ATCP 93.610(1)(e)2.
2. The maximum capacity of a tank or individual compartment used to store Class I liquids shall be 330 gallons.
ATCP 93.610(1)(e)5.
5. Tank wall thickness and joint configuration shall be in accordance with UL 142.
ATCP 93.610(1)(e)6.a.a. The fill opening for the tank shall be liquid tight, lockable and separate from any other opening.
ATCP 93.610(1)(e)6.b.
b. Tanks used to dispense gasoline shall be equipped with a drop tube at the fill opening that terminates within 6 inches of the tank bottom.
ATCP 93.610(1)(e)7.
7. Tanks shall be provided with an updraft-type vent affixed to an 18-inch high standpipe, and the vent shall comply with one of the following:
ATCP 93.610(1)(e)9.a.a. Tanks that store Class I liquids shall be provided with a permanently mounted, listed pumping device.
ATCP 93.610(1)(e)9.b.
b. A pump using a gasoline combustion engine may only be used on tanks containing Class II or III liquids.
ATCP 93.610(1)(e)10.
10. Tank wagons shall be provided with listed fueling hose that is stored and secured on a hanger or hose reel.
ATCP 93.610(1)(e)12.
12. Where Class I or II liquids are dispensed, means shall be provided to electrically bond the tank to the equipment being fueled.
ATCP 93.610(1)(e)13.
13. Frames, chassis, tires, and rims shall be constructed and maintained so they are adequate to support the weight of the system and keep it stable.
ATCP 93.610(1)(e)14.b.
b. Tanks with multiple compartments shall also be marked at the fill point of the tank.
ATCP 93.610(1)(f)1.1. Tank wagons shall be empty of liquid product while being towed off the premises where used or on any public access road, lane or highway.
ATCP 93.610(1)(f)2.
2. Tank wagons shall be protected from public access and public vehicle collision while on the premises where used.
ATCP 93.610(1)(f)3.
3. Tanks placed within 25 feet of a public roadway shall be protected by collision protection.
ATCP 93.610(1)(f)4.
4. Tank wagons that contained Class I liquids immediately before transport shall be purged of flammable vapors before transport off the premises where used.
ATCP 93.610(1)(f)5.
5. The fueling operator shall remain in attendance at the dispensing nozzle while fuel is flowing.
ATCP 93.610(1)(f)7.
7. No more than one tank wagon may be towed at one time by a transport vehicle.
ATCP 93.610(1)(f)9.b.
b. Where setbacks required in subd.
9. a. cannot be met, the setbacks from buildings and public ways shall be the maximum allowed by the current conditions at the site, as approved by the authorized agent or the department.
ATCP 93.610(2)(a)(a)
General. This section applies to temporary uses of movable tanks constructed in accordance with NFPA 30 section 21.4.2. or a similar standard recognized by the department.
ATCP 93.610(2)(b)
(b)
Duration of use. After 24 months, movable tanks need to be either removed, replaced, or inspected and recertified by the manufacturer.
ATCP 93.610(2)(c)
(c)
Location and type of use. Movable tanks may be used only for fueling of vehicles and equipment in the following situations:
ATCP 93.610(2)(d)
(d)
Limitations on location and type of use. Movable tanks may not be used for any retail sales, or for fueling vehicles unless the vehicles are dedicated to the operation of the specific project or facility.
ATCP 93.610(2)(e)1.1. Movable tanks shall be constructed in accordance with the design standards of NFPA 30 section 21.4.2 or a similar standard recognized by the department.
ATCP 93.610(2)(f)1.b.
b. Where setbacks required in subd.
1. a. cannot be met, the setbacks from buildings and public ways shall be the maximum allowed by the current conditions at the site, as approved by the authorized agent or the department.
ATCP 93.610 Note
Note: For farming operations, there are additional setback requirements in s.
ATCP 93.630.
ATCP 93.610(2)(f)2.
2. Movable tanks shall be protected from public access and public vehicle collision.
ATCP 93.610(2)(f)3.
3. Tanks placed within 25 feet of a public roadway shall be protected by collision protection.
ATCP 93.610(2)(f)4.
4. The fueling operator shall remain in attendance at the dispensing nozzle while fuel is flowing.
ATCP 93.610(3)(a)(a)
General. This section applies to temporary uses of tank vehicles that are constructed in accordance with NFPA 385.
ATCP 93.610 Note
Note: See s.
ATCP 93.330 (4) for requirements for converting a tank vehicle to a stationary tank.
ATCP 93.610 Note
Note: In accordance with s.
ATCP 93.700, owners or operators of tank vehicles who conduct fueling in accordance with this section are required to comply with the financial responsibility requirements in subchapter VII.
ATCP 93.610(3)(b)
(b)
Duration of use. Tank vehicles may remain on the customer's property for a maximum of 5 days unless any of the following conditions apply:
ATCP 93.610(3)(b)2.
2. Prior to the tank vehicle arriving at the customer's property, the local fire department has approved conditional use for more than 5 days.
ATCP 93.610 Note
Note: Federal Spill Prevention Control and Countermeasure requirements in
40 CFR 112 include provisions for secondary containment for tank vehicles while parked.
ATCP 93.610(3)(c)
(c)
Location and type of use. Tank vehicles may be used only for transferring fuel into a fixed-tank system, or for fueling of vehicles and equipment in the following situations:
ATCP 93.610(3)(c)3.
3. Fueling of fleet vehicles or locomotives in accordance with this subsection.
ATCP 93.610 Note
Note: This type of fueling is also known by the term “wet-hose fueling.”
ATCP 93.610 Note
Note: NFPA 30A section 11.9 allows fueling of Class II fuels directly from a tank vehicle, for commercial or governmental watercraft used in connection with the business.
ATCP 93.610(3)(d)2.
2. Readily accessible and functional portable fire extinguishers shall be carried on the tank vehicle as required by NFPA 385.
ATCP 93.610 Note
Note: NFPA 385 requires one portable fire extinguisher with a minimum rating of 4A, 40-B:C – or 2 or more extinguishers, each having a minimum rating of 2A, 20-B:C. NFPA 385 and this chapter require portable fire extinguishers to be maintained in accordance with NFPA 10.
ATCP 93.610(3)(d)3.c.
c. Non-water absorbent material capable of absorbing a minimum of 25 gallons of fuel.
ATCP 93.610(3)(e)
(e)
Transfer into tank vehicles. Fuel may be transferred into a tank vehicle only from a fixed storage tank system, except where this chapter permits otherwise for emergencies.
ATCP 93.610(3)(f)
(f)
Operations involving tank vehicles. All operations involving tank vehicles shall be in accordance with all of the following requirements:
ATCP 93.610(3)(f)1.
1. The fueling operation shall take place outdoors, and the point of transfer shall be at least 15 feet from a building.
ATCP 93.610(3)(f)3.
3. Expansion space shall be left in each tank to prevent overflow in the event of a rise in temperature.
ATCP 93.610(3)(f)4.
4. Nighttime deliveries shall be made in well-lighted areas, or a means of lighting shall be provided for the dispensing and delivery area.