NR 428.04(2)(g)1.e.
e. 14 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for a combined cycle combustion turbine with a maximum design power output of less than 25 MWe.
NR 428.04(2)(g)2.
2. Distillate fuel oil-fired units. No person may cause, allow or permit nitrogen oxides to be emitted from a distillate fuel oil-fired combustion turbine in amounts greater than those specified in this subdivision.
NR 428.04(2)(g)2.a.
a. 25 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for a simple cycle combustion turbine with a maximum design power output of 85 MWe or greater.
NR 428.04(2)(g)2.b.
b. 25 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for a simple cycle combustion turbine with a maximum design power output of 40 MWe or greater but less than 85 MWe.
NR 428.04(2)(g)2.c.
c. 65 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for a simple cycle combustion turbine with a maximum design power output of less than 40 MWe.
NR 428.04(2)(g)2.d.
d. 8 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for a combined cycle combustion turbine with a maximum design power output of 25 MWe or greater.
NR 428.04(2)(g)2.e.
e. 25 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for a combined cycle combustion turbine with a maximum design power output of less than 25 MWe.
NR 428.04(2)(g)3.
3. Units fired by an integrated gasification process. No person may cause, allow or permit nitrogen oxides to be emitted from a combined cycle combustion turbine that is fired by fuel derived from an integrated gasification process in amounts greater than 15 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis.
NR 428.04(2)(g)4.
4. Units fired by a biologically derived gaseous fuel. No person may cause, allow or permit nitrogen oxides to be emitted from a biologically derived gaseous fuel fired combustion turbine in amounts greater than those specified in this subdivision.
NR 428.04(2)(g)4.a.
a. 35 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for a simple cycle combustion turbine.
NR 428.04(2)(g)4.b.
b. 35 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for a combined cycle combustion turbine.
NR 428.04(2)(h)
(h)
Reciprocating engines. No person may cause, allow or permit nitrogen oxides to be emitted from a reciprocating engine in amounts greater than those specified in this paragraph.
NR 428.04(2)(h)1.
1. 6.9 grams per brake horsepower-hour for a compression ignition unit with a maximum design power output of 1000 hp or greater.
NR 428.04(2)(h)2.
2. 4.0 grams per brake horsepower-hour for a spark ignition unit with a maximum design power output of 1000 hp or greater.
NR 428.04(2)(i)
(i)
Emissions units using secondary fuel. An emissions unit that is capable of firing secondary fuel is not subject to the requirements under this subsection when utilizing only a secondary fuel if any of the following apply:
NR 428.04(2)(i)1.
1. The emissions unit heat input capacity or maximum design power output while utilizing the secondary fuel is less than the applicability thresholds under this subsection.
NR 428.04(2)(i)2.
2. The emissions unit burns the secondary fuel only during any of the following periods:
NR 428.04(2)(i)2.a.
a. Supply interruption or curtailment of primary fuel. The secondary fuel usage under this paragraph may not
exceed 500 hours within a 12 consecutive month time period unless the owner or operator obtains a fuel variance under s.
NR 436.06.
NR 428.04(2)(i)2.b.
b. Periodic testing, maintenance, or operator training of the secondary fuel when the periodic testing, maintenance, or operator training does not exceed a combined total of 48 hours during any calendar year.
NR 428.04(2)(i)3.
3. The secondary fuel constitutes less than 1 percent on an energy equivalent basis of the emissions unit's fuel consumption within the most recent 12 consecutive month time period.
NR 428.04(3)(a)1.1. The owner or operator of each NO
x emissions unit subject to the requirements of sub. (2) shall comply with the monitoring requirements of subch. III.
NR 428.04(3)(a)2.
2. The emissions measurements recorded and reported in accordance with subch. III shall be used to determine compliance by the unit with the applicable NO
x emissions performance standard under sub. (2).
NR 428.04(3)(b)
(b)
Specific requirements. The owner or operator of each NO
x emissions unit subject to the requirements of sub. (2) shall determine the unit's average NO
x emission rate using methods and procedures specified in
40 CFR part 60, Appendix B, incorporated by reference in s.
NR 484.04 (21), or other emissions monitoring methods approved by the department.
NR 428.04(4)(a)
(a) Except as provided in subd. 1., the owner or operator of each NO
x emissions unit subject to the requirements of this section shall keep on site at the source each of the following documents for a period of 5 years from the date the document is created.
NR 428.04(4)(a)1.
1. All emissions monitoring information, in accordance with subch. III; except that, to the extent that subch. III provides for a 3-year period for record retention, the 3-year period shall apply.
NR 428.04(4)(a)2.
2. Copies of all reports, compliance certifications and other submissions and all records made or required under the NO
x emissions performance program.
NR 428.04(4)(b)
(b) The owner or operator of the NO
x emissions source shall submit the compliance reports and certifications required under the NO
x emissions performance program in conjunction with those required under the construction permit requirements of ch.
NR 406 and the operation permit requirements of s.
NR 407.09.
NR 428.04(4)(c)
(c) The owner or operator claiming exemption from the requirements under sub. (2) pursuant to sub. (2) (i) shall keep a record of all of the following:
NR 428.04(4)(c)1.
1. Each occurrence when a secondary fuel was burned in accordance with the provisions under sub. (2) (i).
NR 428.04(4)(c)2.
2. The reason for each occurrence when a secondary fuel was burned in accordance with the provisions under sub. (2) (i).
NR 428.04(4)(c)3.
3. The monthly and yearly total hours for each occurrence when a secondary fuel was burned in accordance with the provisions under sub. (2) (i).
NR 428.04 History
History: Cr.
Register, January, 2001, No. 541, eff. 2-1-01;
CR 02-076: cr. (2) (g) 3.
Register November 2002 No. 563, eff. 12-1-02;
CR 03-049: am. (2) (g) 1., cr. (2) (g) 4.
Register December 2003 No. 576, eff. 1-1-04;
CR 07-016: am. (2) (h) 1. and 2.
Register July 2007 No. 619, eff. 8-1-07;
CR 08-103: am. (1) and (3) (b)
Register August 2009 No. 644, eff. 9-1-09;
CR 23-017: am. (2) (g) 1. d., cr. (2) (i), (4) (c) Register March 2024 No. 819, eff. 4-1-24. NR 428.05
NR 428.05 Requirements and performance standards for existing sources. NR 428.05(1)(1)
Applicability. The requirements
of this section apply to emissions units described in this section that are located in the county of Kenosha, Manitowoc, Milwaukee, Ozaukee, Racine, Sheboygan, Washington or Waukesha and that were initially constructed on or before February 1, 2001.
NR 428.05(2)(a)
(a) The requirements of this subsection do not apply to emissions units which are subject to the emission limits of sub. (3).
NR 428.05(2)(b)
(b) Except as provided under par. (a), (c), or (f) the following categories of NOx emissions units listed under this subsection shall complete a combustion optimization to minimize NOx emissions in accordance with s.
NR 439.096 by December 31, 2002:
NR 428.05(2)(b)1.
1. Solid fuel-fired boilers with a maximum design heat input of 75 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 20%.
NR 428.05(2)(b)2.
2. Natural gas-fired boilers with a maximum design heat input of 75 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 20%.
NR 428.05(2)(b)3.
3. Distillate or residual fuel oil-fired boilers with a maximum design heat input of 75 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 20%.
NR 428.05(2)(b)4.
4. Cement kilns, lime kilns and calciners with a maximum design heat input of 75 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 20%.
NR 428.05(2)(b)5.
5. Reheat furnaces, annealing furnaces and galvanizing furnaces with a maximum design heat input of 75 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 20%.
NR 428.05(2)(b)6.
6. Glass manufacturing furnaces with a maximum design heat input of 75 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 20%.
NR 428.05(2)(c)
(c) An emissions unit described in par. (b) which first operates with a capacity factor exceeding 20% in an ozone season after the 2000 ozone season shall complete a combustion optimization by December 31 of the calendar year following that ozone season.
NR 428.05(2)(d)
(d) The owner or operator of an NO
x emissions unit subject to a combustion optimization requirement under par. (b) shall operate the emissions unit in a manner consistent with the results of the combustion optimization.
NR 428.05(2)(e)
(e) The owner or operator of a source subject to the NO
x emissions optimization requirements of this subsection shall perform monitoring sufficient to determine compliance with the requirements of this subsection. The monitoring required under this paragraph shall be either continuous monitoring of NO
x emissions or periodic monitoring of parameters adequate to ascertain the quality of the combustion and shall conform to the source's approved combustion optimization plan pursuant to s.
NR 439.096.
NR 428.05(2)(f)
(f) An emissions unit that is capable of firing secondary fuel is not subject to the requirements under this subsection when utilizing only a secondary fuel if any of the following apply:
NR 428.05(2)(f)1.
1. The emissions unit heat input capacity or maximum design power output while utilizing the secondary fuel is less than the applicability thresholds under this subsection.
NR 428.05(2)(f)2.
2. The emissions unit burns the secondary fuel only during any of the following periods:
NR 428.05(2)(f)2.a.
a. Supply interruption or curtailment of primary fuel. The secondary fuel usage under this paragraph may not exceed 500 hours within a 12 consecutive month time period unless the owner or operator obtains a fuel variance under s.
NR 436.06.
NR 428.05(2)(f)2.b.
b. Periodic testing, maintenance, or operator training of the secondary fuel when the periodic testing, maintenance, or operator training does not exceed a combined total of 48 hours during any calendar year.
NR 428.05(2)(f)3.
3. The secondary fuel constitutes less than 1 percent on an energy equivalent basis of the emissions unit's fuel consumption within the most recent 12 consecutive month time period.
NR 428.05(3)(a)(a)
Utility boilers. No person may cause, allow or permit nitrogen oxides to be emitted from a boiler owned or operated by a utility as defined in s.
NR 409.02 (84) with a maximum design heat input of 500 million Btu per hour or greater in excess of the most stringent of the following limits, as applicable, during the ozone season:
NR 428.05(3)(a)1.
1. 0.33 pound per million Btu of heat input on a 30-day rolling average basis, on or after December 31, 2002.
NR 428.05(3)(a)2.
2. 0.31 pound per million Btu of heat input on a 30-day rolling average basis, on or after December 31, 2003.
NR 428.05(3)(a)3.
3. 0.30 pound per million Btu of heat input on a 30-day rolling average basis, on or after December 31, 2004.
NR 428.05(3)(a)4.
4. 0.29 pound per million Btu of heat input on a 30-day rolling average basis, on or after December 31, 2005.
NR 428.05(3)(a)5.
5. 0.29 pound per million Btu of heat input on a 30-day rolling average basis, on or after December 31, 2006.
NR 428.05(3)(a)6.
6. 0.28 pound per million Btu of heat input on a 30-day rolling average basis, on or after December 31, 2007.
NR 428.05(3)(b)
(b)
Other boilers. The requirements of this paragraph apply to boilers which are not subject to the emission limits of par. (a).
NR 428.05(3)(b)1.
1. Solid fuel-fired units. On or after December 31, 2002, no person may cause, allow or permit nitrogen oxides to be emitted from a solid fuel-fired boiler, with a maximum design heat input of 100 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 25%, in excess of the following limits during the ozone season:
NR 428.05(3)(b)1.a.
a. 0.45 pound per million Btu of heat input on a 30-day rolling average basis for cyclone-fired boilers.
NR 428.05(3)(b)1.b.
b. 0.20 pound per million Btu of heat input on a 30-day rolling average basis for fluidized bed combustion boilers.
NR 428.05(3)(b)1.d.
d. 0.30 pound per million Btu of heat input on a 30-day rolling average basis for pulverized coal-fired boilers.
NR 428.05(3)(b)2.
2. Gaseous fuel-fired units. On or after December 31, 2002, no person may cause, allow or permit nitrogen oxides to be emitted from a gaseous fuel-fired boiler, with a maximum design heat input of 100 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 25%, in excess of 0.10 pound per million Btu of heat input on a 30-day rolling average basis during the ozone season.
NR 428.05(3)(b)3.
3. Distillate fuel oil-fired units. On or after December 31, 2002, no person may cause, allow or permit nitrogen oxides to be emitted from a distillate fuel oil-fired boiler, with a maximum design heat input of 100 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 25%, in excess of 0.12 pound per million Btu of heat input on a 30-day rolling average basis during the ozone season.
NR 428.05(3)(b)4.
4. Residual fuel oil-fired units. On or after December 31, 2002, no person may cause, allow or permit nitrogen oxides to be emitted from a residual fuel oil-fired boiler, with a maximum design heat input of 100 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 25%, in excess of 0.20 pound per million Btu of heat input on a 30-day rolling average basis during the ozone season.
NR 428.05(3)(c)
(c)
Reheat, annealing and galvanizing furnaces. On or after December 31, 2002, no person may cause, allow or permit nitrogen oxides to be emitted from a reheat furnace, annealing furnace or galvanizing furnace with a maximum design heat input of 100 million Btu per hour or greater and operated during the 2000 ozone season or a later ozone season with a capacity factor of at least 25%, in excess of 0.10 pound per million Btu heat input on a 30-day rolling average basis during the ozone season.
NR 428.05(3)(d)
(d)
Combustion turbines. On or after December 31, 2002, no person may cause, allow or permit nitrogen oxides to be emitted from a combustion turbine with a maximum design power output of 50 MWe or greater in an amount greater than the following during the ozone season:
NR 428.05(3)(d)1.
1. Gaseous fuel-fired units. 75 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average for units burning gaseous fuel.
NR 428.05(3)(d)2.
2. Distillate fuel oil-fired units. 110 parts per million dry volume (ppmdv), corrected to 15% oxygen, on a 30-day rolling average basis for units burning distillate fuel oil.
NR 428.05(3)(e)
(e)
Reciprocating engines. On or after December 31, 2002, no person may cause, allow or permit nitrogen oxides to be emitted during the ozone season from reciprocating engines with a maximum design power output of 2000 hp or greater in excess of the following limits:
NR 428.05(3)(e)3.
3. 8.5 grams per brake horsepower-hour for distillate fuel oil-fired units.
NR 428.05(3)(f)
(f)
Emissions units using secondary fuel. An emissions unit that is capable of firing secondary fuel is not subject to the requirements under this subsection when utilizing only a secondary fuel if any of the following apply:
NR 428.05(3)(f)1.
1. The emissions unit heat input capacity or maximum design power output while utilizing the secondary fuel is less than the applicability thresholds under this subsection.
NR 428.05(3)(f)2.
2. The emissions unit burns the secondary fuel only during any of the following periods:
NR 428.05(3)(f)2.a.
a. Supply interruption or curtailment of primary fuel. The secondary fuel usage under this paragraph may not exceed 500 hours within a 12 consecutive month time period unless the owner or operator obtains a fuel variance under s.
NR 436.06.
NR 428.05(3)(f)2.b.
b. Periodic testing, maintenance, or operator training of the secondary fuel when the periodic testing, maintenance, or operator training does not exceed a combined total of 48 hours during any calendar year.
NR 428.05(3)(f)3.
3. The secondary fuel constitutes less than 1 percent on an energy equivalent basis of the emissions unit's fuel consumption within the most recent 12 consecutive month time period.