (8) (a) to be (3) (c) 2. and (8) (a) 1. and am. (8) (a) 1., cr. (3) (c) 1., (e), (8) (a) 2. and Table 82.40-9, am. (7) (c), r. (3) (b) 1. b. and c., Register, February, 1994, No. 458, eff. 3-1-94; r. (5) (b) 3., renum. (5) (b) 4., 5. to be (5) (b) 3., 4., Register, December, 1996, No. 480, eff. 4-1-96; correction in (5) (b) 3., made under s. 13.93 (2m) (b) 7., Stats., Register, October, 1996, No. 490; r. and recr. (5) (b), Register, February, 1997, No. 494, eff. 4-1-97; reprinted to restore dropped copy, Register, April, 1997, No. 496; am. (3) (e) and (8) (b) 1. and 2., r. (8) (b) 3. and cr. (3) (f) and (8) (j), Register, April, 2000, No. 532, eff. 7-1-00; except (3) (f) eff. 5-1-00; cr. (3) (d) 3., am. (8) (g) and (i) 2., Register, December, 2000, No. 540, eff. 1-1-01; except (3) (d) 3., eff. 9-1-01; CR 02-002: r. and recr. (3) (a), (d) 1. (intro.) to b., (7) (h), (8) (c) and Tables 82.40-4 to 11, cr. (3) (a) 2., (c) 3. and (d) 1. h., am. (3) (b) 1., (4) (c) 1. b. and 2. b., (7) (d) 1. a. and b., (8) (d) 4., (g), and Tables 82.40-1 and 2, r. (3) (e), renum. (3) (f) and (8) (b) 4. to 8. to be (3) (e) and (8) (b) 3. to 7., Register April 2003 No. 568, eff. 5-1-03; CR 02-129: am. (4) (c) 1. b. Register January 2004 No. 577, eff. 2-1-04, correction in (8) (b) 5. made under s. 13.93 (2m) b. 7., Stats., Register January 2004 No. 577; CR 04-035: r. (3) (e) 2. c., r. and recr. Table 82.40-9, cr. (8) (i) 4. Register November 2004 No. 587, eff. 12-1-04; CR 06-120: r. and recr. (3) (e) 2. b., cr. (3) (e) 2. c. Register February 2008 No. 626, eff. 3-1-08; CR 07-069: cr. (8) (k) Register February 2008 No. 626, eff. 3-1-08; CR 07-100: am. (8) (b) 2. Register September 2008 No. 633, eff. 10-1-08; CR 08-055: am. (3) (b) 1. b., (d) 3. (intro.), (5) (c), (6) (a), (7) (d) 1. b., (8) (b) 2., (j), Tables 82.40-1 and 82.40-2, r. and recr. (3) (e), (8) (e) 2., cr. (8) (b) 8., (d) 3. b. and Table 82.40-3e, renum. (8) (d) 3. to be (8) (d) 3. a. Register February 2009 No. 638, eff. 3-1-09; CR 10-064: am. (3) (a) (title), (c) 1., (5) (a), (6) (a), (8) (b) 3. to 6.,Table 82.40-8 (title) and Table 82.40-10 (title), r. and recr. (3) (d) 1., renum. (3) (d) 2., 3. and Table 82.40-1 to be (3) (d) 3., 4. and Table 82.40-1b, cr. (3) (d) 2., (8) (b) 9., Table 82.40-1a, r. (9) Register December 2010 No. 660, eff. 1-1-11; CR 10-103: r. (3) (e) 2. b. to 2. d., renum. (3) (e) 2. a. to (3) (e) 2., Register August 2011 No. 668, eff. 9-1-11; correction in (2), (3) (a) 1., 2., (c) 2., 3. a., (d) 1. a., b., e., g., 2., 4. b., (5) (b) 4., (c), (d) 5. a., e., (6) (a), (7) (c), (8) (a) 1., (b) 3. c., 5. b., (d) 1., 6., (k) 1., Table 382.40-3e made under s. 13.92 (4) (b) 6., 7., Stats., Register December 2011 No. 672; CR 11-031: r. (8) (b) 2., 8., renum. (8) (b) 3., 4. to (8) (b) 2., 3., am. (8) (b) 3., cr. (8) (b) 4., am. (8) (b) 5. (intro.), 7. Register June 2013 No. 690, eff. 7-1-13; CR 13-046: am. (6) (a) Register December 2013 No. 696, eff. 1-1-14.
Table 382.40-4
- See PDF for diagram PDFMAXIMUM ALLOWABLE LOAD FOR COPPER TUBING-TYPE K, ASTM B88; (C=150)
Table 382.40-5
- See PDF for diagram PDFMAXIMUM ALLOWABLE LOAD FOR COPPER TUBING-TYPE L, ASTM B88; (C=150)
Table 382.40-6
- See PDF for diagram PDFMAXIMUM ALLOWABLE LOAD FOR COPPER TUBING-TYPE M, ASTM B88; (C=150)
Table 382.40-7
- See PDF for diagram PDFMAXIMUM ALLOWABLE LOAD FOR GALVANIZED STEEL PIPE, SCHEDULE 40, ASTM A53; (C=150)
Table 382.40-8
- See PDF for diagram PDFCHLORINATED POLYVINYL CHLORIDE TUBING, ASTM D2846 and F442, SDR 11; (C=150)
Table 382.40-9
MAXIMUM ALLOWABLE LOAD FOR CROSSLINKED POLYETHYLENE (PEX) TUBING,
ASTM F876 and F877; (C=150) - See PDF for diagram PDF
Table 382.40-10
- See PDF for diagram PDFMAXIMUM ALLOWABLE LOAD FOR CHLORINATED POLYVINYL CHLORIDE TUBING, ASTM F442, SDR 13.5; (C=150)
Table 382.40-11
- See PDF for diagram PDFMAXIMUM ALLOWABLE LOAD FOR POLYETHYLENE ALUMINUM POLYETHYLENE TUBING (PexAlPex), ASTM F1281; (C=150)
SPS 382.41 SPS 382.41Cross connection control.
SPS 382.41(1) (1) Scope. The provisions of this section set forth the requirements for the protection of water within water supply systems when and where there is the possibility of contamination due to cross connections or backflow conditions.
SPS 382.41 Note Note: The Department of Natural Resources governs the operation and design of community water systems and under s. NR 811.09 requires the supplier of water to develop and implement a comprehensive cross connection control program.
SPS 382.41(2) (2)Materials.
SPS 382.41(2)(a)(a) All devices, assemblies and mechanisms intended to protect water supplies relative to cross connection or backflow shall be of a type recognized and approved in accordance with ch. SPS 384 and as described in sub. (4).
SPS 382.41(2)(b) (b) All methods including barometric loops and air gaps intended to protect water supplies relative to cross connection or backflow shall be constructed of materials suitable for water supply systems in accordance with ch. SPS 384.
SPS 382.41(3) (3)General requirements. Water supply systems and the connection of each plumbing fixture, piece of equipment, appliance or nonpotable water piping system shall be designed, installed and maintained in such a manner to prevent the contamination of water supplies by means of cross connections.
SPS 382.41(3)(a) (a) Types of cross connection control.
SPS 382.41(3)(a)1.1. Water supply systems shall be protected against contamination due to cross connections or backflow conditions by one of the methods or devices specified in Table 382.41-1 depending upon the situation or Table 382.41-2 depending upon the specific application or use, and the limitations specified in sub. (4).
SPS 382.41(3)(a)2. 2. For the situations described in par. (b) 3., cross connection control shall be provided as part of the fixture fitting outlet or in the water supply piping for the fixture fitting outlet.
SPS 382.41(3)(b) (b) Classifications. For the purposes of this section:
SPS 382.41(3)(b)1. 1. The designation of a high hazard or low hazard situation shall be determined on the basis of how a toxic or nontoxic solution is intended or recommended by the manufacturer of the solution to interface with the potable water supply system.
SPS 382.41(3)(b)2.a.a. A continuous pressure situation shall be considered to exist when a pressure greater than atmospheric within the water supply system exists for more than 12 continuous hours.
SPS 382.41(3)(b)2.b. b. A noncontinuous pressure situation shall be considered to exist if the conditions in subd. 2. a. do not occur.
SPS 382.41(3)(b)3. 3. A high hazard cross connection situation shall be considered to exist for a connection of the water supply system to:
SPS 382.41(3)(b)3.a. a. Any part of the drain system; and
SPS 382.41(3)(b)3.b. b. Any other piping system conveying water from nonpotable sources, including but not limited to lakes, rivers, streams or creeks.
SPS 382.41(3)(b)4. 4. Except as provided in subd. 5., a high hazard cross connection situation shall be considered to exist at:
SPS 382.41(3)(b)4.a. a. A water supply hose bibb, faucet, wall hydrant, sill cock or other outlet which terminates with hose threads allowing a hose to be attached;
SPS 382.41(3)(b)4.b. b. A water supply faucet, wall hydrant or other outlet which terminates with a serrated nipple allowing a hose to be attached;
SPS 382.41(3)(b)4.c. c. A water supply faucet, hydrant or outlet serving a sink used for building maintenance in a public building;
SPS 382.41(3)(b)4.d. d. A chemical pot-feeder or automatic chemical feeder is installed to serve a boiler, cooling tower or chilled water system; and
SPS 382.41(3)(b)4.e. e. In the water supply piping connecting to the outlet of a fire hydrant for any purpose other than fire suppression.
SPS 382.41(3)(b)5. 5. A cross connection shall not be considered to exist at the hose threaded outlet installed for the sole purpose of:
SPS 382.41(3)(b)5.a. a. Draining a water supply system or any portion thereof;
SPS 382.41(3)(b)5.b. b. Obtaining water quality samples of the water supply system or any portion thereof; or
SPS 382.41(3)(b)5.c. c. Connecting individual residential automatic clothes washers.
SPS 382.41(3)(b)6.a.a. A high hazard situation shall be considered to exist for the connection of 2 water supply systems one supplied by a public water supply and the other system supplied by a private well.
SPS 382.41 Note Note: The interconnection of a public water supply system and another source of water is addressed in s. NR 811.09 and must be approved by the Department of Natural Resources.
SPS 382.41(3)(b)6.b. b. Except as provided in subd. 7., a low hazard situation shall be considered to exist for the connection of a piping system, including but not limited to automatic fire sprinkler systems, standpipe systems, and processing purposes, which provides potable water for nonrequired potable water uses.
SPS 382.41 Note Note: Cross connection control devices used in conjunction with automatic fire sprinkler systems are to be listed by an acceptable testing agency for such an application under the standards governing the design and installation of automatic fire sprinkler systems.
SPS 382.41(3)(b)7. 7. A cross connection situation shall not be considered to exist when a multipurpose piping system serves a one- or 2- family dwelling provided the sprinkler system is constructed of materials and joints suitable for water distribution systems as specified in ss. SPS 384.30 (4) (e) and 384.40, respectively.
SPS 382.41(3)(c) (c) Containment.
SPS 382.41(3)(c)1.1. For sewerage treatment facilities which are required to conform with ch. NR 110, in addition to the cross connection control required for each potable water usage or water outlet, a reduced pressure principle backflow preventer shall be installed:
SPS 382.41(3)(c)1.a. a. In the water service to each building or structure within the complex;
SPS 382.41(3)(c)1.b. b. In the private water main upstream of all water services serving the facility; or
SPS 382.41(3)(c)1.c. c. In the water distribution system upstream of all water outlets and in the process piping network upstream of all points of use, if both a water distribution system and a process network is contained within the same building or structure.
SPS 382.41(3)(c)2. 2. For marinas, wharves and docks where potable water outlets are provided to serve boats or ships, in addition to the cross connection control required for each potable water outlet or usage, a reduced pressure principle backflow preventer shall be installed in the water supply system to limit backflow into the water supply source.
SPS 382.41(3)(c)3. 3. The installation of a cross connection control device in the water supply system for a building or structure shall not alleviate the requirement to provide cross connection control for the connection of each plumbing fixture, piece of equipment, appliance or other piping system.
SPS 382.41(3)(d) (d) Prohibitions. The use of a toxic solution as a heat transfer fluid in single-wall heat exchanger for potable water is prohibited.
SPS 382.41(3)(e) (e) Existing automatic fire sprinkler systems. An alteration, modification or addition to an existing automatic fire sprinkler shall necessitate conformance with this section, if the:
SPS 382.41(3)(e)1. 1. Existing water supply line to the existing sprinkler system is increased in diameter; or
SPS 382.41(3)(e)2. 2. Existing device or method which had been previously recognized to address cross connection concerns is to be removed or replaced. - See PDF for table PDF - See PDF for table PDF
a See limitation listed under s. SPS 382.41 (4) (c) 1. a. - See PDF for table PDF
SPS 382.41(4) (4)Limitations.
SPS 382.41(4)(a)(a) Cross connection control devices shall be limited in use in accordance with the respective standard, unless otherwise specifically permitted under this subsection.
SPS 382.41(4)(b)1.1. Except for a deck-mounted device, a pipe applied atmospheric vacuum breaker shall be installed such that the bottom of the device or the critical level mark on the device is at least 6 above all of the following:
SPS 382.41(4)(b)1.a. a. The flood level rim of the receptor serving the water supply port.
SPS 382.41(4)(b)1.b. b. The highest point downstream from the device where backpressure would be created.
SPS 382.41(4)(b)1.c. c. The highest point of an injection or aspiration port.
SPS 382.41(4)(b)2. 2. A deck-mounted pipe applied atmospheric type vacuum breaker shall be installed such that the bottom of the device or the critical level mark on the device is at least one inch above all of the following:
SPS 382.41(4)(b)2.a. a. The flood level rim of the receptor serving the water supply port.
SPS 382.41(4)(b)2.b. b. The highest point downstream from the device where backpressure would be created.
SPS 382.41(4)(b)2.c. c. The highest point of an injection or aspiration port.
SPS 382.41(4)(c)1.a.a. The use a of a hose connection backflow preventer, dual check backflow preventer wall hydrant-freeze resistant or a hose connection vacuum breaker in a continuous pressure situation shall be limited to campgrounds and marinas.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.