NR 810.09
NR 810.09 General treatment and disinfection requirements. Department approved treatment shall be provided and operated by each water supplier where necessary in order to ensure that the finished water supplied to consumers meets the primary maximum contaminant levels contained in
ch. NR 809 and the design standards contained in
ch. NR 811, where applicable. In addition, all of the following requirements shall be met:
NR 810.09(1)(a)(a) All existing and new municipal water systems and all other-than-municipal water systems constructed or modified after December 1, 2010, shall be provided with equipment and the necessary appurtenances which can continuously disinfect the water. The department may require the installation of disinfection equipment at existing other-than-municipal water systems where deemed necessary to ensure a safe water supply. Standby disinfection equipment shall be periodically checked and repaired, if necessary, to ensure it will work when it is required.
NR 810.09(1)(b)
(b) All surface water treatment plants and other waterworks where treatment is required to produce a water quality meeting the primary maximum contaminant levels shall be equipped with backup chemical feed equipment for all chemicals required for treatment in the event of failure of the primary equipment.
NR 810.09(1)(c)
(c) Written approval from the department is required prior to the addition of any chemical to a community water system. Non-community water systems shall refer to
s. NR 812.37 for plan approval requirements for chemical feed systems. At public water systems that treat continuously, a 30-day supply of chemicals shall be kept on hand as required by
s. NR 108.06 (3). The 30-day supply shall be based on average day demand and average dose. Chemicals shall meet current A.W.W.A. standards and be approved by the department. Department approval may consist of, but is not limited to, certification of the chemical for use in potable water under NSF/ANSI Standard 60. Those chemical suppliers relabeling or repackaging NSF/ANSI 60 certified chemicals shall also be certified. Laboratories evaluating products for compliance with NSF/ANSI Standard 60 shall be certified by the American National Standards Institute. Colored chemicals shall be approved if coloring agents are not used in toxic concentrations or in amounts which impart taste, odor or color to the water supply. The department may require the analysis of chemicals if necessary to insure use of safe chemicals.
NR 810.09 Note
Note: Copies of these standards are available for inspection at the office of the Department of Natural Resources and the Legislative Reference Bureau.
NR 810.09 Note
Note: The Department of Safety and Professional Services requires plan submittal and approval of all treatment systems installed to service non-community water systems and designed to reduce health-related contaminants. For more information, see s.
SPS 382.20.
NR 810.09(1)(d)
(d) Chemical containers shall be labeled to include the chemical name, purity, concentration, and name and address of the chemical supplier.
NR 810.09(1)(e)
(e) Requests for the substitution of disinfection agents in lieu of chlorine for bacteriological control shall be submitted to the department for review. Substitute disinfection agents may not be used without specific approval by the department.
NR 810.09(1)(f)
(f) Solution tanks shall be maintained in a sanitary condition.
NR 810.09(1)(g)
(g) The department may require an assay of chemicals delivered.
NR 810.09(1)(h)
(h) A material safety data sheet (MSDS) shall be obtained by the water supplier from the chemical supplier for every chemical.
NR 810.09(2)
(2) Disinfection of water from groundwater sources. NR 810.09(2)(a)(a) All municipal water systems shall provide continuous disinfection of the water prior to entry to the distribution system within 36 months of December 1, 2010. For systems that provide disinfection by chlorination, chloramination, or chlorine dioxide, a detectable residual shall be provided throughout the distribution system.
NR 810.09 Note
Note: It is recommended that all community water systems provide a detectable disinfectant residual throughout the distribution system.(b) When disinfection of water drawn from a groundwater source is required in order to meet the MCL for total coliform or E. coli contained in ch.
NR 809 to maintain bacteriologically safe water, the residual maintained in the distribution system and the residual monitoring shall be as required in ss.
NR 809.74 (2) and
NR 811.43 (2). Additional disinfection requirements including disinfectant contact time or compliance with the disinfection requirements of s.
NR 810.31 (1) may be required by the department on a case-by-case basis. The following conditions, as well as other conditions, are considered by the department to be existing or potential water system public health threats:
NR 810.09 Note
1. A public water system history of microbiological contamination in the water source or distribution system by either coliform or noncoliform bacteria.
NR 810.09 Note
2. The presence of color in raw water from a well serving a public water system.
NR 810.09 Note
3. Inadequate construction, including construction which does not meet current requirements of ch.
NR 811 or
812, of a well which serves a public water system.
NR 810.09(3)
(3) Disinfection of water from surface water and groundwater under the direct influence of surface water sources. NR 810.09(3)(a)(a) For free chlorine, the concentration in the water entering the distribution system of any public water system, primary or consecutive, served by treated surface water shall be at least 0.2 mg/1 at the entry point to the distribution system and detectable throughout the distribution system. For total combined chlorine, the concentration in the water entering the distribution system of any public water system served by treated surface water shall be at least 1.0 mg/l at the entry point to the distribution system and detectable throughout the distribution system. Residual monitoring of the water entering the distribution system shall be provided as required in
s. NR 809.74 (2).
NR 810.09(4)(a)(a) After construction, maintenance, repair or modification, waterworks facilities shall be disinfected by procedures outlined in the following A.W.W.A. Standards: A100 (August 1, 2006) for wells, C651 (June 1, 2005) for water mains, C652 (August 1, 2002) for water storage facilities, C653 (June 1, 2003) for water treatment plants or C654 (November 1, 2003) for wells. In addition, waterworks may not be placed in service until bacteriological samples have established that the water is safe for consumption in accordance with
par. (b).
NR 810.09 Note
Note: Copies of these standards are available for inspection at the office of the Department of Natural Resources and the Legislative Reference Bureau, and may be obtained for personal use from the American Water Works Association, 6666 West Quincy Ave., Denver, Colorado, 80235.
NR 810.09(4)(b)
(b) At least one bacteriologically safe sample shall be obtained before waterworks are placed into service. In the case of new or reconstructed wells, a minimum of 2 bacteriological safe samples, taken at least 8 hours apart during the test pumping period, or on 2 separate days, shall be obtained. When new distribution systems or extensions on a number of streets are installed, bacteriological samples shall be taken at representative locations to establish that all of the improvements are free of contamination. When water main breaks are repaired in public water systems that do not maintain a detectable chlorine residual, a bacteriological sample shall be taken in the area of the break within one working day. The main may be returned to service prior to receiving the results provided that the main has been disinfected and flushed. The water supplier shall comply with
s. NR 809.31 when system sampling indicates the presence of coliform organisms. For water storage facilities, 2 or more successive safe samples, taken at 24-hour intervals, shall be obtained which indicate bacteriologically safe water or one safe sample shall be obtained only if a free chlorine residual of at least 0.1 mg/l is remaining when the results of the safe sample are reported.
NR 810.09(5)
(5) Indirect additives. Written approval from the department is required prior to the use of any indirect chemical or material that may affect the quality of the water supply due to immersion or incidental contact in the water system. Department approval shall include certification of the chemical or material for use in potable water under NSF/ANSI Standard 61. Laboratories evaluating products for compliance with NSF/ANSI Standard 61 shall be certified by the American National Standards Institute. Written department approval is not required where existing equipment is being replaced with similar equipment during maintenance or repair provided that the water supplier can document that the equipment used meets the approval requirements of this section.
NR 810.09 Note
Note: Examples of indirect additives include process media, protective materials such as liners, paints and coatings, sealants, gaskets, fittings and lubricants.
NR 810.09 History
History: CR 09-073: cr.
Register November 2010 No. 659, eff. 12-1-10.
NR 810.10
NR 810.10 Distribution system normal pressure. For community water systems, the system pumps, the distribution system and related storage facilities shall be operated to maintain a minimum of 35 pounds per square inch and a maximum of 100 pounds per square inch at ground level above the water main at all locations in the distribution system under normal operating conditions. Normal operating conditions include the peak hour demand on the maximum day. Where the storage or primary pumping facilities cannot provide a minimum static pressure of 35 psi throughout the distribution system at street elevation it shall be necessary to create a boosted pressure zone to serve those portions of the system. The use of pressure boosting systems on individual service lines shall be limited to a maximum of 10 individual systems in any given service area. The individual pressure boosting systems shall be owned and maintained by the public water system owner. The department may require pressure testing to determine whether adequate pressures are available. In situations where static pressures exceed 100 psi, pressure reducing devices may be required on mains in distribution systems having documented system deficiencies or problems due to high pressure such as main breaks and service line breaks.
NR 810.10 Note
Note: Section
SPS 382.40 (7) (d) 2. a. requires a pressure reducing device to be installed to protect individual services when the incoming pressure exceeds 80 psig.
NR 810.10 History
History: CR 09-073: cr.
Register November 2010 No. 659, eff. 12-1-10.
NR 810.11
NR 810.11 Distribution system fire flow pressure. Community water systems with fire protection shall be operated so that under fire flow conditions the residual pressure in the distribution system is not less than 20 pounds per square inch at ground level. Water suppliers shall maintain current flow studies showing the fire flow capability of the system. Fire pumpers may not be connected to fire hydrants if 20 psi cannot be maintained in the system during operation of the pumpers. In addition, the public water system owner shall notify the fire chief in writing of the location of all fire hydrants that cannot be used by fire pumpers and color code or tag the affected hydrants. The department may require pressure and flow testing to determine whether adequate flows and pressures are available.
NR 810.11 History
History: CR 09-073: cr.
Register November 2010 No. 659, eff. 12-1-10.
NR 810.12
NR 810.12 Distribution system loss of pressure. The water supplier for community water systems shall be responsible for taking corrective action when positive distribution system pressure is lost in an area affecting 25% or more of the overall distribution system or in an entire pressure zone. In addition to restoring system pressure, the water supplier shall perform all of the following:
NR 810.12(1)
(1) Notify the appropriate regional office of the department as soon as possible, but no later than one working day after the loss of pressure, as to the extent of the problem, cause and corrective actions taken.
NR 810.12(2)
(2) Start emergency disinfection of the water supply if the water system is not already continuously disinfected. At a minimum, the free chlorine residual shall be 0.2 mg/l at the entry point to the distribution system and detectable throughout the distribution system or the total combined chlorine residual shall be 1.0 mg/l at the entry point and detectable throughout the distribution system. If loss of pressure was limited to one pressure zone, the above disinfection requirements may be restricted to target the affected pressure zone. Higher disinfectant residuals may be required by the department if deemed necessary to ensure a safe water supply. Water mains and storage facilities in the area that lost pressure shall be flushed to remove contaminated water and to quickly establish an adequate disinfectant residual. Emergency disinfection shall be maintained until approval is obtained from the department to cease.
NR 810.12(3)
(3) Collect distribution system water samples for bacteriological analyses from the pressure loss area as soon as adequate pressure is returned to the water system. The number of samples collected shall increase as the extent of problem areas increases, but in no case may less than 2 samples be collected. The department shall be contacted to determine the number of samples and sampling locations. The water supplier shall comply with
s. NR 809.31 when water system sampling indicates the presence of coliform organisms.
NR 810.12(4)
(4) Issue an immediate boil water notice to all affected water consumers unless it is determined by the department that an acute threat to public health does not exist. The boil water notice shall be maintained until approval is obtained from the department to cease. In this subsection “boil water notice" means a special type of public notice that informs consumers that the water is bacteriologically unsafe and should be boiled prior to consumption. A boil water notice shall include all the following information:
NR 810.12(4)(a)
(a) The water has tested bacteriologically unsafe for drinking.
NR 810.12(4)(b)
(b) All water used for washing of eating utensils, drinking, or cooking should be boiled at a rolling boil for at least one minute.
NR 810.12(4)(c)
(c) Ice and any beverages prepared with unboiled water should be discarded.
NR 810.12(4)(d)
(d) Precautions listed in subd. 1 to 3 are in effect until further notice.
NR 810.12(5)
(5) Notify the public in the area affected as prescribed in
s. NR 809.951 unless the department determines that no health hazard has existed.
NR 810.12(6)
(6) Take all corrective actions necessary to prevent additional pressure losses.
NR 810.12 History
History: CR 09-073: cr.
Register November 2010 No. 659, eff. 12-1-10.
NR 810.13
NR 810.13 System maintenance. Each water supplier for all public water systems shall perform routine maintenance to ensure proper operation of the public water system. Record keeping shall be established to ensure proper scheduling.
NR 810.13(1)
(1) Each water supplier for community and nontransient noncommunity water systems shall perform all of the following:
NR 810.13(1)(a)
(a) Well pump maintenance
. Vertical turbine and submersible well pumps shall be removed and inspected on a regular basis and maintenance provided as needed. A frequency of once every ten years is recommended.
NR 810.13(1)(b)
(b) Well seal inspection
. The seal between the pump base and pump head shall be verified to meet the requirements of
ss. NR 811.31 (1) or
811.32 (1) each time a pump is installed or reinstalled.
NR 810.13(1)(c)
(c) Vessels. Iron filters, softeners, and other similar closed treatment vessels shall be opened up, where practicable, and inspected at a minimum of once every 5 years.
NR 810.13(1)(d)
(d) Emergency power exercising. Emergency generators and auxiliary engines shall be exercised a minimum of once per month and quarterly under full load. A log shall be kept that documents when the unit was operated and maintenance that was performed on the unit. Water suppliers for those public water systems who rent, lease or borrow their generators shall have a contract with the owner of the unit, perform full-load exercising at least annually, and keep records showing when exercising was performed. Water suppliers for those public water systems with right angle units requiring mobile tractors shall perform full load exercising at least annually and keep records showing when exercising was performed. Operational and fueling procedures shall be included in the log.
NR 810.13(1)(e)
(e) Hydropneumatic tanks. Pressure tanks shall be flushed regularly to remove sediment. Tanks equipped with hatches shall have interior inspections a minimum of once every 5 years. Maintenance shall include removal of sediment, cleaning of biofilm, restoration of interior and exterior coating systems to prevent corrosion, cleaning and repair of sight glasses, air volume controls and exercising valves.
NR 810.13(2)
(2) Unless an alternate schedule is approved by the department, each water supplier for community water systems shall perform all of the following:
NR 810.13(2)(a)
(a) Valve exercising
. All distribution system valves shall be exercised a minimum of every 2 to 5 years. The department recommends 5 to 7 years for hydrant lead auxiliary valves.
NR 810.13(2)(b)
(b) Hydrant exercising
. All hydrants shall be exercised at least once every 2 years.
NR 810.13(2)(c)
(c) Hydrant maintenance
. Hydrants shall be maintained in proper working condition, consistent with the manufacturer's recommendations.
NR 810.13(2)(d)
(d) Flushing dead-end mains. A schedule shall be established for flushing dead-end mains or mains in other areas to remove sediment or water of poor quality.
NR 810.13(2)(e)
(e) Meter testing and calibration. For water utilities serving public water systems, master water meters in wellhouses, high lift pumping stations, booster pumping stations and metering stations shall be tested and calibrated at a minimum frequency of every 2 years or as required by
s. PSC 185.83 (2). Calibration results shall be documented and be within acceptable levels for the particular meter being calibrated.
NR 810.13 History
History: CR 09-073: cr.
Register November 2010 No. 659, eff. 12-1-10.
NR 810.14
NR 810.14 Water storage facility inspections. The interior and exterior of water storage facilities serving public water systems shall be regularly inspected and maintained. Inspections of storage facilities 10,000 gallons or greater shall be by a professional tank inspection firm or by a registered professional engineer. Maintenance shall include removal of sediment and biofilm prior to evaluation of structural, mechanical and coating systems. Repairs shall be provided as necessary to ensure good working condition. Interior and exterior paint coatings for steel elevated water storage tanks or treatment structures shall be inspected by a person trained to evaluate the integrity of the paint system and repainted as necessary to maintain structural integrity. The water supplier may perform the inspection if experienced in paint inspection.
NR 810.14(1)
(1) Frequency. All storage facilities shall be inspected a minimum of every 5 years and as required in
sub. (2) (a) unless otherwise approved by the department. Repairs or welding on the exterior of a tank may make a special interior inspection necessary. Exterior inspections of vent and overflow screens and hatches shall be conducted once per year by the water supplier.
NR 810.14(2)
(2) Methods. Any of the following methods are acceptable for the required 5-year interior tank/ water storage facility inspection:
NR 810.14(2)(a)
(a) Drain down inspections. Drain down inspections include completely draining the tank. Rigging and ladders may be necessary to access all surfaces. The tank shall be cleaned of all sediment prior to inspecting. Unless an alternative schedule is approved by the department, a drain down inspection shall be utilized a minimum of every ten years or every other inspection.
NR 810.14(2)(a)1.
1. Following all drain down inspections and painting, the interior of the tank shall be disinfected in accordance with one of the methods in AWWA Standard C652-02. A minimum of 2 successive safe samples, taken at 24-hour intervals, shall be obtained which indicate bacteriologically safe water; or one safe sample shall be obtained only if a free chlorine residual of at least 0.1 mg/l is remaining when the results of the safe sample are reported.
NR 810.14(2)(a)2.
2. For all concrete ground reservoirs with cracks or signs of leakage, the top shall be soaked with water and the interior shall be checked for leaks.
NR 810.14(2)(b)
(b) Float down or partial drain inspections. Float down inspections involve the use of a disinfected inflatable raft and allow access to all levels of the tank. The water level shall be lowered below the normal low operating level to expose the sidewalls of the tank. If the tank is to remain in service during the inspection or the water will be sent to the distribution system following the inspection, all of the following requirements apply:
NR 810.14(2)(b)1.
1. A minimum 0.5 mg/l chlorine residual shall be maintained in the tank throughout the inspection.
NR 810.14(2)(b)2.
2. All equipment shall be dedicated for potable water use and is disinfected with a 200 ppm chlorine solution.
NR 810.14(2)(b)3.
3. For all concrete ground reservoirs with cracks or signs of leakage, the top shall be soaked with water and the interior shall be checked for leaks.
NR 810.14(2)(b)4.
4. A minimum of 2 bacteriologically safe samples shall be obtained from the tank after the inspection, one following the inspection and one 24 hours later.
NR 810.14(2)(b)5.
5. A minimum pressure of 35 psi shall be maintained throughout the distribution system during the inspection.
NR 810.14(2)(c)
(c) Diver inspections. Diver inspections shall involve the use of a commercial diver tethered to, and in communication with, the outside. Procedures shall be done in accordance with Section 4.4 of AWWA Standard C652-02 and Section 12.0 of the Consensus Standards for Commercial Diving and Underwater Inspection. The department recommends that the tank be removed from service during the inspection. If the tank is to remain in service during the inspection or if the water will be sent to the distribution system following the inspection, all of the following requirements apply:
NR 810.14(2)(c)1.
1. A minimum 0.5 mg/l chlorine residual shall be maintained in the tank throughout the inspection.
NR 810.14(2)(c)2.
2. All equipment shall be dedicated for potable water use and shall be disinfected with a 200 ppm chlorine solution. The inspector shall also be disinfected.
NR 810.14(2)(c)3.
3. The inspection of the tank shall be done after the sediment is removed from the bottom of tank and shall include a visual inspection of any expansion joints.
NR 810.14(2)(c)4.
4. For all concrete ground reservoirs with cracks or signs of leakage, the top shall be soaked with water and the interior shall be checked for leaks.
NR 810.14(2)(c)5.
5. A minimum of 2 bacteriologically safe samples shall be obtained from the tank after the inspection, one following the inspection and one 24 hours later.
NR 810.14(2)(d)
(d) Robotic inspections. Robotic inspections shall involve a rover unit with a fiber optic tether and video camera and shall include cleaning capabilities. If the tank is to remain in service during the inspection or if the water will be sent to the distribution system following the inspection, all of the following requirements apply:
NR 810.14(2)(d)1.
1. A minimum 0.5 mg/l chlorine residual shall be maintained in the tank throughout the inspection.
NR 810.14(2)(d)2.
2. All equipment entering the tank shall be dedicated for potable water use and be disinfected with a 200 ppm chlorine solution.
NR 810.14(2)(d)3.
3. For all concrete ground reservoirs with cracks or signs of leakage, the top shall be soaked with water and the interior shall be checked for leaks.
NR 810.14(2)(d)4.
4. A minimum of 2 bacteriologically safe samples shall be obtained from the tank after the inspection, one immediately following the inspection and one 24 hours later.
NR 810.14(3)
(3) Department notification. The department's regional drinking water staff person shall be given 48 hours prior notice of the date and time of the inspection.
NR 810.14(4)
(4) Inspection report submittal. Upon completion of the water storage facility inspection, a completed department report form shall be submitted to the department's regional drinking water staff person documenting the condition of the storage facility. The water supplier shall submit copies of any additional reports and videos prepared by the inspector.
NR 810.14 Note
Note: The report forms are available from the department's regional or central office drinking water program staff.
NR 810.14(5)
(5) Manhole cover gasket. Following all inspections and maintenance, the integrity of the gasket between the access manhole cover and curbing shall be checked and replaced if necessary to prevent the entrance of dust and insects. If no gasket is present, one meeting
s. NR 811.64 (7) requirements shall be provided to prevent the entrance of dust and insects.
NR 810.14 History
History: CR 09-073: cr.
Register November 2010 No. 659, eff. 12-1-10.
NR 810.15
NR 810.15 Cross connections and interconnections. Unprotected cross-connections are prohibited. Cross-connections shall be protected as required in
s. SPS 382.41. Water system interconnections are prohibited except as provided in
sub. (2). In addition the following requirements shall be met:
NR 810.15(1)
(1) Cross connection control program. In order to protect the public water supply system, the water supplier for every municipal water system shall develop and implement a comprehensive cross connection control program for the elimination of all existing unprotected cross-connections and prevention of all future un-protected cross connections to the last flowing tap or end-use device. The program may include providing public education materials in lieu of inspections of low hazard portions of residential or commercial facilities. Low hazard areas consist of normal kitchen and bathroom fixtures. The water supplier shall keep a current record of the cross connection control program available for annual review by the department. The cross connection control program shall include: