Subchapter II — General Requirements
PSC 114.004 General requirements.
PSC 114.005 Application of rules.
PSC 114.006 Adoption of standard by reference.
Subchapter III — Omissions, Changes or Additions to NESC-2017
PSC 114.007 Omissions, changes, additions to NESC-2017.
PSC 114.02 Definitions of special terms.
PSC 114.092 Point of connection of grounding conductor.
PSC 114.094 Grounding electrodes.
PSC 114.096 Ground resistance requirements.
PSC 114.097 Separation of grounding conductors.
PSC 114.099 Additional requirements for grounding and bonding of communication apparatus.
PSC 114.102 Application of rules.
PSC 114.103 Referenced sections.
PSC 114.114 Fire-extinguishing equipment.
PSC 114.202 Application of rules.
PSC 114.210 Referenced sections.
PSC 114.215 Grounding of circuits, supporting structures, and equipment.
PSC 114.219 Marking of poles and structures carrying high voltage supply lines.
PSC 114.231 Clearance of supporting structures from other objects.
PSC 114.232 Vertical clearances of wires, conductors, cables, and equipment above ground, roadway, rail, or water surfaces.
PSC 114.234 Clearance of wires, conductors, cables, and equipment from buildings, bridges, rail cars, swimming pools, and other installations.
PSC 114.235 Clearance for wires, conductors, or cables carried on the same supporting structure.
PSC 114.242 Grades of construction for conductors.
PSC 114.250 General loading requirements and maps.
PSC 114.253 Load factors for structures, cross arms, support hardware, guys, foundations, and anchors.
PSC 114.302 Application of rules.
PSC 114.310 Referenced sections.
PSC 114.317 Outdoor location of oil-insulated padmounted transformers near buildings.
PSC 114.352 Installation.
PSC 114.353 Deliberate separations—Equal to or greater than 300 mm (12 in) from underground structures or other cables.
PSC 114.354 Random separation — separation less than 300 mm (12 in) from underground structures or other cables.
PSC 114.402 Referenced sections.
PSC 114.410 General requirements.
Ch. PSC 114 Note
Note 2: Chapter PSC 114 as it existed on April 30, 1991 was repealed and a new chapter PSC 114 was created effective May 1, 1991; Chapter PSC 114 as it existed on December 31, 1993, was repealed and a new chapter PSC 114 was created effective January 1, 1994. Chapter PSC 114 as it existed on September 30, 1997 was repealed and a new chapter PSC 114 was created effective October 1, 1997. Corrections made under s. 13.93 (2m) (b) 1., 6. and 7., Stats.,
Register, September, 1997, No. 501. Chapter PSC 114 as it existed on June 30, 2003 was repealed and a new chapter PSC 114 was created effective July 1, 2003. Chapter PSC 114 as it existed on January 31, 2008, was repealed and a new chapter PSC 114 was created
Register January 2008 No. 625, effective February 1, 2008. Chapter PSC 114 as it existed on June 30, 2014, was repealed and a new chapter PSC 114 was created
Register June 2014 No. 702, effective July 1, 2014.
PSC 114.001
PSC 114.001
Definitions and general information. PSC 114.001(2)
(2) Administrative authorities. The Wisconsin State Electrical Code is issued and administered by the commission and the department of safety and professional services, division of safety and buildings as part of the Wisconsin Administrative Code. The commission has primary responsibility for issuance and administration of Volume 1 as found in this chapter. The department of safety and professional services, division of safety and buildings has similar responsibility for issuance and administration of Volume 2 which is found in ch.
SPS 316.
PSC 114.001(3)
(3) Availability of state electrical code. The commission has adopted the 2017 edition of the National Electrical Safety Code (NESC-2017) with certain deletions, changes and additions which are found in Volume 1, Wisconsin State Electrical Code. Copies of the NESC may be purchased from the Institute of Electrical and Electronics Engineers, Inc., IEEE Service Center, 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855-1331 (telephone 1-800-678-IEEE) or the American National Standards Institute, 1430 Broadway, New York, NY 10018 (telephone 212/642-4900). Copies of the NESC may be ordered online at
http://standards.ieee.org/nesc. Copies of Volume 1, Wisconsin State Electrical Code, may be ordered from the Wisconsin Department of Administration, Document Sales, 202 S. Thornton Avenue, Madison, WI 53702 (telephone 608/266-3358). Unofficial copies of the rules can be obtained online at
http://docs.legis.wi.gov/code/admin_code/psc/114/.
PSC 114.001 Note
Note 2: The department of safety and professional services, division of safety and buildings, has similarly adopted the National Electrical Code (NEC) with certain deletions, changes and additions which are found in Volume 2, Wisconsin State Electrical Code. Copies of Volume 2, Wisconsin State Electrical Code, may be ordered from the Wisconsin Department of Administration, Document Sales, 202 S. Thornton Avenue, Madison, WI 53702. See ch.
SPS 316 for current availability information for the NEC.
PSC 114.001 History
History: CR 07-021: cr.
Register January 2008 No. 625, eff. 2-1-08; correction in (1) made (4) (b) 6., 7., Stats.,
Register January 2012 No. 673; correction in (2) made (4) (b) 6., Stats., Register.
CR 13-039: r. and recr.
Register June 2014 No. 702, eff. 7-1-14;
CR 18-007: am. (3) Register February 2020 No. 770, eff. 3-1-20.
PSC 114.002(1)(1)
Purpose. The purpose of this chapter is the practical safeguarding of persons during the installation, operation or maintenance of electric supply and communication lines and their associated equipment. This chapter contains basic provisions considered necessary for the safety of employees and the public. This chapter is not intended as a design specification or an instruction manual.
PSC 114.002(2)(a)
(a) This chapter applies to supply and communications lines, equipment, and associated work practices employed by an electric supply, communication, railway, or similar utility in the exercise of its function as a utility. In addition, this chapter prohibits the location of buildings, structures, and equipment and prohibits materials storage and change of grade, by any person in violation of the clearance requirements of this chapter. This chapter has also been adopted by the department of safety and professional services as part of Volume 2, Wisconsin State Electrical Code, for application to installations over 600 volts of parties other than utilities.
PSC 114.002(2)(b)
(b) This chapter applies to utility facilities and functions up to the service point.
PSC 114.002(2)(c)
(c) This chapter applies to street and area lights, supplied by underground or overhead conductors, under the exclusive control of utilities, including their authorized contractors, and municipal electrical departments.
PSC 114.002(2)(d)
(d) This chapter does not apply to installations in mines, ships, railway rolling equipment, aircraft, or automotive equipment, or utilization wiring except as covered in Parts 1 and 3, NESC-2017.
PSC 114.003
PSC 114.003
Authority and statutory references. PSC 114.003(1)(1)
Statutory authority. Volume 1, Wisconsin State Electrical Code, constitutes a general order of the commission authorized by ss.
196.74 and
227.11, Stats.
PSC 114.003(2)(a)
(a) A utility must obtain proof of compliance with Volumes 1 and 2 of the Wisconsin State Electrical Code before energizing service. Proof of such compliance shall consist of a certificate furnished by a municipal or other recognized inspection department or officer, or if there is no such inspection department or officer it shall consist of a written statement furnished by the contractor or other person doing the wiring, indicating that there has been such compliance.
PSC 114.003(2)(b)
(b) A utility shall comply with Volume 1, Wisconsin State Electrical Code when providing electric service.
PSC 114.003 Note
Note 2: The authority for the enforcement of Volume 1, Wisconsin State Electrical Code, is vested in the commission with respect to the installation and operation of circuits or equipment by public utilities and railroads in the exercise of their functions as utilities and railroads.
PSC 114.003(3)(a)
(a) Nothing in this chapter shall be construed to deprive a municipality of jurisdiction over utilities, places of employment or public buildings, except that no local requirements shall be less stringent than the requirements in this chapter.
PSC 114.003 Note
Note 2: See s.
196.58, Stats.
PSC 114.003(3)(b)
(b) A utility may seek commission approval of requirements covering an area related to the subject matter of this chapter that is not specifically addressed by this chapter or the NESC, but such requirements must be acceptable and not less stringent than the requirements of this chapter.
PSC 114.003 Note
Note 2: See s.
196.19, Stats. Also, there are state statutes that refer directly to certain electrical construction. Some of these are: ss.
66.0831,
86.16,
134.41,
182.017,
182.0175,
182.018,
196.171,
196.58,
196.67,
196.72, and
941.40, Stats.
PSC 114.003(4)
(4) Complaints. If a complaint is filed with the commission by any interested party to the effect that public safety requires changes in construction or methods of operation, the commission shall investigate and make recommendations.
PSC 114.003 Note
Note 2: See s.
196.74, Stats., for procedure if changes in utility facilities are necessary.
PSC 114.003(5)
(5) Enforcement. The requirements in the code are enforceable in the same manner as other orders of the commission.
PSC 114.003 History
History: CR 07-021: cr.
Register January 2008 No. 625, eff. 2-1-08;
CR 13-039: r. and recr.
Register June 2014 No. 702, eff. 7-1-14.
PSC 114.004(1)(1)
Character of construction, maintenance and operation. All electrical power and communication equipment and lines shall be of such construction, and so installed, operated, and maintained as to minimize the loss of life and fire hazard.
PSC 114.004(2)(a)(a) All construction and equipment shall be cleaned when necessary and inspected at such intervals as experience has shown to be necessary. Any equipment or construction known to be defective so as to endanger life or property shall be promptly repaired, permanently disconnected, or isolated until repairs can be made. Construction, repairs, additions and changes to electrical equipment and conductors shall be made by qualified persons only.
PSC 114.004(2)(b)
(b) Facilities installed or used in the generation, transmission, distribution, and utilization of electricity shall be designed for such installation or use.
PSC 114.004 History
History: CR 07-021: cr.
Register January 2008 No. 625, eff. 2-1-08;
CR 13-039: r. and recr.
Register June 2014 No. 702, eff. 7-1-14.
PSC 114.005(1)(a)
(a) This chapter shall apply in full to all new installations, reconstructions, alterations and extensions, except as modified or waived by the commission under par.
(b).
PSC 114.005(1)(b)
(b)
Waiving rules. The commission may modify or waive these rules in particular cases when rules are shown for any reason to be impractical or if equivalent safety is secured in other ways.
PSC 114.005(2)(a)
(a) Where an existing installation meets, or is altered to meet these rules, such installation is considered to be in compliance with this edition and is not required to comply with any previous edition.
PSC 114.005(2)(b)
(b) Existing installations, including maintenance replacements, which comply with prior editions of the code, need not be modified to comply with these rules except as may be directed for safety reasons by the commission and within the time the commission determines.
PSC 114.005(2)(c)
(c) Where a utility adds, alters, or replaces conductors or equipment on an existing structure, the structure or the facilities on the structure need not be modified or replaced if the resulting installation will be in compliance with the rules in effect at one of the following times: