SPS 362.2900(1)(a)3. 3. Portable restrooms recognized under ch. SPS 391 may be substituted for water closets required under IBC chapter 29 for buildings accommodating events or temporary occupancies not exceeding 12 consecutive days or as approved by the department.
SPS 362.2900(1)(b) (b) Lavatories. Waterless antiseptic cleansing provisions may be substituted for lavatories required under IBC chapter 29 where systems or devices under par. (a) 2. are substituted for water closets. Where water-based water closets or urinals are used, water-based lavatories shall be provided in numbers to accommodate the number of people served by the water closets and urinals.
SPS 362.2900(2) (2) Permanent outdoor toilets.
SPS 362.2900(2)(a) (a) A permanent outdoor toilet room shall be provided with a suitable approach such as a concrete, gravel or cinder walk.
SPS 362.2900(2)(b) (b) All windows, ventilators, and other openings for a permanent outdoor toilet room shall be screened to limit the entrance of flies, and all doors shall be self closing.
SPS 362.2900(3) (3) Urinals . Urinals shall be placed against walls at least 6 feet 8 inches high.
SPS 362.2900 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 01-139: am. (2) Register June 2002 No. 558, eff. 7-1-02; CR 04-016: am. (2), cr. (4) (b) 3. Register December 2004 No. 588, eff. 1-1-05; CR 06-120: r. and recr. Register February 2008 No. 626, eff. 3-1-08; CR 08-055: am. (1) Register February 2009 No. 638, eff. 3-1-09; correction in (1) (a) 1., 2., 3. made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 16-094: r. and recr., Register April 2018 No. 748 eff. 5-1-18; CR 16-094: renum. (3) (a) to (3) and am., r. (3) (b) 1., 2., renum. (3) (b) 3. to 362.1210 (1m) (a) 4., Register April 2018 No. 748 eff. 5-1-18.
SPS 362.2901 SPS 362.2901Plumbing code. This is a department informational note to be used under IBC section 2901.1: Note: As defined in s. SPS 361.04 (12) and (13), “IPC and International Plumbing Code" and “IPSC and International Private Sewage Code" mean chs. SPS 381 to 387.
SPS 362.2901 History History: CR 01-139: cr. Register June 2002 No. 558, eff. 7-1-02.
SPS 362.2902 SPS 362.2902Plumbing fixtures.
SPS 362.2902(1)(1)Minimum number of fixtures.
SPS 362.2902(1)(a) (a) Exceptions. These are department exceptions to the requirements in IBC section 2902.1:
SPS 362.2902(1)(a)1. 1. Where more than one water closet is required for males, urinals may be substituted for up to 50 percent of the required number of water closets, except that urinals may be substituted for up to 67 percent of the required number of water closets in Group A and E occupancies.
SPS 362.2902(1)(a)2. 2. Where drinking fountains are required, other reasonable alternatives are acceptable, as approved by the department.
SPS 362.2902(1)(a)3. 3. For child day care facilities, bathtubs or showers are not required where other personal hygiene washing arrangements are provided that satisfy the licensing requirements of the Wisconsin department of health services.
SPS 362.2902(1)(a)4. 4. For day nurseries and child day care facilities, children under the age of 30 months need not be considered as a part of the occupant load used to determine the minimum number of water closets.
SPS 362.2902(1)(a)5. 5. Service sinks may be omitted for any occupancy where privies have been substituted for water closets under s. SPS 362.2900 (1) (a) 2.
SPS 362.2902(1)(b) (b) Additional fixtures. These are department informational notes to be used under IBC sections 2902.1 and 2902.2: Note: Additional plumbing fixtures may be required for employees by the U.S. department of labor, occupational safety and health act (OSHA) regulations.
Note: Additional plumbing fixtures may be required by the department of health services for restaurants, mobile home parks, camping grounds, camping resorts, recreational camps and educational camps.
Note: Chapter SPS 390 also has requirements for minimum numbers of sanitary fixtures for a public swimming pool, as based on the pool area. For some buildings, the minimum number of sanitary fixtures determined in that manner may be larger than the minimum number determined in accordance with this section. Compliance with this section does not relieve an owner from complying with ch. SPS 390.
Note: Chapter SPS 391 has requirements for equal speed of access to toilets for each gender, at facilities where the public congregates that do not fall under the scope of this chapter.
SPS 362.2902(1)(c) (c) Substitutions in IBC Table 2902.1.
SPS 362.2902(1)(c)1. 1. Substitute the following wording for the water closets heading in IBC Table 2902.1: Water closetse (see s. SPS 362.2902 (1) (a) 1. for urinals).
SPS 362.2902(1)(c)2. 2. Substitute the following wording for the drinking fountains heading in IBC Table 2902.1: Drinking fountains (see s. SPS 362.2902 (1) (a) 2.).
SPS 362.2902(1)(c)3. 3. In IBC Table 2902.1, substitute the following wording for the required minimum number of water closets for females in type A-4 and A-5 occupancies: 1 per 37 for the first 1,500 and 1 per 60 for the remainder exceeding 1,500.
SPS 362.2902(1)(c)4. 4. Substitute the following wording for the required number of bathtubs or showers in storage occupancies in IBC Table 2902.1: See the International Plumbing Code.
SPS 362.2902(1)(c)5. 5. Substitute the following wording for the required number of bathtubs or showers in factory and industrial occupancies in IBC Table 2902.1: See the International Plumbing Code.
SPS 362.2902(1)(d) (d) Addition to IBC Table 2902.1. This is an additional department footnote for IBC Table 2902.1: Footnote e. Wherever more than 500 people congregate and more than the required minimum number of water closets or urinals are provided for males, twice as many of those additional toilet facilities shall be provided for females.
SPS 362.2902(1)(e) (e) Alternative to IBC Table 2902.1. This is a department alternative to the minimum fixture requirements of IBC Table 2902.1: The required number of toilet fixtures may be based on the actual occupancy load rather than the load determined by square footage per IBC Table 1004.1.1. The actual occupancy load shall be based on justification found acceptable to the department.
SPS 362.2902(2)(a)(a) Lavatories for toilet rooms. This is a department rule in addition to the requirements in IBC section 2902.1: At least one lavatory shall be provided in each toilet room or in a gender-designated lounge adjacent to the toilet room. If a multiple-use lavatory is provided, 24 lineal inches of wash sink, or 20 inches measured along the edge of a circular basin will be considered equivalent to one lavatory.
SPS 362.2902(2)(b) (b) This is a department exception to the requirements in IBC section 2902.2: Separate facilities may not be required in all occupancies when the number of fixtures is provided as required under IBC Table 2902.1 in individual user toilet rooms.
SPS 362.2902(4) (4) Public facilities. This is a department exception to the requirements in IBC section 2902.3: Toilet rooms may be omitted in a small retail or mercantile building where all of the following requirements are met:
SPS 362.2902(4)(a) (a) No more than 25 occupants are accommodated.
SPS 362.2902(4)(b) (b) Other restrooms are conveniently located and available to the patrons and employees during all hours of operation.
SPS 362.2902(4)(c) (c) The omission is approved in writing by the local unit of government.
SPS 362.2902(4)(d) (d) A copy of the written approval from the local unit of government is provided to the department or its authorized representative upon request.
SPS 362.2902(5) (5) Location of restaurant toilet rooms. This is a department informational note to be used under IBC section 2902.3:
SPS 362.2902 Note Note: Additional requirements for restaurant toilet rooms may be applied by the Department of Health Services.
SPS 362.2902(5m) (5m)Location of toilet facilities. Substitute the following wording for the exception in IBC section 2902.3.2: The location and maximum travel distance to required employee facilities in factory and industrial occupancies and to required employee and patron or camper facilities serving seasonal recreational and educational camp buildings are permitted to exceed that required by this section, provided that the location and maximum distance of travel are approved.
SPS 362.2902(6) (6) Pay facilities. Substitute the following wording for the requirements in IBC section 2902.3.4 All toilet facilities shall be free of charge.
SPS 362.2902 Note Note: Section 146.085, Stats., prohibits charging a fee for the use of toilet facilities and imposes a fine of $10 to $50 for violations.
SPS 362.2902 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 01-139: am. (2) Register June 2002 No. 558, eff. 7-1-02; CR 02-002: cr. (1) (c) Register April 2003 No. 568, eff. 5-1-03; CR 04-016: r. and recr. (1) (a), am. (1) (c) 1. and 2., renum. (1) (c) 3., 4., and (4) to (7) to be (1) (c) 4., 5., and (6) to (9), cr. (1) (c) 3., (d), (4) and (5) Register December 2004 No. 588, eff. 1-1-05; CR 06-120: am. (1) (c) 1. and (d), r. and recr. (1) (c) 3., r. (3), (4) and (8), renum. (5) to (7) and (9) to be (3) to (5) and (6) and am. (4) (intro.), (5) and (6) Register February 2008 No. 626, eff. 3-1-08; CR 08-055: cr. (1) (a) 5. Register February 2009 No. 638, eff. 3-1-09; correction in (1) (a) 3. made under s. 13.92 (4) (b) 6., Stats., Register February 2009 No. 638; correction in (1) (a) 5., (c) 1., 2. made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; corrections in (4) (intro.), (5), (6) made under s. 13.92 (4) (b) 7., Stats., Register September 2014 No. 705; CR 16-094: am. (1) (a) 1., 2., cr. (1) (e), renum. (2) to (2) (a), cr. (2) (b), r. (3), Register April 2018 No. 748 eff. 5-1-18; CR 22-069: cr. (5m) Register July 2023 No. 811, eff. 8-1-23.
SPS 362.2903 SPS 362.2903Drinking facilities. This is a department rule in addition to the requirements in IBC section 2903: Drinking fountains, water coolers and bottled water dispensers may not be located or installed in public restrooms.
SPS 362.2903 History History: CR 10-103: cr. Register August 2011 No. 668, eff. 9-1-11.
SPS 362.3001 SPS 362.3001Elevators.
SPS 362.3001(1)(1)Referenced standards. Substitute the following wording for the requirements in IBC section 3001.2: Except as otherwise provided for in chs. SPS 361 to 366, the design, construction, installation, alteration, repair, and maintenance of conveyances and their components shall comply with ch. SPS 318.
SPS 362.3001(2) (2) Change in use. Substitute the following wording for the requirements in IBC section 3001.4: A change in use of an elevator from freight to passenger, passenger to freight, or from one freight class to another freight class shall comply with ch. SPS 318.
SPS 362.3001 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 04-043: cr. (4) Register December 2004 No. 588, eff. 1-1-05; CR 06-120: r. (4) Register February 2008 No. 626, eff. 3-1-08; CR 10-103: r. (1), renum. (2), (3) to be (1), (2) and am. Register August 201 No. 668, eff. 9-1-11; correction in (1), (2) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 16-094: am. (1), Register April 2018 No. 748 eff. 5-1-18.
SPS 362.3002 SPS 362.3002Hoistway enclosures.
SPS 362.3002(1)(1)Elevator car to accommodate ambulance stretcher. Substitute the following wording for IBC section 3002.4:
SPS 362.3002(1)(a) (a) Where passenger elevators are provided, at least one elevator shall be provided for fire department emergency access to all floors served by passenger elevators in all of the following situations:
SPS 362.3002(1)(a)1. 1. A building four or more stories above or four or more stories below grade plane.
SPS 362.3002(1)(a)2. 2. Any floor above or below the level affording fire department vehicle access, if the floor accommodates any one of the following occupancies:
SPS 362.3002(1)(a)2.c. c. Outpatient clinic and ambulatory health care facility.
SPS 362.3002(1)(b) (b) The elevator car provided for fire department emergency access shall be of such a size and configuration to accommodate an ambulance stretcher 24 inches by 84 inches with not less than 5-inch radius corners, in the horizontal, open position.
SPS 362.3002(1)(c) (c) Except in hospitals and except where all of a building's elevators are large enough for fire department emergency access, all elevator cars that are provided for fire department emergency access shall be identified by the international symbol for emergency medical services, star of life. The symbol may not be less than 3 inches high and shall be placed on both sides of the elevator hoistway door frame on all floor levels, approximately 60 inches above the floor.
SPS 362.3002(2) (2) Venting. This is a department rule in addition to the requirements in IBC section 3002: A ventilation opening in a hoistway wall, where provided, shall have guards securely anchored to the supporting structure inside the hoistway. The guards shall consist of a wire-mesh screen of at least 0.0915-inch diameter steel wire with openings that will reject a ball one-inch in diameter, or expanded metal screen of equivalent strength and open area.
SPS 362.3002(3) (3) Area of vents. This is a department rule in addition to the requirements in IBC section 3002: Where vent openings automatically open upon detection of smoke in the elevator lobbies or hoistway, upon power failure and upon activation of a manual override control, the manual override control shall comply with all of the following:
SPS 362.3002(3)(a) (a) Be a keyed switch of the open-auto-close type with the three positions labeled, that is operated with an FEO-K1 key or other approved key.
SPS 362.3002(3)(b) (b) Be located adjacent to the elevator hoistway door frame at the level of fire department vehicle access, approximately 48 inches above the floor, or other approved location. This location may be behind a locked panel.
SPS 362.3002(3)(c) (c) Be labeled “hoistway vent control."
SPS 362.3002(4) (4) Plumbing and mechanical systems. Substitute the following wording for the requirements and the exception in IBC section 3002.9:
SPS 362.3002(4)(a) (a) General. Except as specified in par. (b), plumbing and mechanical systems shall not be located in an elevator shaft.
SPS 362.3002(4)(b)1.1. Except as provided in subd. 2., A drain or sump complying with ss. SPS 382.33 and 382.36 shall be provided in an elevator pit. Connection of the drain or sump to a sanitary system is prohibited.
SPS 362.3002(4)(b)2. 2. An elevator pit is exempt from the sump or drain requirement under subd. 1. for any of the following situations:
SPS 362.3002(4)(b)2.a. a. The floor of an elevator walk-in pit is level with the adjacent floor.
SPS 362.3002(4)(b)2.b. b. The elevator does not extend to the building's lowest floor level and the pit floor is not in contact with the earth.
SPS 362.3002(4)(b)2.c. c. The pit floor is above adjacent grade where the elevator hoistway shaft has one or more exterior walls.
SPS 362.3002(4)(b)2.d. d. The pit will not allow the entrance of ground water and will not be greater than 16 inches in depth.
SPS 362.3002(4)(b)3. 3. The aggregate capacity for drainage from the pit shall be at least one of the following:
SPS 362.3002(4)(b)3.a. a. 30 gpm in a hoistway with one elevator.
SPS 362.3002(4)(b)3.b. b. 50 gpm in a hoistway with two or three elevators.
SPS 362.3002(4)(b)3.c. c. 80 gpm in a hoistway with four elevators.
SPS 362.3002 Note Note: See s. SPS 382.36 for the width or diameter and depth of a sump pump located in an elevator pit.
SPS 362.3002 History History: CR 10-103: cr. Register August 2011 No. 668, eff. 9-1-11; CR 14-020: r. and recr. (3) Register August 2014 No. 704, eff. 9-1-14; CR 16-094: renum 362.3002 to (1), r. and recr. (title), renum. 362.3004 (1) to (3) to (2) to (4) and am., Register April 2018 No. 748 eff. 5-1-18.
SPS 362.3003 SPS 362.3003Standardized fire service elevator keys. Substitute the following for the requirements in IBC section 3003.3. All elevators shall be equipped to operate with a standardized fire service elevator key in accordance with ch. SPS 318.
SPS 362.3003 History History: CR 16-094: cr., Register April 2018 No. 748 eff. 5-1-18.
SPS 362.3005 SPS 362.3005Machine rooms.
SPS 362.3005(1)(1)Scope. This is a department rule in addition to the requirements in IBC section 3005: This section applies to elevator machine rooms, machinery spaces, control rooms, and control spaces not within the hoistway.
SPS 362.3005(2) (2) Access. This is a department informational note to be used under IBC section 3005.1: Note: See ch. SPS 318 for additional requirements, including a prohibition against accessing elevator machine rooms, machinery spaces, control rooms, or control spaces through a toilet room, sleeping room or other private space; and a prohibition against accessing spaces, machinery or equipment not related to a conveyance through machine rooms, machinery spaces, control rooms, control spaces, or hoistways.
SPS 362.3005(3) (3) Temperature and humidity. Substitute the following wording for the requirements in IBC section 3005.2: Elevator machine rooms that contain solid-state equipment for elevator operation shall be provided with an independent means to control the temperature and humidity in the machine room.
SPS 362.3005 Note Note: See IBC section 3003.1.4 and ASME A17.1 section 2.7.9.2 for additional requirements that may apply.
SPS 362.3005(4) (4) Pressurization. This is a department exception to the requirements in IBC section 3005.3: An elevator machine room which serves a pressurized elevator hoistway and which is not directly connected to the pressurized elevator shaft is not required to be pressurized.
SPS 362.3005(4m) (4m) Shunt trip. The following is an exception to IBC section 3005.5. A sprinkler of a sidewall type installed 24 inches or less above the elevator pit floor may not require a heat detector or other means to disconnect the main line power supply.
SPS 362.3005(5) (5) Plumbing systems. Substitute the following wording for the requirements in IBC section 3005.6: Plumbing systems not used in connection with the operation of the elevator may not be located in elevator equipment rooms.
SPS 362.3005 History History: CR 00-179: cr. Register December 2001 No. 552, eff. 7-1-02; CR 01-111: renum. (1) and (2) to be (2) and (3) and cr. (1) Register June 2002 No. 558, eff. 7-1-02; CR 04-016: renum. (3) to be (4), cr. (3) Register December 2004 No. 588, eff. 1-1-05; CR 14-020: renum. (1), (2), (4) to (2), (4), (5), cr. (1), (r) (3), cr. (3) Register August 2014 No. 704, eff. 9-1-14; (1) (title), (3) (title) added under s. 13.92 (4) (b) 2., Stats., Register August 2014 No. 704; CR 16-094: renum. 362.3006 to 362.3005 and am., cr. (4m), Register April 2018 No. 748 eff. 5-1-18; correction in (4) and (5) made under s. 13.92 (4) (b) 7., Stats., Register April 2018 No. 748.
SPS 362.3100 SPS 362.3100Special construction. These are department rules in addition to the requirements in IBC chapter 31: Mausoleum structures shall be designed, constructed, and maintained in accordance with chs. SPS 361 to 366. Mausoleums shall be classified as a Group S-1 storage occupancy and shall be constructed of reinforced concrete or other materials of similar durability.