This is the preview version of the Wisconsin State Legislature site.
Please see http://docs.legis.wisconsin.gov for the production version.
SPS 382.31(17m)(e)1. 1. The AAV must be installed in the vertical position, plus or minus 15 degrees from plumb.
SPS 382.31(17m)(e)2. 2. The vent system being served by the AAV may have horizontal offsets located less than 36 inches above the floor on which the fixtures are installed provided the vent does not connect to another vent.
SPS 382.31(17m)(e)3. 3. The installation location of the AAV shall conform with all of the following:
SPS 382.31(17m)(e)3.a. a. A minimum of 4 inches above the top of the horizontal pipe being served (See Note).
SPS 382.31(17m)(e)3.b. b. No more than 20 inches below the flood rim of any fixture served by this product (See Note).
SPS 382.31(17m)(e)3.c. c. At least 6 inches above insulation materials (See Note).
SPS 382.31(17m)(e)3.d. d. In an accessible area.
SPS 382.31(17m)(e)3.e. e. Within a space that allows air to enter the product and has an opening equivalent to requirements in sub. (14).
SPS 382.31(17m)(e)3.f. f. With at least one 3-inch or larger diameter vent, serving the same building drain on which the AAV is installed, which extends to the atmosphere outside of the building.
SPS 382.31 Note Note: The distance is measured from termination of the vent pipe to the point specified in the rule.
SPS 382.31(17m)(f) (f) AAVs shall be tested. The AAV shall be tested prior to or after installation. The AAV shall be subjected to a pressure equal to 1 inch of water column. After observing for 1 minute, if the pressure falls .5 of an inch or less, it will be considered a passing AAV.
SPS 382.31(17m)(g) (g) When an AAV is installed in a building, the contractor shall provide the owner with a copy of the manufacturer's written AAV description.
SPS 382.31(18) (18)Prohibited uses. A vent or vent system shall not be used for purposes other than the venting of the plumbing system.
SPS 382.31(18)(a) (a) Boiler blowoff basin vents. Vent piping from boiler blowoff basins shall not be connected to a vent or vent system serving a sanitary drain system, storm drain system or chemical waste system.
SPS 382.31(18)(b) (b) Chemical waste vents. Vent piping for chemical waste systems shall not be connected to a vent system serving a sanitary drain system or storm drain system.
SPS 382.31(18)(c) (c) Steam vents. Vents serving steam operated sterilizers, cleansing or degreasing equipment, pressing machines or any other apparatus which normally discharges steam into the vent shall not be connected to a vent or a vent system serving a sanitary drain system, storm drain system or chemical waste system.
SPS 382.31 History History: Cr. Register, February, 1985, No. 350, eff. 3-1-85; am. (11) (a), (17) (b) 3. b. and (c) 2. b., r. and recr. (11) (b), r. (13) (a) 2., cr. (17) (b) 3. c. and (c) 2. c., Register, May, 1988, No. 389, eff. 6-1-88; reprinted to correct (17) (c) 4., Register, February, 1991, No. 422; cr. (4) (b) 4. and (17) (a) l. f., r. and recr. (5) (c) l. c. and (17) (c) 4., am. (5) (c) 2. c., (10) (intro.), (b) 1., (11) (b), (17) (a) l. e. and (17) (b), Register, August, 1991, No. 428, eff. 9-1-91; am. (6) (c), (7) (b), (10) (intro.), (a), (b) 1., (e), (13) (a) 1. c., (c) (intro.), 1. and 4., r. (16) (h), Register, February, 1994, No. 458, eff. 3-1-94; CR 02-002: renum. (8) to be (8) (a) and am., cr. (8) (b), (14) (j) and (16) (h), am. (11) (a), (12) (intro.), (a), (13) (c) 1. (17) (a) 1. (intro.) to b., and Table 82.31-4, r. and recr. Table 82.31-5, Register April 2003 No. 568, eff. 5-1-03; CR 08-055: am. (4) (a), (10) (c), (13) (a) 1. e., (14) (g) 2., (17) (a) 1. e., (b) 1. and 3., r. and recr. (5) and (6), r. (17) (a) 1. f. Register February 2009 No. 638, eff. 3-1-09; correction in (17) (a) 1. (intro.) made under s. 13.92 (4) (b) 7., Stats., Register February 2009 No. 638; CR 10-064: am. (5) (a) 2., (6) (c), (17) (a) 2., r. (14) (g) 2., renum. (14) (g) 3. and 4. to be (14) (g) 2. and 3. Register December 2010 No. 660, eff. 1-1-11; correction in (14) (g) (intro.) made under s. 13.92 (4) (b) 7., Stats., Register December 2010 No. 660; correction in (2), (5) (a) 2., (9) (a) 1., 2., (12) (d), (14) (a) (intro.), (b) 1., (c), (d), (e), (f), (g) 1., 2., 3., (i) 1. a., b., (j), (17) (a) 1. b., d., e., (b) 3. a., 6., (c) 2. a., 6. made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 23-006: r. and recr. (11) (a), (16) (d), (e), am. (17) (intro.), cr. (17) (d), (17m) Register September 2023 No. 813, eff. 10-1-23; correction in (16) (h), made under 13.92 (4) (b) 7., Stats., and correction in (16) (e), (17m) (e) 3. e., f., (f) made under s. 35.17, Stats., Register September 2023 No. 813.
SPS 382.32 SPS 382.32Traps and direct fixture connections.
SPS 382.32(1)(1)Scope. The provisions of this section set forth the requirements for the types and installation of traps and direct fixture connections.
SPS 382.32(2) (2)Materials. All traps and fixture connections shall be of approved materials in accordance with ch. SPS 384.
SPS 382.32(3) (3)General. Each plumbing fixture, each compartment of a plumbing fixture and each floor drain shall be separately trapped by a water seal trap, except as provided in par. (a) or as otherwise permitted by this chapter. A fixture shall not be double trapped.
SPS 382.32(3)(a) (a) Trap exceptions. The plumbing fixtures listed in subds. 1. to 3. shall not be required to be separately trapped:
SPS 382.32(3)(a)1. 1. Fixtures having integral traps;
SPS 382.32(3)(a)2. 2. Compartments of a combination plumbing fixture installed on one trap, provided:
SPS 382.32(3)(a)2.a. a. No compartment is more than 6" deeper than any other;
SPS 382.32(3)(a)2.b. b. The distance between the compartments' waste outlets farthest apart does not exceed 30"; and
SPS 382.32(3)(a)2.c. c. No compartment waste outlet is equipped with a food waste grinder.
SPS 382.32(3)(a)3. 3. Storm drains as provided in s. SPS 382.36 (12) (a).
SPS 382.32 Note Note: Residential exclusion see s. SPS 325.01 (4) (a).
SPS 382.32(3)(b) (b) Trap seals. Each trap shall provide a liquid seal depth of not less than 2" and not more than 4", except as otherwise specified in this chapter.
SPS 382.32(3)(c) (c) Loss of trap seal. A trap seal primer valve may be installed on a trap subject to high rates of evaporation.
SPS 382.32(3)(c)1. 1. A trap seal primer valve or other means of trap seal protection acceptable to the department shall be provided for a trap subject to seal loss due to evaporation.
SPS 382.32 Note Note: Liquids acceptable to use for reducing trap seal evaporation include mineral oil, vegetable oil, propylene glycol and glycerin.
SPS 382.32(3)(c)2. 2. Trap seal primer valves shall conform to ASSE 1018 or ASSE 1044.
SPS 382.32 Note Note: A list of referenced standards is contained in ch. SPS 381.
SPS 382.32(3)(c)3. 3. Barrier type trap seal protectors for floor drains shall conform to ASSE 1072.
SPS 382.32(3)(d) (d) Design. Traps shall be self-scouring and shall not have interior partitions, except where such traps are integral with the fixture. Uniform diameter P-traps shall be considered self-scouring.
SPS 382.32(3)(e) (e) Size.
SPS 382.32(3)(e)1.1. Except as provided in subd. 2., traps shall be of diameters not less than those specified in Table 382.30-1.
SPS 382.32(3)(e)2. 2. The minimum trap diameter for a trap serving a shower replacing a non-public residential-type bathtub is 1.5 inches provided each of the following apply:
SPS 382.32(3)(e)2.a. a. The shower shall have no more than one control valve and not allow for the operation of more than one showerhead simultaneously.
SPS 382.32(3)(e)2.b. b. It shall be permissible under this approval to use a diverter valve that feeds up to 2 showerheads provided the showerheads cannot be used simultaneously.
SPS 382.32(3)(e)2.c. c. The showerhead shall have a maximum flow rate of 2.5 gallons per minute.
SPS 382.32(3)(f) (f) Prohibited traps. The installation of the types of traps listed in subds. 1. to 6. shall be prohibited:
SPS 382.32(3)(f)1. 1. Bell traps;
SPS 382.32(3)(f)2. 2. Drum traps, except where specifically approved by the department;
SPS 382.32(3)(f)3. 3. S-traps which are not integral parts of fixtures;
SPS 382.32(3)(f)4. 4. Separate fixture traps which depend on interior partitions for the trap seal;
SPS 382.32(3)(f)5. 5. Traps which depend upon moving parts to maintain the trap seal; and
SPS 382.32(3)(f)6. 6. Traps which in case of defect would allow the passage of sewer air.
SPS 382.32(4) (4)Installation.
SPS 382.32(4)(a) (a) Setting of traps. All traps shall be rigidly supported and set true with respect to the water level and so located as to protect the water seals, and shall be protected from freezing and evaporation.
SPS 382.32(4)(b) (b) Distance from fixture drain outlets.
SPS 382.32(4)(b)1.1. `Vertical distance.' Except as provided in subd. 1. a. to c., the vertical distance between the top of the fixture drain outlet and the horizontal center line of the trap outlet shall not exceed 15".
SPS 382.32(4)(b)1.a. a. The vertical distance between the top of the strainer of a floor drain or the opening of a standpipe receptor and the horizontal center line of the trap outlet shall not exceed 36".
SPS 382.32(4)(b)1.b. b. The vertical distance between the top of the fixture drain outlet of a pedestal fixture or a cuspidor and the horizontal center line of the trap outlet shall not exceed 60".
SPS 382.32(4)(b)1.c. c. The vertical distance between the water level in the bowl of a floor outlet water closet or floor outlet clinic sink and the center line of the horizontal portion of the fixture drain may not exceed 36 inches.
SPS 382.32(4)(b)1.d. d. The vertical distance from the inlet to the horizontal centerline of the fixture drain for a campsite receptor, exterior storm drain inlet, or a receptor for a sanitary dump station may exceed 3 feet so as to permit the trap to be installed below the predicted depth of frost.
SPS 382.32(4)(b)1.e. e. The vertical distance of a floor outlet fixture between the top of the fixture drain outlet and the horizontal center line of the trap outlet may not exceed 18 inches.
SPS 382.32(4)(b)2. 2. `Horizontal distance.' Except as provided in subd. 2. a. and b., the horizontal distance between the vertical centerline of a fixture drain outlet and the vertical centerline of the trap inlet shall not exceed 15".
SPS 382.32(4)(b)2.a. a. The horizontal distance for a pedestal drinking fountain shall not exceed 24".
SPS 382.32(4)(b)2.b. b. The horizontal distance for an exterior sanitary area drain or a residential garage floor drain discharging through an interior trap shall not exceed 25 feet.
SPS 382.32(4)(b)2.c. c. The minimum horizontal distance between the vertical centerline of the outlet from a floor-mounted water closet and a 3-inch double tee shall be 30 inches.
SPS 382.32 Note Note: See ch. SPS 382 Appendix for further explanatory material.
SPS 382.32(5) (5)Direct fixture drain connection. Except as provided in s. SPS 382.33, all plumbing fixtures and appliances discharging wastes shall connect directly to a drain system.
SPS 382.32(5)(a) (a) Floor drains.
SPS 382.32(5)(a)1.1. Floor drains shall be so located as to be accessible for cleaning purposes.
SPS 382.32(5)(a)2. 2. A floor drain receiving the wash from garbage cans shall be at least 3" in diameter.
SPS 382.32(5)(b) (b) Kitchen sinks. Horizontal drain piping serving a kitchen sink trap shall not connect to vertical drain piping by means of a double sanitary tee where an appliance with pump discharge or a food waste grinder are installed.
SPS 382.32(5)(c) (c) Water closets. A water closet shall discharge through a drain pipe or fitting with a minimum diameter of 3".
SPS 382.32(5)(c)1. 1. A floor mounted wall outlet water closet shall connect to a 4 inch or 4 × 3 inch closet collar fitting or to a horizontal or vertical carrier type fitting.
SPS 382.32(5)(c)2. 2. A floor outlet water closet shall connect to a 4 inch or 4 × 3 inch closet collar fitting.
SPS 382.32(5)(c)3. 3. A wall mounted wall outlet water closet shall connect to a horizontal or vertical carrier type fitting.
SPS 382.32(5)(c)4. 4. Two water closets discharging to a vertical drain from opposite sides by means of the same fitting shall be installed in accordance with subd. 4. a. and b.
SPS 382.32(5)(c)4.a. a. Where the vertical drain is 3" in diameter, the fitting for floor outlet water closets shall be a 3 inch double wye pattern fitting.
SPS 382.32(5)(c)4.b. b. Where the water closets are wall outlet types the fitting shall be a double wye pattern fitting or a carrier-type fitting.
SPS 382.32(5)(d) (d) Blowout-type fixtures. Blowout-type plumbing fixtures shall be installed in accordance with the approval of the department.
SPS 382.32 History History: Cr. Register, February, 1985, No. 350, eff. 3-1-85; am. (4) (a), cr. (5) (intro.) and (d), Register, May, 1988, No. 389, eff. 6-1-88; am. (4) (b) 1. b., Register, April, 2000, No. 532, eff. 7-1-00; CR 02-002: r. and recr. (3) (c) 1. and (4) (b) 2., am. (4) (b) 1. b., cr. (4) (b) 1. d., Register April 2003 No. 568, eff. 5-1-03; CR 02-129: am. (3) (intro.) Register January 2004 No. 577, eff. 2-1-04; CR 04-035: am. (3) (a) 3. Register November 2004 No. 587, eff. 12-1-04; CR 08-055: cr. (4) (b) 2. c. Register February 2009 No. 638, eff. 3-1-09; correction in (2), (3) (a) 3., (e), (5) (intro.) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 23-006: am. (3) (c) 2., cr. (3) (c) 3., renum. (3) (e) to (3) (e) 1. and am., cr. (3) (e) 2., am. (4) (b) 1., c., cr. (4) (b) 1. e., am. (5) (b), (c) 2. Register September 2023 No. 813, eff. 10-1-23.
SPS 382.33 SPS 382.33Indirect and local waste piping.
SPS 382.33(1)(1)Scope.
SPS 382.33(1)(a)(a) The provisions of this section set forth the requirements for the installation of indirect waste piping and local waste piping.
SPS 382.33(1)(b) (b) Indirect waste piping and local waste piping draining the fixtures, appliances and devices having a public health concern, including but not limited to those listed in Table 382.33-1, shall be considered as plumbing and shall comply with the provisions of this section.
SPS 382.33(2) (2)Materials. Indirect waste piping more than 30" in length and all local waste piping shall be of approved materials in accordance with ch. SPS 384.
SPS 382.33(3) (3)Size. Except as provided in pars. (a) and (b), indirect waste piping more than 30" in length and all local waste piping shall be sized in accordance with s. SPS 382.30.
SPS 382.33(3)(a) (a) Indirect or local waste piping not exceeding 20 feet in length for refrigerated food display cases may not be less than one inch in diameter.
SPS 382.33(3)(b) (b) Indirect waste piping, attached to an appliance, appurtenance or equipment through which pressurized waste is discharged, shall be sized in accordance with specifications of the manufacturer of the appliance, appurtenance or equipment. - See PDF for table PDF
SPS 382.33(4) (4)Installation. Indirect waste piping and local waste piping shall be so installed as to permit access for flushing and cleaning.
SPS 382.33(5) (5)Traps.
SPS 382.33(5)(a) (a) Indirect waste piping.
Loading...
Loading...
Published under s. 35.93, Stats. Updated on the first day of each month. Entire code is always current. The Register date on each page is the date the chapter was last published.