DCF 57.40(4)(c)(c) If the temperature inside the group home exceeds 80° Fahrenheit during summer months, the licensee shall provide for air circulation with fans or by other means. DCF 57.40(4)(d)(d) The heating unit shall be maintained in a safe condition as determined by an annual inspection by an individual professionally qualified to conduct such inspections. DCF 57.40(4)(f)(f) Bath and toilet rooms shall have either a window that opens or be equipped with exhaust ventilation to the outside. DCF 57.40(5)(5) Lighting. All habitable rooms shall have electric lighting sufficient to meet the needs of the group home and its residents. DCF 57.40(6)(6) Space requirements. There shall be at least 200 square feet of living space for each resident of the home. “Living space” includes any area that is used by a resident in daily living and excludes unfinished basement, attic, attached garage or similar areas, not usually occupied by a resident in daily living. The licensee shall ensure compliance with all of the following space requirements: DCF 57.40(6)(a)2.2. A group home serving only males or only females shall have at least one full bathroom that contains a toilet, sink, and a tub or shower available for use by residents. A group home initially licensed on or after January 1, 2006, serving males and females shall have 2 full bathrooms that are gender specific, each containing a toilet, sink and a tub or shower, unless the department grants an exception under s. DCF 57.02. DCF 57.40(6)(a)3.3. A bathroom that can be accessed only through a room used as a bedroom may not be counted as being available for use by residents who do not occupy that bedroom. DCF 57.40(6)(a)4.4. If the total number of residents and children of residents over the age of 2 years exceeds 10, there shall be 2 full bathrooms. DCF 57.40(6)(b)1.1. Each bedroom shall have a door that allows for privacy and a window that allows natural light to enter. DCF 57.40(6)(b)2.2. At least one wall of each room used as a bedroom by a resident shall be an outside wall. DCF 57.40(6)(b)3.3. For group homes licensed before January 1, 2006, the floor space of each bedroom shall be as follows: DCF 57.40(6)(b)3.a.a. A bedroom that is used by one resident shall have at least 55 square feet of floor space. DCF 57.40(6)(b)3.b.b. A bedroom that is occupied by 2 residents shall have at least 50 square feet of floor space for each resident. DCF 57.40(6)(b)3.c.c. A bedroom that is occupied by 3 or more residents shall have at least 45 square feet of floor space for each resident. DCF 57.40(6)(b)3.d.d. A bedroom that is occupied by a custodial parent and that parent’s child or children shall have the additional square footage required in s. DCF 57.36 (7). DCF 57.40(6)(b)4.4. For a group home that is licensed after the effective date of this rule, January 1, 2006, all of the following shall apply: DCF 57.40(6)(b)4.a.a. A bedroom that is used by one resident shall have at least 80 square feet of floor space. If the resident is non-ambulatory or uses adaptive devices for ambulating, the bedroom shall have at least 100 square feet of floor space. DCF 57.40(6)(b)4.b.b. A bedroom that is used by more than one resident shall have a minimum of 60 square feet of floor space for each resident. If either or both of the residents are non-ambulatory or uses adaptive devices for ambulation, the bedroom shall have at least 80 square feet of floor space for each resident. DCF 57.40(6)(b)5.5. The minimum space between beds, cribs, and bassinets shall be at least 2 feet. There shall be at least 5 feet of space between bunk beds. The top deck of a bunk bed shall be at least 3 feet below the lowest point of the ceiling and there shall be at least 3 feet between upper and lower bunks. DCF 57.40(6)(c)(c) Dining areas. Dining areas shall be of sufficient size to permit all residents and staff to sit down for meals at one time. DCF 57.40(6)(d)1.1. The kitchen shall be equipped with a stove, refrigerator, cooking and eating utensils, and any other appliance or utensil that may be required to meet the needs of each resident. DCF 57.40(6)(d)2.2. Each refrigerator and freezer shall be equipped with a clearly visible, accurate thermometer. Refrigerators shall be maintained at 40° Fahrenheit or lower. Freezers shall be maintained at 0° Fahrenheit or lower. DCF 57.40(6)(e)(e) Storage space. A group home shall have storage space to accommodate clothing and other personal items of each resident of the group home. DCF 57.40(6)(f)(f) Study areas. There shall be a quiet area in the group home suitable for study. DCF 57.40(6)(g)(g) Laundry. Laundry facilities shall be available to meet the needs of all residents. Any laundry equipment in the group home shall be installed and vented in accordance with the manufacturer’s recommendations. DCF 57.40(7)(7) Stairways. Each stairway shall have a handrail. DCF 57.40 HistoryHistory: CR 04-067: cr. Register September 2005 No. 597, eff. 1-1-06; corrections in (3) (a) 2., (6) (a) 2. and (b) 3. d. made under s. 13.92 (4) (b) 7., Stats., Register November 2008 No. 635; correction in (3) (a) 2. made under s. 13.92 (4) (b) 7., Stats., Register August 2011 No. 668; EmR1106: emerg. cr. (7), eff. 9-16-11; CR 11-026: cr. (7) Register December 2011 No. 672, eff.1-1-12. DCF 57.41DCF 57.41 General safety precautions. DCF 57.41(1)(1) Windows and doors that are used for ventilation shall be properly screened. DCF 57.41(2)(2) Electrical systems and appliances shall be in good repair and properly protected. DCF 57.41(3)(3) Tubs and showers shall have safety strips or other non-slip surfaces applied to prevent slipping. DCF 57.41(4)(4) Group homes constructed on or after the effective date of this chapter, January 1, 2006, shall provide ground fault outlets for any electrical outlet within 6 feet of a water source in bathrooms, kitchens, laundry rooms, basements, in the garage and on the exterior of the group home. DCF 57.41(5)(5) Staff members and volunteers shall use universal precautions when exposed to blood and blood containing body fluids and tissue discharges. DCF 57.41(6)(6) The indoor and outdoor premises shall be free of hazards. DCF 57.41(7)(7) There shall be no flaking or deteriorating paint on exterior or interior surfaces. DCF 57.41(8)(8) No lead based paint or other toxic finishing material may be used on the premises of the group home. DCF 57.41(9)(9) Stairways, halls, and aisles shall be maintained in good repair, adequately lighted and free from obstacles. DCF 57.41(11)(11) Exterior stairs, walks, ramps and porches shall be maintained in a safe condition and free from the accumulation of water, ice, or snow. DCF 57.41(12)(12) Dangerous equipment and harmful substances unnecessary for the operation of the group home may not be kept on the premises. All necessary but potentially dangerous equipment, toxic substances and medications shall be kept inaccessible to residents. DCF 57.41 HistoryHistory: CR 04-067: cr. Register September 2005 No. 597, eff. 1-1-06. DCF 57.42(1)(a)(a) Each group home shall have a smoke detection system. The system shall be an electrically interconnected system listed by Underwriter’s Laboratory or a radio signal-emitting system which has at least one centrally mounted alarm horn which, when activated can be heard throughout the premises. DCF 57.42(1)(b)(b) A smoke detector shall be located at each of the following locations in the home: DCF 57.42(1)(b)2.2. Next to doors leading to every enclosed stairway on each floor level. DCF 57.42(1)(b)3.3. Every hall. Smoke detectors located in a hall shall not be spaced more than 30 feet apart nor more than 15 feet from any wall. DCF 57.42(1)(b)4.4. Common use rooms, including living rooms, dining areas, lounges, family rooms and recreation rooms, except the kitchen. DCF 57.42(1)(c)(c) The smoke detection system shall be tested at least monthly and results documented and kept on file at the group home. DCF 57.42(1)(d)(d) A smoke detector that is located in a room used as a bedroom may be battery operated, free-standing and separate from the interconnected system. DCF 57.42(2)(a)(a) There shall be a diagrammatic floor plan of the group home posted on each floor level of the group home clearly indicating the direction of each exit for emergency evacuation. DCF 57.42(2)(b)(b) Evacuation drills shall be conducted with residents at least monthly and documented, including the date and time of the drill, the evacuation time and any problems encountered during the drill. An evacuation drill shall be conducted during sleeping hours, or which, simulates sleeping hours at least once every 6 months. DCF 57.42(2)(c)(c) Staff members shall personally evacuate each resident with limited mobility or having limited understanding regarding evacuation procedures from the group home. If the group home population includes a hearing impaired resident, there shall be written procedures specifying that a staff member shall immediately alert the resident in case of fire. DCF 57.42(3)(a)(a) Each group home shall have a fire extinguisher in the size, type, and location specified by the local fire department. At least one fire extinguisher shall be located in the kitchen and on each floor level of the group home. DCF 57.42(3)(b)(b) Each extinguisher shall be operable at all times, inspected at least once a year by a qualified fire safety expert and have a label indicating its present condition and date of its last inspection. DCF 57.42(4)(4) Fire safety inspection. The licensee shall have an annual fire safety inspection. The results of the inspection shall be reported to the department field office that serves the group home as required under s. DCF 57.13 (9). DCF 57.42 HistoryHistory: CR 04-067: cr. Register September 2005 No. 597, eff. 1-1-06; correction in (4) made under s. 13.92 (4) (b) 7., Stats., Register November 2008 No. 635; EmR1106: emerg. am. (4), eff. 9-16-11; CR 11-026: am. (4) Register December 2011 No. 672, eff. 1-1-12. DCF 57.425(1)(1) A group home in a one-unit or two-unit building shall have a functional carbon monoxide detector installed in the basement and on each floor level, except the attic, garage, or storage area of each unit, in accordance with the requirements of s. 101.647, Stats. DCF 57.425 NoteNote: A one-unit building is a single family residence. A two-unit building is a duplex or two-flat.
DCF 57.425(2)(2) A group home in a building with at least 3 units shall have one or more functional carbon monoxide detectors installed in accordance with the requirements of s. 101.149, Stats. DCF 57.425 HistoryHistory: EmR1106: emerg. cr., eff. 9-16-11; CR 11-026: cr. Register December 2011 No. 672, eff.1-1-12. DCF 57.43DCF 57.43 Furnishings and appliances. DCF 57.43(1)(1) The living space shall be sufficiently furnished and in a good state of repair, maintained in a clean condition, and shall allow for free and informal use by residents. DCF 57.43(2)(2) Each bed shall be of such size as to ensure comfort of the resident. Each bed shall have suitable springs in good condition, a clean, comfortable mattress that is covered with a mattress pad and a waterproof covering when necessary, a pillow, at least 2 sheets, a bedspread, and blankets adequate for the season. DCF 57.43(3)(3) The top bunk of a bunk bed shall not be used by residents with conditions limiting mobility and shall have a safety rail if used by a child under 8 years of age. DCF 57.43 HistoryHistory: CR 04-067: cr. Register September 2005 No. 597, eff. 1-1-06. DCF 57.44(1)(1) All garbage containing food waste shall be kept in covered, non-combustible watertight containers. Garbage shall be removed from the group home daily. DCF 57.44(2)(2) Dishes, silverware, and utensils shall be maintained and stored in a clean and sanitary manner. Eating and drinking utensils shall be thoroughly cleaned with detergent and hot water and rinsed after each use. DCF 57.44(3)(3) Single service dinnerware and utensils shall not be used at meals on a regular basis and may not be re-used. DCF 57.44(4)(4) All bed linens shall be changed at least once a week or more often if necessary. DCF 57.44 HistoryHistory: CR 04-067: cr. Register September 2005 No. 597, eff. 1-1-06. DCF 57.45(1)(1) A person who operates a group home shall be licensed by the department pursuant to this chapter and s. 48.625, Stats. Only one group home license may be issued for any one location. DCF 57.45(2)(2) For each location proposed for licensure by an applicant in sub. (1), the individual, corporation, or agency as applicable shall make a good faith effort to establish and maintain a community advisory committee as specified in s. 48.68 (4), Stats.
/code/admin_code/dcf/021_099/57
true
administrativecode
/code/admin_code/dcf/021_099/57/v/40/6/g
Department of Children and Families (DCF)
Chs. DCF 021-99; Safety and Permanence
administrativecode/DCF 57.40(6)(g)
administrativecode/DCF 57.40(6)(g)
section
true