NR 440.20(8)(c)3. 3. The procedures in Method 19 shall be used to determine the percent SO2 reduction (%Rg) of any SO2 control system. Alternatively, a combination of an`as fired' fuel monitor and emission rates measured after the control system, following the procedures in Method 19, may be used if the percent reduction is calculated using the average emission rate from the SO2 control device and the average SO2 input rate from the `as fired' fuel analysis for 30 successive boiler operating days.
NR 440.20(8)(c)4. 4. The appropriate procedures in Method 19 shall be used to determine the emission rate.
NR 440.20(8)(c)5. 5. The continuous monitoring system in sub. (7) (b) and (d) shall be used to determine the concentrations of SO2 and CO2 or O2.
NR 440.20(8)(d) (d) The owner or operator shall determine compliance with the NOx standard in sub. (5) as follows:
NR 440.20(8)(d)1. 1. The appropriate procedures in Method 19 shall be used to determine the emission rate of NOx.
NR 440.20(8)(d)2. 2. The continuous monitoring system in sub. (7) (c) and (d) shall be used to determine the concentrations of NOx and CO2 or O2.
NR 440.20(8)(e) (e) The owner or operator may use the following as alternatives to the reference methods and procedures specified in this subsection:
NR 440.20(8)(e)1. 1. For Method 5 or 5B, Method 17 may be used at facilities with or without wet FGD systems if the stack temperature at the sampling location does not exceed an average temperature of 160°C (320 °F). The procedures of sections 2.1 and 2.3 of Method 5B may be used in Method 17 only if it is used after wet FGD systems. Method 17 may not be used after wet FGD systems if the effluent is saturated or laden with water droplets.
NR 440.20(8)(e)2. 2. The Fc factor (CO2 ) procedures in Method 19 may be used to compute the emission rate of particulate matter under the stipulations of s. NR 440.19 (7) (d) 1. The CO2 shall be determined in the same manner as the O2 concentration.
NR 440.20(8)(f) (f) Electric utility combined cycle gas turbines are performance tested for particulate matter, sulfur dioxide and nitrogen oxides using the procedures of Method 19 of 40 CFR part 60, Appendix A, incorporated by reference in s. NR 440.17 (1). The sulfur dioxide and nitrogen oxides emission rates from the gas turbine used in Method 19 calculations are determined when the gas turbine is performance tested under s. NR 440.50. The potential uncontrolled particulate matter emission rate from a gas turbine is defined as 17 ng/J (0.04 lb/million Btu) heat input.
NR 440.20(9) (9)Reporting requirements.
NR 440.20(9)(a)(a) For sulfur dioxide, nitrogen oxides and particulate matter emissions, the performance test data from the initial performance test and from the performance evaluation of the continuous monitors (including the transmissometer) shall be submitted to the department.
NR 440.20(9)(b) (b) For sulfur dioxide and nitrogen oxides the following information shall be reported to the department for each 24-hour period.
NR 440.20(9)(b)1. 1. Calendar date.
NR 440.20(9)(b)2. 2. The average sulfur dioxide and nitrogen oxide emission rates (ng/J or lb/million Btu) for each 30 successive boiler operating days, ending with the last 30-day period in the quarter; reasons for noncompliance with the emission standards; and description of corrective actions taken.
NR 440.20(9)(b)3. 3. Percent reduction of the potential combustion concentration of sulfur dioxide for each 30 successive boiler operating days, ending with the last 30-day period in the quarter; reasons for noncompliance with the standard; and description of corrective actions taken.
NR 440.20(9)(b)4. 4. Identification of the boiler operating days for which pollutant or diluent data have not been obtained by an approved method for at least 18 hours of operation of the facility; justification for not obtaining sufficient data; and description of corrective actions taken.
NR 440.20(9)(b)5. 5. Identification of the times when emissions data have been excluded from the calculation of average emission rates because of startup, shutdown, malfunction (NOx only), emergency conditions (SO2 only) or other reasons, and justification for excluding data for reasons other than startup, shutdown, malfunction or emergency conditions.
NR 440.20(9)(b)6. 6. Identification of “F" factor used for calculations, method of determination and type of fuel combusted.
NR 440.20(9)(b)7. 7. Identification of times when hourly averages have been obtained based on manual sampling methods.
NR 440.20(9)(b)8. 8. Identification of the times when the pollutant concentration exceeded full span of the continuous monitoring system.
NR 440.20(9)(b)9. 9. Description of any modifications to the continuous monitoring system which could affect the ability of the continuous monitoring system to comply with Performance Specification 2 or 3 of 40 CFR part 60, Appendix B, incorporated by reference in s. NR 440.17.
NR 440.20(9)(c) (c) If the minimum quantity of emission data as required by sub. (7) is not obtained for any 30 successive boiler operating days, the following information obtained under the requirements of sub. (6) (h) shall be reported to the department for that 30-day period:
NR 440.20(9)(c)1. 1. The number of hourly averages available for outlet emissions rates (no) and inlet emission rates (n i), as applicable.
NR 440.20(9)(c)2. 2. The standard deviation of hourly averages for outlet emission rates (So) and inlet emission rates (S i), as applicable.
NR 440.20(9)(c)3. 3. The lower confidence limit for the mean outlet emission rate (Eo*) and the upper confidence limit for the mean inlet emission rate (Ei*), as applicable.
NR 440.20(9)(c)4. 4. The applicable potential combustion concentration.
NR 440.20(9)(c)5. 5. The ratio of the upper confidence limit for the mean outlet emission rate (Eo*) and the allowable emission rate (Estd), as applicable.
NR 440.20(9)(d) (d) If any standards under sub. (4) are exceeded during emergency conditions because of control system malfunction, the owner or operator of the affected facility shall submit a signed statement:
NR 440.20(9)(d)1. 1. Indicating if emergency conditions existed and requirements under sub. (6) (d) were met during each period, and
NR 440.20(9)(d)2. 2. Listing the following information:
NR 440.20(9)(d)2.a. a. Time periods the emergency condition existed;
NR 440.20(9)(d)2.b. b. Electrical output and demand on the owner or operator's electric utility system and the affected facility;
NR 440.20(9)(d)2.c. c. Amount of power purchased from interconnected neighboring utility companies during the emergency period;
NR 440.20(9)(d)2.d. d. Percent reduction in emissions achieved;
NR 440.20(9)(d)2.e. e. Atmospheric emission rate (ng/J) of the pollutant discharged; and
NR 440.20(9)(d)2.f. f. Actions taken to correct control system malfunction.
NR 440.20(9)(e) (e) If fuel pretreatment credit toward the sulfur dioxide emission standard under sub. (4) is claimed, the owner or operator of the affected facility shall submit a signed statement:
NR 440.20(9)(e)1. 1. Indicating what percentage cleaning credit was taken for the calendar quarter, and whether the credit was determined in accordance with the provisions of sub. (8) and Method 19 of 40 CFR part 60, Appendix A, incorporated by reference in s. NR 440.17; and
NR 440.20(9)(e)2. 2. Listing the quantity, heat content, and date each pretreated fuel shipment was received during the previous quarter; the name and location of the fuel pretreatment facility; and the total quantity and total heat content of all fuels received at the affected facility during the previous quarter.
NR 440.20(9)(f) (f) For any periods for which opacity, sulfur dioxide or nitrogen oxides emissions data are not available, the owner or operator of the affected facility shall submit a signed statement indicating if any changes were made in operation of the emission control system during the period of data unavailability. Operations of the control system and affected facility during periods of data unavailability are to be compared with operation of the control system and affected facility before and following the period of data unavailability.
NR 440.20(9)(g) (g) The owner or operator of the affected facility shall submit a signed statement indicating whether:
NR 440.20(9)(g)1. 1. The required continuous monitoring system calibration, span, and drift checks or other periodic audits have or have not been performed as specified.
NR 440.20(9)(g)2. 2. The data used to show compliance was or was not obtained in accordance with approved methods and procedures of this chapter and is representative of plant performance.
NR 440.20(9)(g)3. 3. The minimum data requirements have or have not been met; or, the minimum data requirements have not been met for errors that were unavoidable.
NR 440.20(9)(g)4. 4. Compliance with the standards has or has not been achieved during the reporting period.
NR 440.20(9)(h) (h) For the purposes of the reports required under s. NR 440.07, periods of excess emissions are defined as all 6-minute periods during which the average opacity exceeds the applicable opacity standards under sub. (3) (b). Opacity levels in excess of the applicable opacity standard and the date of such excesses shall be submitted to the department each calendar quarter.
NR 440.20(9)(i) (i) The owner or operator of an affected facility shall submit the written reports required under this subsection and ss. NR 440.01 to 440.15 to the department semiannually for each 6-month period. All semiannual reports shall be postmarked by the 30th day following the end of each 6-month period.
NR 440.20(9)(j) (j) The owner or operator of an affected facility may submit electronic quarterly reports for SO2, NOx and opacity in lieu of submitting the written reports required under pars. (b) and (h). The format of each quarterly electronic report shall be coordinated with the department. The electronic report shall be submitted no later than 30 days after the end of the calendar quarter and shall be accompanied by a certification statement from the owner or operator, indicating whether compliance with the applicable emission standards and minimum data requirements of this section was achieved during the reporting period. Before submitting reports in the electronic format, the owner or operator shall coordinate with the department to obtain agreement to submit reports in this alternative format.
NR 440.20 History History: Cr. Register, January, 1984, No. 337, eff. 2-1-84; am. (7) (h) 1., 3., 4., (L) 1. and (8) (a) 1., Register, September, 1986, No. 369, eff. 10-1-86; am. (2) (intro.), (7) (h) 1. to 3., (i) 1., (8) (a) 1. to 6., r. (8) (a) 7., Register, September, 1990, No. 417, eff. 10-1-90; am. (4) (h) 1. and 2., (5) (a) 1., (c), (6) (d) 3. (intro.) and (h), r. and recr. (7) (f), (h), (i) (intro.) to 2. and (8), cr. (7) (j), Register, July, 1993, No. 451, eff. 8-1-93; am. (2) (n), (y), (5) (a) 1., (7) (h) 2., (8) (b) 2., Register, December, 1995, No. 480, eff. 1-1-96; correction in (4) (b) (intro.) made under s. 13.93 (2m) (b) 7., Stats., Register, November, 1999, No. 527; CR 06-109: am. (1) (b), (2) (b), (n), (q) 1. b. and (y), (4) (d) 2., (f), (5) (a) (intro.), 1. and 2., (b) and (c), (7) (e) and (i) 1. and 3., (8) (title) and (b) 2. b. and (9) (i), cr. (2) (gr) and (Lm), (5) (d), (6) (a) (title), (b) (title), (c) (title), (d) (title), (e) (title), (f) (title), (g) (title) and (h) (title), (i) to (k), (7) (c) 2. and (k) to (n), (8) (f) and (9) (j), renum. (7) (c) to be (7) (c) 1. Register May 2008 No. 629, eff. 6-1-08.
NR 440.205 NR 440.205Industrial - commercial - institutional steam generating units.
NR 440.205(1) (1)Applicability.
NR 440.205(1)(a)(a) The affected facility to which this section applies is each steam generating unit that commences construction, modification, or reconstruction after June 19, 1984, and that has a heat input capacity from fuels combusted in the steam generating unit of more than 29 MW (100 million Btu/hour).
NR 440.205(1)(b) (b) Any affected facility meeting the applicability requirements under par. (a) and commencing construction, modification, or reconstruction after June 19, 1984, but on or before June 19, 1986, is subject to the following standards:
NR 440.205(1)(b)1. 1. Coal-fired affected facilities having a heat input capacity between 29 and 73 MW (100 and 250 million Btu/hour), inclusive, are subject to the particulate matter and nitrogen oxides standards under this section.
NR 440.205(1)(b)2. 2. Coal-fired affected facilities having a heat input capacity greater than 73 MW (250 million Btu/hour) and meeting the applicability requirements under s. NR 440.19 (standards of performance for fossil fuel-fired steam generators) are subject to the particulate matter and nitrogen oxides standards under this section and to the sulfur dioxide standards in s. NR 440.19 (4).
NR 440.205(1)(b)3. 3. Oil-fired affected facilities having a heat input capacity between 29 and 73 MW (100 and 250 million Btu/hour), inclusive, are subject to the nitrogen oxides standards in this section.
NR 440.205(1)(b)4. 4. Oil-fired affected facilities having a heat input capacity greater than 73 MW (250 million Btu/hour) and meeting the applicability requirements in s. NR 440.19 (standards of performance for fossil fuel-fired steam generators) are also subject to the nitrogen oxides standards in this section and the particulate matter and sulfur dioxide standards in s. NR 440.19 (3) and (4).
NR 440.205(1)(c) (c) Affected facilities which also meet the applicability requirements under s. NR 440.26 (standards of performance for petroleum refineries) are subject to the particulate matter and nitrogen oxides standards under this section and the sulfur dioxide standards under s. NR 440.26 (5).
NR 440.205(1)(d) (d) Affected facilities which also meet the applicability requirements in s. NR 440.21 (standards of performance for incinerators) are subject to the nitrogen oxides and particulate matter standards in this section.
NR 440.205(1)(e) (e) Steam generating units meeting the applicability requirements in s. NR 440.20 (standards of performance for electric utility steam generating units) are not subject to this section.
NR 440.205(1)(f) (f) Any change to an existing steam generating unit for the sole purpose of combusting gases containing TRS as defined in s. NR 440.45 (2) is not considered a modification under s. NR 440.14 and the steam generating unit is not subject to this section.
NR 440.205(1)(g) (g) Affected facilities which meet the applicability requirements under s. NR 440.216 (1) are not subject to this section.
NR 440.205(1)(h) (h) Unless and until s. NR 440.50 is revised to extend the applicability of s. NR 440.50 to steam generator units subject to this section, this section will continue to apply to combined cycle gas turbines that are capable of combusting more than 29 MW (100 million Btu/hour) heat input of fossil fuel in the steam generator. Only emissions resulting from combustion of fuels in the steam generating unit are subject to this section. (The gas turbine emissions are subject to s. NR 440.50.)
NR 440.205(2) (2)Definitions. As used in this section, terms not defined in this subsection have the meanings given in s. NR 440.02.
NR 440.205(2)(a) (a) “Annual capacity factor" means the ratio between the actual heat input to a steam generating unit from the fuels listed in sub. (3) (a), (4) (a) or (5) (a), as applicable, during a calendar year and the potential heat input to the steam generating unit had it been operated for 8,760 hours at the maximum steady state design heat input capacity. In the case of steam generating units that are rented or leased, the actual heat input shall be determined based on the combined heat input from all operations of the affected facility in a calendar year.
NR 440.205(2)(b) (b) “Byproducts/waste" means any liquid or gaseous substance produced at chemical manufacturing plants, petroleum refineries or pulp and paper mills (except natural gas, distillate oil, or residual oil) and combusted in a steam generating unit for heat recovery or for disposal. Gaseous substances with carbon dioxide levels greater than 50% or carbon monoxide levels greater than 10% are not byproduct/waste for the purposes of this section.
NR 440.205(2)(c) (c) “Chemical manufacturing plants" means industrial plants which are classified by the department of commerce under SIC code 28 in the Standard Industrial Classification Manual, incorporated by reference in s. NR 440.17.
NR 440.205(2)(d) (d) “Coal" means all solid fuels classified as an anthracite, bituminous, subbituminous, or lignite by the American Society for Testing and Materials in ASTM D388-99 (reapproved 2004), Standard Specification for Classification of Coals by Rank, incorporated by reference in s. NR 440.17 (2) (a) 12., coal refuse, and petroleum coke. Coal-derived synthetic fuels, including but not limited to solvent refined coal, gasified coal, coal-oil mixtures, and coal-water mixtures, are also included in this definition for the purposes of this section.
NR 440.205(2)(e) (e) “Coal refuse" means any byproduct of coal mining or coal cleaning operations with an ash content greater than 50%, by weight, and a heating value less than 13,900 kJ/kg (6,000 Btu/lb) on a dry basis.
NR 440.205(2)(f) (f) “Combined cycle system" means a system where a separate source, such as a gas turbine, internal combustion engine, kiln, etc., provides exhaust gas to a heat recovery steam generating unit.
NR 440.205(2)(g) (g) “Conventional technology" means wet flue gas desulfurization (FGD) technology, dry FGD technology, atmospheric fluidized bed combustion technology, and oil hydrodesulfurization technology.
NR 440.205(2)(h) (h) “Distillate oil" means fuel oils which contain 0.05 weight percent nitrogen or less and comply with the specifications for fuel oils number 1 and 2, as defined by the American Society for Testing and Materials in ASTM D396-98, Standard Specification for Fuel Oils, incorporated by reference in s. NR 440.17 (2) (a) 13.
NR 440.205(2)(i) (i) “Dry flue gas desulfurization technology" means a sulfur dioxide control system that is located downstream of the steam generating unit and removes sulfur oxides from the combustion gases of the steam generating unit by contacting the combustion gases with an alkaline slurry or solution and forming a dry powder material. This definition includes devices where the dry powder material is subsequently converted to another form. Alkaline slurries or solutions used in dry flue gas desulfurization technology include but are not limited to lime and sodium.
NR 440.205(2)(j) (j) “Duct burner" means a device that combusts fuel and that is placed in the exhaust duct from another source, such as a stationary gas turbine, internal combustion engine, kiln, etc., to allow the firing of additional fuel to heat the exhaust gases before the exhaust gases enter a heat recovery steam generating unit.
NR 440.205(2)(k) (k) “Emerging technology" means any sulfur dioxide control system that is not defined as a conventional technology under this subsection, and for which the owner or operator of the facility has applied to the administrator and received approval to operate as an emerging technology under sub. (10) (a) 4.
NR 440.205(2)(m) (m) “Fluidized bed combustion technology" means combustion of fuel in a bed or series of beds (including but not limited to bubbling bed units and circulating bed units) of limestone aggregate (or other sorbent materials) in which these materials are forced upward by the flow of combustion air and the gaseous products of combustion.
NR 440.205(2)(n) (n) “Fuel pretreatment" means a process that removes a portion of the sulfur in a fuel before combustion of the fuel in a steam generating unit.
NR 440.205(2)(o) (o) “Full capacity" means operation of the steam generating unit at 90% or more of the maximum steady-state design heat input capacity.
NR 440.205(2)(p) (p) “Heat input" means heat derived from combustion of fuel in a steam generating unit and does not include the heat input from preheated combustion air, recirculated flue gases, or exhaust gases from other sources, such as gas turbines, internal combustion engines, kilns, etc.
NR 440.205(2)(q) (q) “Heat release rate" means the steam generating unit design heat input capacity (in MW or Btu/hour) divided by the furnace volume (in cubic meters or cubic feet); the furnace volume is that volume bounded by the front furnace wall where the burner is located, the furnace side waterwall, and extending to the level just below or in front of the first row of convection pass tubes.
NR 440.205(2)(r) (r) “Heat transfer medium" means any material that is used to transfer heat from one point to another point.
NR 440.205(2)(s) (s) “High heat release rate" means a heat release rate greater than 730,000 J/sec-m3 (70,000 Btu/hour-ft3).
NR 440.205(2)(t) (t) “Lignite" means a type of coal classified as lignite A or lignite B by the American Society for Testing and Materials in ASTM D388-99 (reapproved 2004), Standard Specification for Classification of Coals by Rank, incorporated by reference in s. NR 440.17 (2) (a) 12.
NR 440.205(2)(u) (u) “Low heat release rate" means a heat release rate of 730,000 J/sec-m3 (70,000 Btu/hour-ft3) or less.
NR 440.205(2)(v) (v) “Mass-feed stoker steam generating unit" means a steam generating unit where solid fuel is introduced directly into a retort or is fed directly onto a grate where it is combusted.
NR 440.205(2)(w) (w) “Maximum heat input capacity" means the ability of a steam generating unit to combust a stated maximum amount of fuel on a steady state basis, as determined by the physical design and characteristics of the steam generating unit.
NR 440.205(2)(x) (x) “Municipal-type solid waste" means refuse, more than 50% of which is waste consisting of a mixture of paper, wood, yard wastes, food wastes, plastics, leather, rubber, and other combustible materials, and noncombustible materials such as glass and rock.
NR 440.205(2)(y) (y) “Natural gas" means: