SPS 363.0405 Lighting systems.
SPS 363.0406 Requirements for additional efficiency package options.
SPS 363.0407 Total building performance.
SPS 363.0408 System commissioning.
SPS 363.0503 Alterations.
SPS 363.0600 Referenced standards.
SPS 363.5101 Administration and enforcement.
SPS 363.5202 Substitutions.
SPS 363.5302 Exterior design conditions.
SPS 363.5303 Materials, systems, and equipment.
SPS 363.5401 Certificate.
SPS 363.5402 Building envelope requirements.
SPS 363.5404 Lighting equipment.
SPS 363.5405 Calculation software tools.
SPS 363.5503 Alterations.
SPS 363.5600 Referenced standards.
SPS 363.001
SPS 363.001 Purpose. This chapter regulates the design and construction of buildings for the effective use of energy. This chapter provides flexibility to permit the use of innovative approaches and techniques to achieve the effective use of energy. This chapter is not intended to abridge safety, health or environmental requirements contained in other applicable codes.
SPS 363.001 History
History: CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08.
SPS 363.002(1)(1)
Mixed occupancy. Where a building includes both commercial and residential occupancies, each occupancy shall be separately considered and meet the applicable provisions of IECC commercial provisions for commercial occupancies or IECC residential provisions for residential occupancies.
SPS 363.002(2)
(2) Exempt buildings and structures. Glazed structures or glazed portions of buildings used for the production of plant life or for maintaining plant life as the primary purpose are exempt from the building thermal envelope provisions of
chs. SPS 361 to
366, provided that glazed portions are separated from the remainder of the building by building thermal envelope assemblies complying with this chapter.
SPS 363.002 History
History: CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08;
CR 10-103: r. and recr. (2)
Register August 2011 No. 668, eff. 9-1-11;
CR 16-094: am. (1), (2),
Register April 2018 No. 748 eff. 5-1-18.
subch. II of ch. SPS 363
Subchapter II — Changes, Additions or Omissions to the International Energy Conservation Code (IECC)
SPS 363.0100
SPS 363.0100 Changes, additions or omissions to IECC. Changes, additions or omissions to the IECC are specified in this subchapter and are rules of the department and are not requirements of the IECC.
SPS 363.0100 Note
Note: The sections in this chapter are generally numbered to correspond to the numbering used in the IECC, with a 0 to the right of the decimal point referring to the commercial provisions and a 5 to the right of the decimal point referring to the residential provisions of the IECC, i.e., s.
SPS 363.0101 refers to IECC section C101 and s.
SPS 363.5101 refers to section IECC section R101.
SPS 363.0100 History
History: CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08.
SPS 363.0101
SPS 363.0101 Administration and enforcement. The requirements in IECC sections C101 and C103 to C109 are not included as part of this chapter.
SPS 363.0202(1)(1)
Additions. This is a department definition for this chapter in addition to the definitions in IECC section C202: “Effective aperture" or “EA" means for windows, the visible light transmittance times the window wall ratio per wall; and for sky lights, the well efficiency times the visible light transmittance times the sky light area times 0.85 divided by the gross exterior roof area.
SPS 363.0202(2)
(2) Substitutions. Substitute the following for the corresponding definitions listed in IECC section C202:
SPS 363.0202(2)(b)
(b) “Daylight responsive control” means a device or system that provides the automatic control of lamps and luminaires located in daylight zone only or a manual control of lamps or luminaires located in daylight zone only in such manner that at least 50% of the lamps are controlled in a reasonably uniform illumination pattern per IECC
section C405.2.2.2, with the capability for the lamps to be operated at 100% or 0% of their design lighting capability.
SPS 363.0202 History
History: CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08; correction in (2) made under s.
13.92 (4) (b) 7., Stats.,
Register August 2011 No. 668; correction in (2) made under s.
13.92 (4) (b) 7., Stats.,
Register December 2011 No. 672;
CR 16-094: am. (1), renum. (2) to (2) (intro.) and am., cr. (2) (a), (b),
Register April 2018 No. 748 eff. 5-1-18.
SPS 363.0302
SPS 363.0302 Exterior design conditions. These are department rules in addition to the requirements in IECC section C302: The exterior design temperatures used for heating and cooling load calculations shall be as specified under Table 363.0302.
SPS 363.0302 History
History: CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08; correction made under s.
13.92 (4) (b) 7., Stats.,
Register December 2011 No. 672.
SPS 363.0303
SPS 363.0303
Materials, systems and equipment. These are department rules in addition to the requirements in IECC section C303.
SPS 363.0303(1)
(1) General. Except as specified in
sub. (2), when available, information on thermal properties, performance of building envelope sections, and components and heat transfer shall be obtained from ASHRAE Handbook of Fundamentals.
SPS 363.0303 Note
Note: Use of the ASHRAE Handbook of Fundamentals standard in effect at the time of publication of the 2015 IECC constitutes compliance with this section.
SPS 363.0303(2)(a)(a) When the information is not available from ASHRAE Handbook of Fundamentals, the data shall be obtained from laboratory or field-test measurements. If laboratory or field test measurements are used for envelope heat transmission, the measurements shall be obtained using one of the following test methods:
SPS 363.0303(2)(b)
(b) For foam plastic insulation that incorporates a substance other than air as the insulating medium, laboratory or field tests shall be conducted on representative samples that have been aged for the equivalent of 5 years or until the R–Value has stabilized to determine thermal properties or performance. The tests shall be conducted by an independent third party.
SPS 363.0303(2)(c)
(c) Integrally insulated concrete masonry systems within the scope of the National Concrete Masonry Association (NCMA) shall be evaluated for the thermal performance of the masonry or concrete units in accordance with one of the following:
SPS 363.0303(2)(c)1.
1. NCMA Evaluation Procedures for the Integrally-Insulated Concrete Masonry Walls.
SPS 363.0303(2)(d)
(d) All other concrete or masonry units not within the scope of the NCMA Evaluation Procedures shall comply with one of the following methods for determining the thermal performance of the assembly or system:
SPS 363.0303 History
History: CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08;
CR 09-104: r. (1), (2) (title), renum (2) (a), (b) to be (1), (2) and am.
Register December 2010 No. 660, eff. 1-1-11;
CR 10-103: renum. from Comm 63.0102 and am. (intro.)
Register August 2011 No. 668, eff. 9-1-11; correction in (2) (d) 3. made under s.
13.92 (4) (b) 7., Stats.,
Register December 2011 No. 672;
CR 16-094: am. (2) (a) 2. to 4.,
Register April 2018 No. 748 eff. 5-1-18.
SPS 363.0401(1)
(1)
Additional requirements. This is a department rule in addition to the requirements in IECC section C401.2: All of the following rules shall apply regardless of whether the IECC chapter 4[CE] or ASHRAE 90.1 standard is used to determine compliance:
SPS 363.0401(2)
(2) Automatic receptacle control. The requirements in ANSI/ASHRAE/IESNA 90.1-2013 section 8.4.2 are not included as part of this chapter.
SPS 363.0401(3)
(3) Monitoring. Substitute the following wording for ANSI/ASHRAE/IESNA 90.1-2013 section 8.4.3.1: A measurement device shall be installed in new buildings to monitor total electrical energy use. For buildings with tenants, total electrical energy shall be monitored for the total building or for each individual tenant.
SPS 363.0401(4)
(4) Application. Substitute the following wording for 2015 IECC
section C401.2 condition 2: The requirements of sections C402 to C405.
SPS 363.0401(5)
(5) Compliance requirements. Substitute the following in IECC
section C401.2 condition 3: The requirements of IECC
sections C402.5, C403.2, C404, C405.2, C405.3, C405.4, C405.6, and C407. The building energy cost shall be equal to or less than the standard reference design building.
SPS 363.0401 History
History: CR 06-120: cr.
Register February 2008 No. 626, eff. 3-1-08;
CR 10-103: am. (2)
Register August 2011 No. 668, eff. 9-1-11; correction in (1), (2), (3) made under s.
13.92 (4) (b) 7., Stats.,
Register December 2011 No. 672;
CR 16-094: renum. 363.0501 to 363.0401 (1) and am., cr. (2) to (5),
Register April 2018 No. 748 eff. 5-1-18.
SPS 363.0402(1)(1)
Opaque assemblies. Substitute 2009 IECC Table 502.2 (1)
for 2015 IECC Table C402.1.3 and renumber Table C402.1.3.
SPS 363.0402(2)
(2) Opaque element maximum u-factors. Substitute 2009 IECC Table 502.1.2 for 2015 IECC Table C402.1.4 and renumber Table C402.1.4.
SPS 363.0402 History
History: CR 16-094: cr.,
Register April 2018 No. 748 eff. 5-1-18.
SPS 363.0403(1)(1)
Calculation of heating and cooling loads. The following wording is a department requirement in addition to the requirements in IECC
section C403.2.1: Design heating and cooling loads shall be determined in accordance with
s. SPS 363.0302 and Table 363.0302.
SPS 363.0403(2)
(2) Equipment and system sizing. Substitute the following wording for the requirements and the exceptions in IECC
section C403.2.2: Heating and cooling equipment and systems shall be sized to provide the minimum space and system loads calculated in accordance with
s. SPS 363.0302.
SPS 363.0403(3)
(3) Economizers Simple Hvac Systems. Substitute the following wording for the requirements in IECC
section C403.3: Supply air economizers shall be provided on the following cooling systems:
SPS 363.0403(3)(b)
(b) All other cooling systems
> 54,000 Btu/h. Where a single room or space is supplied by multiple air systems, the aggregate cooling capacity of those systems shall be used in applying this requirement.
SPS 363.0403(4)
(4) Economizers cooling requirements. Substitute the following wording for the title of IECC Table C403.3 (1): MINIMUM BUILDING CHILLED WATER SYSTEM COOLING CAPACITY FOR DETERMINING ECONOMIZER COOLING REQUIREMENTS.
SPS 363.0403(5)
(5) Climate zones 6 and 7. Substitute the following wording for the requirements in IECC
section C403.4.2.3.2.2: For climate zones 6 and 7 as indicated in IECC Figure C301.1 and Table C301.1, if an open-circuit cooling tower is used, then a separate heat exchanger shall be required to isolate the cooling tower from the heat pump loop, and heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop and providing an automatic valve to stop the flow of fluid.
SPS 363.0403(6)
(6) Zone isolation. The requirements in IECC
section C403.2.4.4 are not included as part of
chs. SPS 361 to
366.
SPS 363.0403(7)
(7) Demand controlled ventilation. Substitute the following for the wording, but not the exceptions, in IECC section 403.2.6.1: Demand control ventilation (DCV) is required for spaces larger than 40 people per 1000 sq. ft. (93 m
2) of floor area (as established in IMC Table 403.3) and served by systems with one or more of the following: