NR 440.216(12)(c)
(c) The procedures and test methods specified in
subds. 1. to
11. shall be used to determine compliance with the emission limits for particulate matter and opacity under
sub. (3) (a) and
(b).
NR 440.216(12)(c)3.
3. Method 5 of
40 CFR part 60, Appendix A, incorporated by reference in
s. NR 440.17 (1), shall be used for determining compliance with the particulate matter emission limit. The minimum sample volume shall be 1.7 cubic meters. The probe and filter holder heating systems in the sample train shall be set to provide a gas temperature no greater than 160
± 14
°C (320
± 25
°F). An oxygen or carbon dioxide measurement shall be obtained simultaneously with each Method 5 run.
NR 440.216(12)(c)4.
4. The owner or operator of an affected facility may request that compliance with the particulate matter emission limit be determined using carbon dioxide measurements corrected to an equivalent of 7% oxygen. The relationship between oxygen and carbon dioxide levels for the affected facility shall be established as specified in
par. (b) 6.
NR 440.216(12)(c)5.
5. As specified under
s. NR 440.08, all performance tests shall consist of 3 test runs. The average of the particulate matter emission concentrations from the 3 test runs shall be used to determine compliance.
NR 440.216(12)(c)7.
7. The owner or operator of an affected facility shall conduct an initial performance test for particulate matter emissions and opacity as required under
s. NR 440.08.
NR 440.216(12)(c)8.
8. The owner or operator of an affected facility shall install, calibrate, maintain and operate a continuous opacity monitoring system for measuring opacity and shall comply with the following methods and procedures:
NR 440.216(12)(c)8.a.
a. The output of the continuous opacity monitoring system shall be recorded on a 6-minute average basis.
NR 440.216(12)(c)8.d.
d. The initial performance evaluation shall be completed no later than 180 days after the date of the initial startup of the municipal waste combustor unit, as specified under
s. NR 440.08.
NR 440.216(12)(c)9.
9. Following the date that the initial performance test for particulate matter is completed or is required to be completed under
s. NR 440.08 for an affected facility, the owner or operator shall conduct a performance test for particulate matter on an annual basis, no more than 12 calendar months following the previous performance test.
NR 440.216(12)(c)11.
11. Following the date that the initial performance test for opacity is completed or is required to be completed under
s. NR 440.08 for an affected facility, the owner or operator shall conduct a performance test for opacity on an annual basis, no more than 12 calendar months following the previous performance test, using the test method specified in
subd. 6.
NR 440.216(12)(d)
(d) The procedures and test methods specified in this paragraph shall be used to determine compliance with the emission limits for cadmium, lead and mercury under
sub. (3) (c) to
(e):
NR 440.216(12)(d)1.
1. The following procedures and test methods shall be used to determine compliance with the emission limits for cadmium and lead under
sub. (3) (c) and
(d):
NR 440.216(12)(d)1.d.
d. An oxygen or carbon dioxide measurement shall be obtained simultaneously with each Method 29 test run for cadmium and lead required under
subd. 1. c.
NR 440.216(12)(d)1.e.
e. The owner or operator of an affected facility may request that compliance with the cadmium or lead emission limit be determined using carbon dioxide measurements corrected to an equivalent of 7% oxygen. The relationship between oxygen and carbon dioxide levels for the affected facility shall be established as specified in
par. (b) 6.
NR 440.216(12)(d)1.f.
f. All performance tests shall consist of a minimum of 3 test runs conducted under representative full load operating conditions. The average of the cadmium or lead emission concentrations from 3 test runs or more shall be used to determine compliance.
NR 440.216(12)(d)1.g.
g. Following the date of the initial performance test or the date on which the initial performance test is required to be completed under
s. NR 440.08, the owner or operator of an affected facility shall conduct a performance test for compliance with the emission limits for cadmium and lead on an annual basis, no more than 12 calendar months following the previous performance test.
NR 440.216(12)(d)2.
2. The following procedures and test methods shall be used to determine compliance with the mercury emission limit under
sub. (3) (e):
NR 440.216(12)(d)2.c.
c. Method 29 of
40 CFR part 60, Appendix A, incorporated by reference in
s. NR 440.17 (1), shall be used to determine the mercury emission concentration. The minimum sample volume when using Method 29 for mercury shall be 1.7 cubic meters.
NR 440.216(12)(d)2.d.
d. An oxygen or carbon dioxide measurement shall be obtained simultaneously with each Method 29 test run for mercury required under
subd. 2. c.
NR 440.216(12)(d)2.e.
e. The percent reduction in the potential mercury emissions (%PHg) shall be computed using the following equation:
where:
%PHg is the percent reduction of the potential mercury emissions achieved
Ei is the potential mercury emission concentration measured at the control device inlet, corrected to 7% oxygen, dry basis
Eo is the controlled mercury emission concentration measured at the mercury control device outlet, corrected to 7% oxygen, dry basis
NR 440.216(12)(d)2.f.
f. All performance tests shall consist of a minimum of 3 test runs conducted under representative full load operating conditions. The average of the mercury emission concentrations or percent reductions from 3 test runs or more shall be used to determine compliance.
NR 440.216(12)(d)2.g.
g. The owner or operator of an affected facility may request that compliance with the mercury emission limit be determined using carbon dioxide measurements corrected to an equivalent of 7% oxygen. The relationship between oxygen and carbon dioxide levels for the affected facility shall be established as specified in
par. (b) 6.
NR 440.216(12)(d)2.h.
h. The owner or operator of an affected facility shall conduct an initial performance test for mercury emissions as required under
s. NR 440.08.
NR 440.216(12)(d)2.i.
i. Following the date that the initial performance test for mercury is completed or is required to be completed under
s. NR 440.08, the owner or operator of an affected facility shall conduct a performance test for mercury emissions on a annual basis, no more than 12 calendar months following the previous performance test.
NR 440.216(12)(d)2.k.
k. The owner or operator of an affected facility where activated carbon injection is used to comply with the mercury emission limit shall follow the procedures specified in
par. (m) for measuring and calculating carbon usage.
NR 440.216(12)(e)
(e) The following procedures and test methods shall be used for determining compliance with the sulfur dioxide emission limit under
sub. (4) (a):
NR 440.216(12)(e)2.
2. Section 5.4 of Method 19 shall be used to determine the daily geometric average percent reduction in the potential sulfur dioxide emission concentration.
NR 440.216(12)(e)3.
3. The owner or operator of an affected facility may request that compliance with the sulfur dioxide emission limit be determined using carbon dioxide measurements corrected to an equivalent of 7% oxygen. The relationship between oxygen and carbon dioxide levels for the affected facility shall be established as specified in
par. (b) 6.
NR 440.216(12)(e)4.
4. The owner or operator of an affected facility shall conduct an initial performance test for sulfur dioxide emissions as required under
s. NR 440.08. Compliance with the sulfur dioxide emission limit, concentration or percent reduction, shall be determined by using the continuous emission monitoring system specified in
subd. 5. to measure sulfur dioxide and calculating a 24-hour daily geometric average emission concentration or a 24-hour daily geometric average percent reduction using Method 19, sections 4.3 and 5.4, as applicable.
NR 440.216(12)(e)5.
5. The owner or operator of an affected facility shall install, calibrate, maintain and operate a continuous emission monitoring system for measuring sulfur dioxide emissions discharged to the atmosphere and record the output of the system.
NR 440.216(12)(e)6.
6. Following the date that the initial performance test for sulfur dioxide is completed or is required to be completed under
s. NR 440.08, compliance with the sulfur dioxide emission limit shall be determined based on the 24-hour daily geometric average of the hourly arithmetic average emission concentrations using continuous emission monitoring system outlet data if compliance is based on an emission concentration, or continuous emission monitoring system inlet and outlet data if compliance is based on a percent reduction.
NR 440.216(12)(e)7.
7. At a minimum, valid continuous monitoring system hourly averages shall be obtained as follows for 75% of the operating hours per day for 90% of the operating days per calendar quarter that the affected facility is combusting municipal solid waste:
NR 440.216(12)(e)7.a.
a. At least 2 data points per hour shall be used to calculate each 1-hour arithmetic average.
NR 440.216(12)(e)7.b.
b. Each sulfur dioxide 1-hour arithmetic average shall be corrected to 7% oxygen on an hourly basis using the 1-hour arithmetic average of the oxygen or carbon dioxide continuous emission monitoring system data.
NR 440.216(12)(e)8.
8. The 1-hour arithmetic averages required under
subd. 6. shall be expressed in parts per million corrected to 7% oxygen, dry basis, and used to calculate the 24-hour daily geometric average emission concentrations and daily geometric average emission percent reductions. The 1-hour arithmetic averages shall be calculated using the data points required under
s. NR 440.13 (5) (b).
NR 440.216(12)(e)9.
9. All valid continuous emission monitoring system data shall be used in calculating average emission concentrations and percent reductions even if the minimum continuous emission monitoring system data requirements of
subd. 7. are not met.
NR 440.216(12)(e)10.
10. The procedures under
s. NR 440.13 shall be followed for installation, evaluation and operation of the continuous emission monitoring system.
NR 440.216(12)(e)11.
11. The initial performance evaluation shall be completed no later than 180 days after the date of initial startup of the municipal waste combustor as specified under
s. NR 440.08.
NR 440.216(12)(e)12.a.
a. During each relative accuracy test run of the continuous emission monitoring system required by Performance Specification 2, sulfur dioxide and oxygen or carbon dioxide data shall be collected concurrently, or within a 30 to 60 minute period, by both the continuous emission monitors and the following test methods:
2) For oxygen or carbon dioxide, Method 3, 3A or 3B of
40 CFR part 60, Appendix A, incorporated by reference in
s. NR 440.17 (1), as applicable, shall be used.
NR 440.216(12)(e)12.b.
b. The span value of the continuous emissions monitoring system at the inlet to the sulfur dioxide control device shall be 125% of the maximum estimated hourly potential sulfur dioxide emissions of the municipal waste combustor unit. The span value of the continuous emission monitoring system at the outlet of the sulfur dioxide control device shall be 50% of the maximum estimated hourly potential sulfur dioxide emissions of the municipal waste combustor unit.
NR 440.216(12)(e)14.
14. When sulfur dioxide emissions data are not obtained because of continuous emission monitoring system breakdowns, repairs, calibration checks and zero and span adjustments, emissions data shall be obtained by using other monitoring systems as approved by the department or Method 19 of
40 CFR part 60, Appendix A, incorporated by reference in
s. NR 440.17 (1), to provide, as necessary, valid emissions data for a minimum of 75% of the hours per day that the affected facility is operated and combusting municipal solid waste for 90% of the days per calendar quarter that the affected facility is operated and combusting municipal solid waste.
NR 440.216(12)(f)
(f) The following procedures and test methods shall be used for determining compliance with the hydrogen chloride emission limit under
sub. (4) (b):
NR 440.216(12)(f)1.
1. Method 26 or 26A of
40 CFR part 60, Appendix A, incorporated by reference in
s. NR 440.17 (1), as applicable, shall be used to determine the hydrogen chloride emission concentration. The minimum sampling time shall be one hour.
NR 440.216(12)(f)2.
2. An oxygen or carbon dioxide measurement shall be obtained simultaneously with each test run for hydrogen chloride required by
subd. 1.
NR 440.216(12)(f)3.
3. The percent reduction in potential hydrogen chloride emissions (%P
HCl) shall be computed using the following equation:
where:
%PHCl is the percent reduction of the potential hydrogen chloride emissions achieved
Ei is the potential hydrogen chloride emission concentration measured at the control device inlet, corrected to 7% oxygen, dry basis
Eo is the controlled hydrogen chloride emission concentration measured at the control device outlet, corrected to 7% oxygen, dry basis
NR 440.216(12)(f)4.
4. The owner or operator of an affected facility may request that compliance with the hydrogen chloride emission limit be determined using carbon dioxide measurements corrected to an equivalent of 7% oxygen. The relationship between oxygen and carbon dioxide levels for the affected facility shall be established as specified in
par. (b) 6.
NR 440.216(12)(f)5.
5. As specified under
s. NR 440.08, all performance tests shall consist of 3 test runs. The average of the hydrogen chloride emission concentrations or percent reductions from the 3 test runs shall be used to determine compliance.
NR 440.216(12)(f)6.
6. The owner or operator of an affected facility shall conduct an initial performance test for hydrogen chloride as required under
s. NR 440.08.
NR 440.216(12)(f)7.
7. Following the date that the initial performance test for hydrogen chloride is completed or is required to be completed under
s. NR 440.08, the owner or operator of an affected facility shall conduct a performance test for hydrogen chloride emissions on an annual basis, no more than 12 calendar months following the previous performance test.
NR 440.216(12)(g)
(g) The following procedures and test methods shall be used to determine compliance with the limits for dioxin/furan emissions under
sub. (5):
NR 440.216(12)(g)3.b.
b. An oxygen or carbon dioxide measurement shall be obtained simultaneously with each Method 23 test run for dioxins/furans.
NR 440.216(12)(g)4.
4. The owner or operator of an affected facility shall conduct an initial performance test for dioxin/furan emissions in accordance with
subd. 3., as required under
s. NR 440.08.
NR 440.216(12)(g)5.
5. Following the date that the initial performance test for dioxins/furans is completed or is required to be completed under
s. NR 440.08, the owner or operator of an affected facility shall conduct performance tests for dioxin/furan emissions in accordance with
subd. 3. and according to one of the following schedules:
NR 440.216(12)(g)5.a.
a. For affected facilities, performance tests shall be conducted on an annual basis, no more than 12 calendar months following the previous performance test.
NR 440.216(12)(g)5.c.
c. Where all performance tests over a 2-year period indicate that dioxin/furan emissions are less than or equal to 7 nanograms per dry standard cubic meter, total mass, for all affected facilities located within a municipal waste combustor plant, the owner or operator of the municipal waste combustor plant may elect to conduct annual performance tests for one affected facility, that is, unit, per year at the municipal waste combustor plant. At a minimum, a performance test for dioxin/furan emissions shall be conducted annually, no more than 12 months following the previous performance test, for one affected facility at the municipal waste combustor plant. Each year a different affected facility at the municipal waste combustor plant shall be tested, and the affected facilities at the plant shall be tested in sequence, for example, unit 1, unit 2, unit 3, as applicable. If each annual performance test continues to indicate a dioxin/furan emission level less than or equal to 7 nanograms per dry standard cubic meter, total mass, the owner or operator may continue conducting a performance test on only one affected facility per year. If any annual performance test indicates a dioxin/furan emission level greater than 7 nanograms per dry standard cubic meter, total mass, performance tests thereafter shall be conducted annually on all affected facilities at the plant until and unless all annual performance tests for all affected facilities at the plant over a 2-year period indicate a dioxin/furan emission level less than or equal to 7 nanograms per dry standard cubic meter, total mass.
NR 440.216(12)(g)6.
6. The owner or operator of an affected facility that selects to follow the performance testing schedule specified in
subd. 5. c. shall follow the procedures specified in
sub. (13) (g) 2. for reporting the selection of this schedule.
NR 440.216(12)(g)7.
7. The owner or operator of an affected facility where activated carbon is used to comply with the dioxin/furan emission limits specified in
sub. (5) or the dioxin/furan emission level specified in
subd. 5. c. shall follow the procedures specified in
par. (m) for measuring and calculating the carbon usage rate.
NR 440.216(12)(g)8.
8. The owner or operator of an affected facility may request that compliance with the dioxin/furan emission limit be determined using carbon dioxide measurements corrected to an equivalent of 7% oxygen. The relationship between oxygen and carbon dioxide levels for the affected facility shall be established as specified in
par. (b) 6.
NR 440.216(12)(g)9.
9. As specified under
s. NR 440.08, all performance tests shall consist of 3 test runs. The average of the dioxin/furan emission concentrations from the 3 test runs shall be used to determine compliance.
NR 440.216(12)(h)
(h) The following procedures and test methods shall be used to determine compliance with the nitrogen oxides emission limit for affected facilities under
sub. (6):