NR 440.285(5)(b) (b) Any notice under par. (a) will be published only after notice and an opportunity for a public hearing.
NR 440.285(5)(c) (c) Any person seeking permission under this section shall submit to the administrator a written application including:
NR 440.285(5)(c)1. 1. An actual emissions test that uses a full-sized or scale-model storage vessel that accurately collects and measures all VOC emissions from a given control device and that accurately simulates wind and accounts for other emission variables such as temperature and barometric pressure.
NR 440.285(5)(c)2. 2. An engineering evaluation that the administrator determines is an accurate method of determining equivalence.
NR 440.285(5)(d) (d) The administrator may condition the permission on requirements that may be necessary to ensure operation and maintenance to achieve the same emission reduction as specified in sub. (3).
NR 440.285(6) (6)Reporting and recordkeeping requirements. The owner or operator of each storage vessel as specified in sub. (3) (a) shall keep records and furnish reports as required by par. (a), (b), or (c) depending upon the control equipment installed to meet the requirements of sub. (3). The owner or operator shall keep copies of all reports and records required by this section, except for the record required by par. (c) 1., for at least 2 years. The record required by par. (c) 1. will be kept for the life of the control equipment.
NR 440.285(6)(a) (a) After installing control equipment in accordance with sub. (3) (a) 1. (fixed roof and internal floating roof), the owner or operator shall meet the following requirements:
NR 440.285(6)(a)1. 1. Furnish the department with a report that describes the control equipment and certifies that the control equipment meets the specifications of subs. (3) (a) 1. and (4) (a) 1. This report shall be an attachment to the notification required by s. NR 440.07 (1) (c).
NR 440.285(6)(a)2. 2. Keep a record of each inspection performed as required by sub. (4) (a) 1. to 4. Each record shall identify the storage vessel on which the inspection was performed and shall contain the date the vessel was inspected and the observed condition of each component of the control equipment (seals, internal floating roof, and fittings).
NR 440.285(6)(a)3. 3. If any of the conditions described in sub. (4) (a) 2. are detected during the annual visual inspection required by sub. (4) (a) 2., a report shall be furnished to the department within 30 days of the inspection. Each report shall identify the storage vessel, the nature of the defects, and the date the storage vessel was emptied or the nature of and date the repair was made.
NR 440.285(6)(a)4. 4. After each inspection required by sub. (4) (a) 3. that finds holes or tears in the seal or seal fabric, defects in the internal floating roof, or other control equipment defects listed in sub. (4) (a) 3. b., a report shall be furnished to the department within 30 days of the inspection. The report shall identify the storage vessel and the reason it did not meet the specifications of sub. (3) (a) 1. or (4) (a) 3. and list each repair made.
NR 440.285(6)(b) (b) After installing control equipment in accordance with sub. (3) (a) 2. (external floating roof), the owner or operator shall meet the following requirements:
NR 440.285(6)(b)1. 1. Furnish the department with a report that describes the control equipment and certifies that the control equipment meets the specifications of subs. (3) (a) 2. and (4) (b) 2. to 4. This report shall be an attachment to the notification required by s. NR 440.07 (1) (c).
NR 440.285(6)(b)2. 2. Within 60 days of performing the seal gap measurements required by sub. (4) (b) 1., furnish the department with a report that contains:
NR 440.285(6)(b)2.a. a. The date of measurement.
NR 440.285(6)(b)2.b. b. The raw data obtained in the measurement.
NR 440.285(6)(b)2.c. c. The calculations described in sub. (4) (b) 2. and 3.
NR 440.285(6)(b)3. 3. Keep a record of each gap measurement performed as required by sub. (4) (b). Each record shall identify the storage vessel in which the measurement was performed and shall contain:
NR 440.285(6)(b)3.a. a. The date of measurement.
NR 440.285(6)(b)3.b. b. The raw data obtained in the measurement.
NR 440.285(6)(b)3.c. c. The calculations described in sub. (4) (b) 2. and 3.
NR 440.285(6)(b)4. 4. After each seal gap measurement that detects gaps exceeding the limitations specified by sub. (4) (b) 4., submit a report to the department within 30 days of the inspection. The report will identify the vessel and contain the information specified in par. (b) 2. and the date the vessel was emptied or the repairs made and date of repair.
NR 440.285(6)(c) (c) After installing control equipment in accordance with sub. (3) (a) 3. or (b) 1. (closed vent system and control device other than a flare), the owner or operator shall keep the following records:
NR 440.285(6)(c)1. 1. A copy of the operating plan.
NR 440.285(6)(c)2. 2. A record of the measured values of the parameters monitored in accordance with sub. (4) (c) 2.
NR 440.285(6)(d) (d) After installing a closed vent system and flare to comply with sub. (3), the owner or operator shall meet the following requirements:
NR 440.285(6)(d)1. 1. A report containing the measurements required by s. NR 440.18 (6) shall be furnished to the department as required by s. NR 440.08. This report shall be submitted within 6 months of the initial startup date.
NR 440.285(6)(d)2. 2. Records shall be kept of all periods of operation during which the flare pilot flame is absent.
NR 440.285(6)(d)3. 3. Semiannual reports of all periods recorded under subd. 2. in which the pilot flame was absent shall be furnished to the department.
NR 440.285(7) (7)Monitoring of operations.
NR 440.285(7)(a)(a) The owner or operator shall keep copies of all records required by this section, except for the record required by par. (b) for at least 2 years. The record required by par. (b) shall be kept for the life of the source.
NR 440.285(7)(b) (b) The owner or operator of each storage vessel as specified in sub. (1) (a) shall keep readily accessible records showing the dimensions of the storage vessel and an analysis showing the capacity of the storage vessel.
NR 440.285(7)(c) (c) Except as provided in pars. (f) and (g), the owner or operator of each storage vessel either with a design capacity greater than or equal to 151 m3 storing a liquid with a maximum true vapor pressure greater than or equal to 3.6 kPa, or with a design capacity greater than or equal to 75 m3 but less than 151 m3 storing a liquid with a maximum true vapor pressure greater than or equal to 15.0 kPa, shall maintain a record of the VOL stored, the period of storage, and the maximum true vapor pressure of that VOL during the respective storage period.
NR 440.285(7)(d) (d) Except as provided in par. (g), the owner or operator of each storage vessel either with a design capacity greater than or equal to 151 m3 storing a liquid with a maximum true vapor pressure that is normally less than 5.2 kPa, or with a design capacity greater than or equal to 75 m3 but less than 151 m3 storing a liquid with a maximum true vapor pressure that is normally less than 27.6 kPa, shall notify the department within 30 days when the maximum true vapor pressure of the liquid exceeds the respective maximum true vapor pressure values for each volume range.
NR 440.285(7)(e) (e) Available data on the storage temperature may be used to determine the maximum true vapor pressure as follows:
NR 440.285(7)(e)1. 1. For vessels operated above or below ambient temperatures, the maximum true vapor pressure is calculated based upon the highest expected calendar-month average of the storage temperature. For vessels operated at ambient temperatures, the maximum true vapor pressure is calculated based upon the maximum local monthly average ambient temperature as reported by the national weather service.
NR 440.285(7)(e)2. 2. For crude oil or refined petroleum products the vapor pressure may be obtained by the following:
NR 440.285(7)(e)2.a. a. Available data on the Reid vapor pressure and the maximum expected storage temperature based on the highest expected calendar-month average temperature of the stored product may be used to determine the maximum true vapor pressure from nomographs contained in API Publication 2517, incorporated by reference in s. NR 440.17, unless the department specifically requests that the liquid be sampled, the actual storage temperature determined, and the Reid vapor pressure determined from the sample or samples.
NR 440.285(7)(e)2.b. b. The true vapor pressure of each type of crude oil with a Reid vapor pressure less than 13.8 kPa or with physical properties that preclude determination by the recommended method is to be determined from available data and recorded if the estimated maximum true vapor pressure is greater than 3.5 kPa.
NR 440.285(7)(e)3. 3. For other liquids, the vapor pressure may be obtained from one of the following:
NR 440.285(7)(e)3.a. a. Standard reference texts.
NR 440.285(7)(e)3.b. b. Use of ASTM Method D2879-97, incorporated by reference in s. NR 440.17 (2) (a) 34.
NR 440.285(7)(e)3.c. c. Measurement by an appropriate method approved by the administrator.
NR 440.285(7)(e)3.d. d. Calculation using an appropriate method approved by the administrator.
NR 440.285(7)(f) (f) The owner or operator of each vessel storing a waste mixture of indeterminate or variable composition shall be subject to the following requirements.
NR 440.285(7)(f)1. 1. Prior to the initial filling of the vessel, the highest maximum true vapor pressure for the range of anticipated liquid compositions to be stored shall be determined using the methods described in par. (e).
NR 440.285(7)(f)2. 2. For vessels in which the vapor pressure of the anticipated liquid composition is above the cutoff for monitoring but below the cutoff for controls as defined in sub. (3) (a), an initial physical test of the vapor pressure is required; and a physical test at least once every 6 months thereafter is required as determined by one of the following methods:
NR 440.285(7)(f)2.a. a. ASTM D2879-97, incorporated by reference in s. NR 440.17 (2) (a).
NR 440.285(7)(f)2.b. b. ASTM D323-94 incorporated by reference in s. NR 440.17 (2) (a) 11.
NR 440.285(7)(f)2.c. c. Measurement by an appropriate method as approved by the administrator.
NR 440.285(7)(g) (g) The owner or operator of each vessel equipped with a closed vent system and control device meeting the specifications of sub. (3) or with emissions reductions equipment as specified in 40 CFR 65.42 (b) (4), (b) (5), (b) (6) or (c) as in effect on December 14, 2000 is exempt from the requirements of pars. (c) and (d).
NR 440.285 History History: Cr. Register, September, 1990, No. 417, eff. 10-1-90; am (1) (c), (2) (f) (intro.) and (4) (a) 4., Register, July, 1993, No. 451, eff. 8-1-93 ; am. (2) (f) 1., (7) (e) 2. a., Register, December, 1995, No. 480, eff. 1-1-96 ; am., Register, November, 1999, No. 527, eff. 12-1-99; CR 06-109: am. (1) (a) and (b), (2) (f), (i), (j) (intro.) and 1. and (k), (7) (b), (e) 3., (f) 2. and (g), r. (1) (c), cr. (1) (d) 8. and (e), (2) (hm) and (j) 3. Register May 2008 No. 629, eff. 6-1-08; corrections in (1) (e) 2. and (4) (c) 1. (intro.) made under s. 13.92 (4) (b) 7., Stats., Register May 2008 No. 629.
NR 440.29 NR 440.29Secondary lead smelters.
NR 440.29(1) (1)Applicability and designations of affected facility.
NR 440.29(1)(a)(a) The provisions of this section are applicable to the following affected facilities in secondary lead smelters: pot furnaces of more than 250 kg (550 lb) charging capacity, blast (cupola) furnaces and reverberatory furnaces.
NR 440.29(1)(b) (b) Any facility under par. (a) that commences construction or modification after June 11, 1973, is subject to the requirements of this section.
NR 440.29(2) (2)Definitions. As used in this section, terms not defined in this subsection have the meanings given in s. NR 440.02.
NR 440.29(2)(a) (a) “Blast furnace" means any furnace used to recover metal from slag.
NR 440.29(2)(b) (b) “Lead" means elemental lead or alloys in which the predominant component is lead.
NR 440.29(2)(c) (c) “Reverberatory furnace" includes the following types of reverberatory furnaces: stationary, rotating, rocking and tilting.
NR 440.29(2)(d) (d) “Secondary lead smelter" means any facility producing lead from a leadbearing scrap material by smelting to the metallic form.
NR 440.29(3) (3)Standard for particulate matter.
NR 440.29(3)(a)(a) On and after the date on which the performance test required to be conducted by s. NR 440.08 is completed, no owner or operator subject to the provisions of this section may discharge or cause the discharge into the atmosphere from a blast (cupola) or reverberatory furnace any gases which:
NR 440.29(3)(a)1. 1. Contain particulate matter in excess of 50 mg/dscm (0.022 gr/dscf).
NR 440.29(3)(a)2. 2. Exhibit 20% opacity or greater.
NR 440.29(3)(b) (b) On and after the date on which the performance test required to be conducted by s. NR 440.08 is completed, no owner or operator subject to the provisions of this section may discharge or cause the discharge into the atmosphere from any pot furnace any gases which exhibit 10% opacity or greater.
NR 440.29(4) (4)Test methods and procedures.
NR 440.29(4)(a)(a) In conducting the performance tests required in s. NR 440.08, the owner or operator shall use as reference methods and procedures the test methods in Appendix A of 40 CFR part 60, incorporated by reference in s. NR 440.17, or other methods and procedures as specified in this subsection, except as provided in s. NR 440.08 (2).
NR 440.29(4)(b) (b) The owner or operator shall determine compliance with the particulate matter standards in sub. (3) as follows:
NR 440.29(4)(b)1. 1. Method 5 shall be used to determine the particulate matter concentration during representative periods of furnace operation, including charging and tapping. The sampling time and sample volume for each run shall be at least 60 minutes and 0.90 dscm (31.8 dscf).
NR 440.29(4)(b)2. 2. Method 9 and the procedures in s. NR 440.11 shall be used to determine opacity.
NR 440.29 History History: Cr. Register, January, 1984, No. 337, eff. 2-1-84; am. (2) (intro.), Register, September, 1990, No. 417, eff. 10-1-90; r. and recr. (4), Register, July, 1993, No. 451, eff. 8-1-93; CR 06-109: renum. (2) (a), (b) and (c) to be (2) (b), (c) and (d), cr. (2) (a) Register May 2008 No. 629, eff. 6-1-08.
NR 440.30 NR 440.30Secondary brass and bronze production plants.
NR 440.30(1)(1)Applicability and designation of affected facility.
NR 440.30(1)(a)(a) The provisions of this section are applicable to the following affected facilities in secondary brass or bronze production plants: reverberatory and electric furnaces of 1,000 kg (2,205 lb) or greater production capacity and blast (cupola) furnaces of 250 kg/hr (550 lb/hr) or greater production capacity. Furnaces from which molten brass or bronze are cast into the shape of finished products, such as foundry furnaces, are not considered to be affected facilities.
NR 440.30(1)(b) (b) Any facility under par. (a) that commences construction or modification after June 11, 1973, is subject to the requirements of this section.
NR 440.30(2) (2)Definitions. As used in this section, terms not defined in this subsection have the meanings given in s. NR 440.02.
NR 440.30(2)(a) (a) “Blast furnace" means any furnace used to recover metal from slag.
NR 440.30(2)(b) (b) “Brass or bronze" means any metal alloy containing copper as its predominant constituent, and lesser amounts of zinc, tin, lead or other metals.
NR 440.30(2)(c) (c) “Electric furnace" means any furnace which uses electricity to produce over 50% of the heat required in the production of refined brass or bronze.
NR 440.30(2)(d) (d) “Reverberatory furnace" includes the following types of reverberatory furnaces: stationary, rotating, rocking and tilting.
NR 440.30(3) (3)Standard for particulate matter.
NR 440.30(3)(a)(a) On and after the date on which the performance test required to be conducted by s. NR 440.08 is completed, no owner or operator subject to the provisions of this section may discharge or cause the discharge into the atmosphere from a reverberatory furnace any gases which:
NR 440.30(3)(a)1. 1. Contain particulate matter in excess of 50 mg/dscm (0.022 gr/dscf).
NR 440.30(3)(a)2. 2. Exhibit 20% opacity or greater.
NR 440.30(3)(b) (b) On and after the date on which the performance test required to be conducted by s. NR. 440.08 is completed, no owner or operator subject to the provisions of this section may discharge or cause the discharge into the atmosphere from any blast (cupola) or electric furnace any gases which exhibit 10% opacity or greater.
NR 440.30(4) (4)Test methods and procedures.
NR 440.30(4)(a)(a) In conducting performance tests required in s. NR 440.08, the owner or operator shall use as reference methods and procedures the test methods in Appendix A of 40 CFR part 60, incorporated by reference in s. NR 440.17, or other methods and procedures as specified in this subsection, except as provided in s. NR 440.08 (2).
NR 440.30(4)(b) (b) The owner or operator shall determine compliance with the particulate matter standards in sub. (3) as follows: