NR 662.214 Note Note: See the required standards specified in s. NR 662.207 (1).
NR 662.214(2)(c) (c) Describe its intended best practices for providing training to ensure safe on-site transfers of unwanted material and hazardous waste by trained professionals. See the required standards specified in s. NR 662.207 (4) (a).
NR 662.214(2)(d) (d) Describe its intended best practices for removing unwanted material from the laboratory, including all of the following:
NR 662.214(2)(d)1. 1. For regularly scheduled removals, develop a regular schedule for identifying and removing unwanted materials from its laboratories.
NR 662.214 Note Note: See the required standards specified in s. NR 662.208 (1) (a) and (b).
NR 662.214(2)(d)2. 2. For removals when maximum volumes are exceeded, include all of the following information:
NR 662.214(2)(d)2.a. a. Describe its intended best practices for removing unwanted materials from the laboratory within 10 calendar days when unwanted materials have exceeded their maximum volumes.
NR 662.214 Note Note: See the required standards specified in s. NR 662.208 (4).
NR 662.214(2)(d)2.b. b. Describe its intended best practices for communicating that unwanted materials have exceeded their maximum volumes.
NR 662.214(2)(e) (e) Describe its intended best practices for making hazardous waste determinations, including specifying the duties of the individuals involved in the process.
NR 662.214 Note Note: See the required standards specified in ss. NR 662.011 (1) to (4) and 662.209 to 662.212.
NR 662.214(2)(f) (f) Describe its intended best practices for laboratory clean-outs, if the eligible academic entity plans to use the incentives for laboratory clean-outs provided in s. NR 662.213, including all of the following:
NR 662.214(2)(f)1. 1. Procedures for conducting laboratory clean-outs.
NR 662.214 Note Note: See the required standards specified in s. NR 662.213 (1) (a) to (c).
NR 662.214(2)(f)2. 2. Procedures for documenting laboratory clean-outs.
NR 662.214 Note Note: See the required standards specified in s. NR 662.213 (1) (d).
NR 662.214(2)(g) (g) Describe its intended best practices for emergency prevention, including all of the following:
NR 662.214(2)(g)1. 1. Procedures for emergency prevention, notification, and response, appropriate to the hazards in the laboratory.
NR 662.214(2)(g)2. 2. A list of chemicals that the eligible academic entity has, or is likely to have, that become more dangerous when they exceed their expiration date or as they degrade.
NR 662.214(2)(g)3. 3. Procedures to safely dispose of chemicals that become more dangerous when they exceed their expiration date or as they degrade.
NR 662.214(2)(g)4. 4. Procedures for the timely characterization of unknown chemicals.
NR 662.214(3) (3) An eligible academic entity shall make its laboratory management plan available to laboratory workers, students, or any others at the eligible academic entity who request it.
NR 662.214(4) (4) An eligible academic entity shall review and revise its laboratory management plan, as needed.
NR 662.214 History History: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20.
NR 662.215 NR 662.215Unwanted material that is not solid or hazardous waste.
NR 662.215(1)(1)If an unwanted material at an eligible academic entity does not meet the definition of solid waste specified in s. NR 661.0002, it is no longer subject to this subchapter or to the RCRA hazardous waste regulations.
NR 662.215(2) (2) If an unwanted material at an eligible academic entity does not meet the definition of hazardous waste specified in s. NR 661.0003, it is no longer subject to this subchapter or to the RCRA hazardous waste regulations, but shall be managed in compliance with any other applicable regulations or conditions.
NR 662.215 History History: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20.
NR 662.216 NR 662.216Non-laboratory hazardous waste generated at an eligible academic entity. An eligible academic entity that generates hazardous waste outside of a laboratory is not eligible to manage that hazardous waste under this subchapter and remains subject to all of the following:
NR 662.216(1) (1) Generator requirements of ss. NR 662.011 and 662.015 for large quantity generators and small quantity generators if the hazardous waste is managed in a satellite accumulation area, and all other applicable generator requirements of ch. NR 662, with respect to that hazardous waste.
NR 662.216(2) (2) The conditional exemption under s. NR 662.014 for very small quantity generators, with respect to that hazardous waste.
NR 662.216 History History: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20.
subch. L of ch. NR 662 Subchapter L — Alternative Standards for Episodic Generation
NR 662.230 NR 662.230Applicability. This subchapter is applicable to very small quantity generators and small quantity generators as defined in s. NR 660.10.
NR 662.230 History History: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20.
NR 662.231 NR 662.231Definitions. In addition to the definitions set forth under s. NR 660.10, the following definitions apply to this subchapter:
NR 662.231(1) (1) “ Episodic event” means an activity or activities, either planned or unplanned, that does not normally occur during generator operations, resulting in an increase in the generation of hazardous wastes that exceeds the calendar month quantity limits for the generator's usual category.
NR 662.231(2) (2) “ Planned episodic event” means an episodic event that the generator planned and prepared for, including regular maintenance, tank cleanouts, short-term projects, and removal of excess chemical inventory.
NR 662.231(3) (3) “ Unplanned episodic event” means an episodic event that the generator did not plan or reasonably did not expect to occur, including production process upsets, product recalls, accidental spills, or acts of nature.
NR 662.231 History History: CR 19-082: cr. Register August 2020 No. 776, eff. 9-1-20.
NR 662.232 NR 662.232Conditions for a generator managing hazardous waste from an episodic event.
NR 662.232(1)(1)Very small quantity generator. A very small quantity generator may maintain its existing generator category for hazardous waste generated during an episodic event provided that the generator complies with all of the following:
NR 662.232(1)(a) (a) The very small quantity generator is limited to one episodic event per calendar year, unless a petition is granted under s. NR 662.233.
NR 662.232(1)(b) (b) The very small quantity generator shall notify the department no later than 30 calendar days prior to initiating a planned episodic event using EPA Form 8700-12. In the event of an unplanned episodic event, the generator shall notify the department within 72 hours of the unplanned event via phone, email, or fax and subsequently submit EPA Form 8700-12. The generator's notification shall include the start date and end date of the episodic event, the reason for the episodic event, types and estimated quantities of hazardous waste expected to be generated as a result of the episodic event, and shall identify a facility contact and emergency coordinator with 24-hour telephone access to discuss the notification submittal or respond to an emergency in compliance with s. NR 662.016 (2) (i) 1.
NR 662.232(1)(c) (c) The very small quantity generator shall have an EPA identification number or obtain an EPA identification number using EPA Form 8700-12.
NR 662.232(1)(d) (d) A very small quantity generator is prohibited from accumulating hazardous waste generated from an episodic event on drip pads and in containment buildings. When accumulating hazardous waste in containers and tanks the following conditions apply:
NR 662.232(1)(d)1. 1. A very small quantity generator accumulating in containers shall mark or label its containers with all of the following:
NR 662.232(1)(d)1.a. a. The words “Episodic Hazardous Waste.
NR 662.232(1)(d)1.b. b. An indication of the hazards of the contents. Acceptable indications of hazardous contents include the following: applicable hazardous waste characteristic or characteristics, such as ignitable, corrosive, reactive, or toxic; hazard communication consistent with the department of transportation requirements on labeling or placarding, incorporated into s. Trans 326.01 (3); a hazard statement or pictogram consistent with the Occupational Safety and Health Administration Hazard Communication Standard, incorporated into s. SPS 332.50; or a chemical hazard label consistent with the National Fire Protection Association 704 label, incorporated into s. SPS 314.001 (1) (a).”
NR 662.232(1)(d)1.c. c. The date the episodic event began, clearly visible for inspection on each container.
NR 662.232(1)(d)2. 2. A very small quantity generator accumulating episodic hazardous waste in tanks shall do all of the following:
NR 662.232(1)(d)2.a. a. Mark or label the tanks with the words “Episodic Hazardous Waste.”
NR 662.232(1)(d)2.b. b. Mark or label the tanks with an indication of the hazards of the contents. Acceptable indications of hazardous contents include the following: applicable hazardous waste characteristic or characteristics, such as ignitable, corrosive, reactive, or toxic; hazard communication consistent with the department of transportation requirements on labeling or placarding, incorporated into s. Trans 326.01 (3); a hazard statement or pictogram consistent with the Occupational Safety and Health Administration Hazard Communication Standard, incorporated into s. SPS 332.50; or a chemical hazard label consistent with the National Fire Protection Association 704 label, incorporated into s. SPS 314.001 (1) (a).
NR 662.232(1)(d)2.c. c. Use inventory logs, monitoring equipment or other records to identify the date upon which each episodic event begins.
NR 662.232(1)(d)2.d. d. Keep inventory logs or records with the information specified in subd. c. on-site and available for inspection for at least 3 years from the end date of the episodic event.
NR 662.232(1)(d)3. 3. Hazardous waste shall be managed in a manner that minimizes the possibility of a fire, explosion, or release of hazardous waste or hazardous waste constituents to the air, soil, or water, including all of the following conditions:
NR 662.232(1)(d)3.a. a. Containers shall be in good condition and compatible with the hazardous waste being accumulated therein. Containers shall be kept closed except to add or remove waste.
NR 662.232(1)(d)3.b. b. Tanks shall be in good condition and compatible with the hazardous waste accumulated therein. Tanks shall have procedures in place to prevent overflow. Tanks shall be inspected at least once each operating day to ensure all applicable discharge control equipment, such as waste feed cutoff systems, bypass systems, and drainage systems are in good working order and to ensure the tank is operated according to its design by reviewing the data gathered from monitoring equipment such as pressure and temperature gauges from the inspection.
NR 662.232 Note Note: Examples of preventing a tank overflow include high level alarms, an automatic waste feed cutoff system, or a bypass system to a standby tank when hazardous waste is continuously fed into the tank.
NR 662.232(1)(e) (e) The very small quantity generator shall comply with the hazardous waste manifest provisions of subch. B when it sends its episodic event hazardous waste off-site to a designated facility, as defined in s. NR 660.10 (21).
NR 662.232(1)(f) (f) The very small quantity generator shall manifest and send its hazardous waste generated from the episodic event to a designated facility, as defined in s. NR 660.10 (21), within 60 days of the start of the event.
NR 662.232(1)(g) (g) A very small quantity generator shall maintain all of the following records for 3 years from the end date of the episodic event:
NR 662.232(1)(g)1. 1. Beginning and end dates of the episodic event.
NR 662.232(1)(g)2. 2. A description of the episodic event.
NR 662.232(1)(g)3. 3. A description of the types and quantities of hazardous wastes generated during the event.
NR 662.232(1)(g)4. 4. A description of how the hazardous waste was managed as well as the name of the RCRA-designated facility that received the hazardous waste.
NR 662.232(1)(g)5. 5. The name of the hazardous waste transporter.
NR 662.232(1)(g)6. 6. An approval letter from the department if the generator petitioned to conduct one additional episodic event per calendar year.
NR 662.232(2) (2)Small quantity generators. A small quantity generator may maintain its existing generator category during an episodic event provided that the generator complies with all of the following conditions:
NR 662.232(2)(a) (a) The small quantity generator is limited to one episodic event per calendar year unless a petition is granted under s. NR 662.233.
NR 662.232(2)(b) (b) The small quantity generator shall notify the department no later than 30 calendar days prior to initiating a planned episodic event using EPA Form 8700-12. In the event of an unplanned episodic event, the small quantity generator shall notify the department within 72 hours of the unplanned event via phone, email, or fax, and subsequently submit EPA Form 8700-12. The generator's notification shall include the start date and end date of the episodic event and the reason for the episodic event, types and estimated quantities of hazardous wastes expected to be generated as a result of the episodic event, and identify a facility contact and emergency coordinator with 24-hour telephone access to discuss the notification submittal or respond to emergency.
NR 662.232(2)(c) (c) The small quantity generator shall have an EPA identification number or obtain an EPA identification number using EPA Form 8700-12.
NR 662.232(2)(d) (d) A small quantity generator is prohibited from accumulating hazardous wastes generated from an episodic event waste on drip pads and in containment buildings. When accumulating hazardous waste generated from an episodic event in containers and tanks, all of the following conditions apply:
NR 662.232(2)(d)1. 1. A small quantity generator accumulating episodic hazardous waste in containers shall meet the standards specified in s. NR 662.016 (2) (b) and shall mark or label its containers with all of the following:
NR 662.232(2)(d)1.a. a. The words “Episodic Hazardous Waste.”
NR 662.232(2)(d)1.b. b. An indication of the hazards of the contents. Acceptable indications of hazardous contents include the following: applicable hazardous waste characteristic or characteristics, such as ignitable, corrosive, reactive, or toxic; hazard communication consistent with the department of transportation requirements on labeling or placarding, incorporated into s. Trans 326.01 (3); a hazard statement or pictogram consistent with the Occupational Safety and Health Administration Hazard Communication Standard, incorporated into s. SPS 332.50; or a chemical hazard label consistent with the National Fire Protection Association 704 label, incorporated into s. SPS 314.001 (1) (a).
NR 662.232(2)(d)1.c. c. The date upon which the episodic event began, clearly visible for inspection on each container.
NR 662.232(2)(d)2. 2. A small quantity generator accumulating episodic hazardous waste in tanks shall meet the standards specified in s. NR 662.016 (2) (c) and shall do all of the following:
NR 662.232(2)(d)2.a. a. Mark or label the tanks with the words “Episodic Hazardous Waste.”
NR 662.232(2)(d)2.b. b. Mark or label the tanks with an indication of the hazards of the contents. Acceptable indications of hazardous contents include the following: applicable hazardous waste characteristic or characteristics such as, ignitable, corrosive, reactive, or toxic; hazard communication consistent with the department of transportation requirements on labeling or placarding, incorporated into s. Trans 326.01 (3); a hazard statement or pictogram consistent with the Occupational Safety and Health Administration Hazard Communication Standard, incorporated into s. SPS 332.50; or a chemical hazard label consistent with the National Fire Protection Association, incorporated into s. SPS 314.001 (1) (a).
NR 662.232(2)(d)2.c. c. Use inventory logs, monitoring equipment or other records to identify the date upon which each period of accumulation begins and ends.
NR 662.232(2)(d)2.d. d. Keep inventory logs or records with the information in subd. 2. c. on-site and available for inspection.
NR 662.232(2)(e) (e) The small quantity generator shall treat hazardous waste generated from an episodic event on-site or manifest and ship such hazardous waste off-site to a designated facility, as defined in s. NR 660.10 (21), within 60 calendar days from the start of the episodic event.
NR 662.232(2)(f) (f) The small quantity generator shall maintain all of the following records for 3 years from the end date of the episodic event:
NR 662.232(2)(f)1. 1. Beginning and end dates of the episodic event.
NR 662.232(2)(f)2. 2. A description of the episodic event.
NR 662.232(2)(f)3. 3. A description of the types and quantities of hazardous wastes generated during the event.
NR 662.232(2)(f)4. 4. A description of how the hazardous waste was managed as well as the name of the designated facility, as defined in s. NR 660.10 (21), that received the hazardous waste.
NR 662.232(2)(f)5. 5. Name of the hazardous waste transporter.