ATCP 93.050(90)
(90) “
Precision tightness testing” or “precision tightness test” means a procedure for testing the ability of a tank system to prevent a release of a regulated substance, that is capable of detecting a 0.1 gallon per hour leak rate with a probability of detection of 0.95 and a probability of false alarm of 0.05.
ATCP 93.050(91)
(91) “
Pressurized piping” means product piping that experiences product pressure above normal atmospheric pressure. Product pressure may be generated from a pump or static head of an aboveground storage tank.
ATCP 93.050(92)
(92) “
Pressurized system” or “remote pumping system” means a dispensing system where the pump is not located at, or is remote from, the dispenser.
ATCP 93.050(93)
(93) “
Product” means any regulated substance in a storage tank.
ATCP 93.050(94)
(94) “
Public access fueling” means the use of a facility by persons who are not employees of the facility to dispense fuel into vehicles, or to transfer fuel for resale into vehicles that are not owned or operated by the facility.
ATCP 93.050(96)
(96) “
Public used-oil collection center” means any used-oil collection facility that allows an individual who is not an employee of the facility to transfer used oil from a portable container into a storage tank.
ATCP 93.050(97)
(97) “Public way” means any public thoroughfare, sidewalk, dedicated alley, railroad, waterway or right-of-way. The point of measurement is from the engineered or natural borders of the vehicle or pedestrian traffic lanes.
ATCP 93.050(98)
(98) “
Readily accessible” means capable of being reached easily and quickly for operation, maintenance and inspection.
ATCP 93.050(99)
(99) “
Re-commission” means the process of returning a system, component or process to a code-complying, in-service condition.
ATCP 93.050(100)
(100) “Recreational vehicle” means any self-propelled motor-driven vehicle that is used for moving people typically off-road, on land, snow, ice or water for sport or recreation, such as snowmobiles and all-terrain vehicles.
ATCP 93.050(101)
(101) “Red-tag” means a red tag secured to a component of a storage or dispensing system, which gives notice that the system or the product stored is under enforcement action for failure to comply with the requirements of either this chapter or ch.
ATCP 94, and which prohibits operation of the system until the tag is removed by or under the direction of the authority having jurisdiction.
ATCP 93.050(102)
(102) “Regulated substance” means any flammable or combustible liquid and any liquid that is a federally regulated hazardous substance as defined in s.
168.21, Stats.
ATCP 93.050 Note
Note: The definition of federally regulated hazardous substances in s.
168.21 (3), Stats., corresponds to the CERCLA List of Hazardous Substances and Reportable Quantities contained in
40 CFR 302.4, Table 302.4.
ATCP 93.050(103)
(103) “Release” means any discharge, including spilling, leaking, pumping, pouring, emitting, emptying, leaching, dumping or disposal of a regulated substance into groundwater, surface water or subsurface soils.
ATCP 93.050 Note
Note: See sub. (62) for a definition of “leak,” sub. (76) for a definition of “obvious release” and sub. (113) for a definition of “suspected release.”
ATCP 93.050(104)
(104) “Release detection” means determining whether a discharge of a regulated substance has occurred from a storage tank system into the environment.
ATCP 93.050(105)
(105) “Repair” means any work necessary to correct or restore a tank, pipe, spill prevention equipment, overfill prevention equipment, corrosion protection equipment, leak detection equipment, or other storage tank or dispensing system component that either has caused a suspected or obvious release or has failed to function properly.
ATCP 93.050(106)
(106) “Residential watercraft fueling facility” means that portion of a 1- or 2-family residential property where liquid fuels are stored in or dispensed for non-retail purposes from fixed equipment on land into the fuel tanks of self-propelled watercraft, including all facilities used for the storage, dispensing, and handling of flammable and combustible liquids.
ATCP 93.050(107)
(107) “Sacrificial anode system” means a method of corrosion protection that generates cathodic current from the galvanic corrosion of an expendable anode which is more electrochemically active than the structure being protected.
ATCP 93.050(108)
(108) “Secondary containment” means an approved barrier installed around a storage tank system that is designed to prevent a leak from the primary tank or piping from contacting the surrounding earth or the waters of the state before the leak can be detected and cleaned up.
ATCP 93.050(109)
(109) “Significant noncompliance” means the existence of one or more of the following:
ATCP 93.050(109)(a)
(a) A violation that causes, or may cause, a substantial, continuing risk to public health or the environment.
ATCP 93.050(109)(b)
(b) A violation that substantially deviates from a requirement of this chapter.
ATCP 93.050(109)(c)
(c) A violation that includes failure to install, maintain or operate equipment essential to preventing or detecting leaks.
ATCP 93.050(109)(d)
(d) A violation that is observed to reoccur repeatedly as a result of intentional or unintentional administrative or operational oversight.
ATCP 93.050(110)
(110) “Space heating” means heating of areas intended for occupancy or storage.
ATCP 93.050(111)
(111) “Storm water or wastewater collection system” means piping, pumps, conduits, and any other equipment necessary to collect and transport the flow of surface water run-off resulting from precipitation, or domestic, commercial, or industrial wastewater to and from retention areas or any areas where treatment is designated to occur. The collection of storm water and wastewater does not include treatment except where incidental to conveyance.
ATCP 93.050(112)
(112) “Structure” means an assembly of materials forming a construction for occupancy, storage, use, shelter or weather protection meeting the definition of place of employment under sub.
(88) or public building under sub.
(95).
ATCP 93.050 Note
Note: The department does not consider a tank to be a structure although local or municipal regulations may classify a tank as a structure.
ATCP 93.050(113)(a)
(a) There is indication that a tank system or dispensing system has leaked — such as inventory losses; observable free product or evidence of free product in secondary containment at dispensers, submersible pumps or spill buckets; petroleum odors; unexplained presence of water in a tank; or activation of a leak detection alarm system — but there is no observable environmental evidence of a release.
ATCP 93.050(113)(b)
(b) There is observable environmental evidence of a release, such as soil discoloration or free product, but the source is unknown.
ATCP 93.050 Note
Note: See sub. (62) for a definition of “leak,” sub. (76) for a definition of “obvious release” and sub. (103) for a definition of “release.”
ATCP 93.050(114)
(114) “Tank” means a device designed to contain an accumulation of regulated substance and constructed of non-earthen materials such as concrete, steel, fiberglass or plastic, and including the following types of tanks, which have the following meanings:
ATCP 93.050(114)(a)
(a) “Abandoned tank” means an aboveground or underground tank with or without product that is not recognized by this chapter as in-use, temporarily out of service, or closed.
ATCP 93.050(114)(b)
(b) “Accumulator tank” or “accumulator reservoir” means a container that is integral to a closed-loop mechanical-system operation of equipment, and that is used either to provide a regulated substance on demand, such as a fluid that is used as a heating or cooling media, or to store a regulated substance that is displaced from the functioning equipment, such as from an elevator or hydraulic lift.
ATCP 93.050 Note
Note: Accumulator tanks are outside the scope of this chapter.
ATCP 93.050(114)(c)
(c) “Breakout tank” means a tank that is used to relieve surges in an oil pipeline system or to receive and store oil transported by a pipeline for reinjection and continued transportation by a pipeline. Tanks considered by this chapter to be breakout tanks do not have piping that transfers product directly to or from a loading rack.
ATCP 93.050(114)(d)
(d) “Day tank” means an intermediate tank in a product transfer system between a storage tank and the end use of the product, usually a generator. The purpose of a day tank is to provide immediate product to the end source where the supply may otherwise be influenced by product temperature, viscosity or inadequate supply pressure.
ATCP 93.050(114)(e)
(e) “Farm tank” means a tank that is constructed in accordance with NFPA 30A section 13.2 and installed on a farm premises.
ATCP 93.050(114)(f)
(f) “Field-erected tank” means an aboveground tank that is built on the site from sections and components.
ATCP 93.050 Note
Note: See par. (p) for a definition of “fixed tank.”
ATCP 93.050(114)(g)
(g) “Gravity tank” means a supply tank from which the product is delivered directly by gravity.
ATCP 93.050(114)(h)
(h) “Integral tank” means a vessel with a liquid capacity of less than 110 gallons, which supplies fuel to an engine and which is assembled and used with the engine as a single unit of equipment.
ATCP 93.050 Note
Note: Vessels with a capacity of 110 gallons or more are included in the definition of storage tank in par. (q).
ATCP 93.050(114)(i)
(i) “Movable tank” means an aboveground storage tank that meets all of the following:
ATCP 93.050(114)(i)1.
1. Has a liquid capacity of 110 gallons or more, and is used for storing and dispensing liquid motor vehicle fuel.
ATCP 93.050(114)(i)2.
2. Is supported on skids, wheels without axles, or similar means and is not mounted upon a tank vehicle or chassis capable of road travel.
ATCP 93.050 Note
Note: Movable tanks are acceptable for use at construction projects, farms, and other locations recognized in subch. VI, where it is more practical to move the tank, typically by lifting equipment, to off-road motorized equipment for dispensing, rather than drive the motorized equipment to the tank.
ATCP 93.050(114)(j)
(j) “Multi-compartment tank” or “multi-chamber tank” means a vessel that contains 2 or more compartments created by the presence of an interior wall so that 2 or more substances can be stored at the same time within a single tank shell.
ATCP 93.050 Note
Note: In accordance with s.
ATCP 93.250, each compartment of a multi-compartment tank is considered a separate tank, even if the same substance is stored in more than one compartment.
ATCP 93.050(114)(k)
(k) “Portable tank” means an aboveground closed vessel that has a liquid capacity of 110 gallons or more; is not otherwise defined in this chapter; is equipped with skids, mountings or accessories to facilitate handling of the tank by mechanical means; and is not intended for fixed installation or for highway vehicle fueling. “Portable tank” includes intermediate bulk containers.
ATCP 93.050(114)(L)1.1. “Process tank” or “flow-through process tank” means a tank that forms an integral part of a production process through which there is a steady, variable, recurring, or intermittent flow of materials during the operation of the process and the tank is utilized to carry out or control the heating, cooling, mixing, blending, separating, metering, or chemical action of materials. The processing is done on a regular basis and it is the primary function of the tank.
ATCP 93.050(114)(L)2.
2. “Process tank” or “flow-through process tank” does not include a tank that is used for the storage of materials before their introduction into the production process or for the storage of finished products or by-products from the production process, or a tank that is only used to recirculate materials. A process tank would be considered a storage tank if the vessel is used as storage for a period exceeding 96 hours after the processing ends.
ATCP 93.050 Note
Note: Process tanks are outside the scope of this chapter.
ATCP 93.050(114)(m)
(m) “Product recovery tank” means a tank that forms an integral part of a ch.
ATCP 93 regulated substance spill control system for a storage, processing or transfer area. The purpose of the tank is spill recovery and temporary containment. A product recovery tank does not include a tank that is used for the storage of materials or by-products from a flow-through reclamation process. A product recovery tank will be considered a storage tank if the vessel is used as storage for a period exceeding 96 hours after the control of a release or spill.
ATCP 93.050 Note
Note: Product recovery tanks are outside the scope of this chapter.
ATCP 93.050(114)(n)
(n) “Residential tank” means a tank located on the same property as a 1- or 2-family dwelling or a residential building that falls within the scope of chs.
SPS 361 to
366 and used only by the residents of the property or for the maintenance of the property.
ATCP 93.050(114)(o)
(o) “Service tank” means a tank that is used for a limited period of time during the servicing of liquid-bearing equipment, to hold liquids temporarily during the servicing, cleaning or relocation of the equipment.
ATCP 93.050 Note
Note: Service tanks are outside the scope of this chapter. Service tanks include the defueling and refueling tanks that are used in commercial aviation environments. These tanks are used for removal of fuel from an aircraft to facilitate other maintenance for the aircraft and for return of that fuel to the aircraft immediately thereafter. They are typically not moved from one site to another and are operated by employees of an aviation service company under aviation service protocols and monitored situations.
ATCP 93.050(114)(p)
(p) “Stationary tank” or “fixed tank” means a storage vessel intended for stationary installation and not intended for relocation, loading, unloading, or attachment to a transport vehicle, as part of its normal operation in the process of use.
ATCP 93.050(114)(q)
(q) “Storage tank” means a liquid-tight vessel that is intended for fixed or stationary use or a tank that is used for fuel dispensing under subch.
VI but is not used for any of the excepted purposes in s.
ATCP 93.020 (6). This term includes a vessel which has a liquid capacity of 110 gallons or more and which is assembled and used with an engine as a single unit of equipment.
ATCP 93.050(114)(r)
(r) “Work-top tank” means an aboveground steel rectangular tank for combined use as a working surface and a storage tank for Class IIIB liquids.
ATCP 93.050(115)
(115) “Tank system” includes the primary tank and pipe, integral secondary containment, integral supports, leak detection, overfill prevention, spill containment, anti-siphon devices, any vapor-recovery system connected to the tank, and the necessary core components that allow the tank system to function as intended and in accordance with the installation requirements. Tank system configurations include onshore underground storage tanks, onshore aboveground storage tanks, and storage tanks over water that are integral with a stationary pier, floating vessel or floating structure for the purpose of storage or vehicle fueling.
ATCP 93.050 Note
Note: In a typical fueling island, the dispensing system, as defined in sub. (41), begins immediately downstream of the emergency shutoff valve, and all components upstream of that point, including the shutoff valve, are part of the tank system.
ATCP 93.050(116)
(116) “Tank-system integrity assessment” or “TSIA” means the process by which the department seeks to determine if the integrity of a tank system or any component thereof has been compromised. This process includes precision tightness testing, inventory reconciliation, visual inspection of system components, and calibration checks of dispensers and automatic tank gauges.
ATCP 93.050 Note
Note: In general, TSIAs are to be performed if there are indications that the integrity of a system has been compromised.
ATCP 93.050(117)
(117) “Tank-system site assessment” or “TSSA” means the process by which the department expects tank-system owners or operators to determine if a tank system or any component of that system has released petroleum products or other hazardous substances into the soil, groundwater or surface waters. This process includes all of the following:
ATCP 93.050(117)(a)
(a) Observation of field conditions, such as stained soils; odors; pitting, holes or cracks in tank system components; observable leaks; and elevated in-field soil-gas readings.
ATCP 93.050(117)(b)
(b) Collection of soil samples for laboratory analysis of petroleum products or other hazardous substances, as prescribed in the department's
Tank System Assessment: A Guide to the
Assessment and Reporting of Suspected or Obvious Releases From Underground and Aboveground Storage Tank Systems.
ATCP 93.050(117)(c)
(c) Reporting of the field observations and sampling results in a format prescribed by the department.
ATCP 93.050 Note
Note: In general, TSSAs are to be performed at the time a storage tank system, or some component thereof, is to be permanently closed, upgraded or repaired, or if a change in service is to take place.
ATCP 93.050(118)
(118) “Tank vehicle” means a tank truck or trailer system designed and constructed to comply with NFPA 385.
ATCP 93.050 Note
Note: NFPA 385 recognizes 3 types of tank vehicles: (1) a tank truck in which the cargo tank is supported entirely on the truck chassis, (2) a tank semi-trailer in which the cargo tank is supported by both the truck chassis and trailer chassis, and (3) a tank full-trailer in which the cargo tank is supported entirely on the trailer chassis.
ATCP 93.050(119)
(119) “Tank wagon” means a tank that is affixed to a trailer system with at least one axle, is constructed in accordance with s.
ATCP 93.610 (1), has a liquid capacity of 1,100 gallons or less, and is used for storing and dispensing liquid motor vehicle fuel for equipment used on the site, or is used for storing other liquids regulated under this chapter. A tank wagon is not constructed to comply with NFPA 385.
ATCP 93.050 Note
Note: Since a tank wagon is not designed and constructed under NFPA 385 criteria, it shall be towed empty on the road for transport and placement in accordance with s.
ATCP 93.610 (1).
ATCP 93.050(120)
(120) “Temporarily out of service” or “TOS” means a storage tank system that is not in use meets the requirements of s.
ATCP 93.445 (1) or
93.545 (1) and is intended to be placed back into use within 24 months.
ATCP 93.050 Note
Note: Temporarily out of service does not apply to stationary tanks that are of seasonal use, such as heating fuel storage tanks.
ATCP 93.050(121)
(121) “Transfer area” means the area where product is transferred, commonly referred to as loading or unloading, between a storage tank and a transport vehicle. Transfer areas are located at terminals, as well as at end-user and intermediate vendors in the product distribution stream. The transfer area may involve loading racks, pipe stands, or direct hose-to-valve connections, and accommodate top or bottom transfer.
ATCP 93.050(121m)
(121m) “Underground storage tank” or “underground tank” has the meaning given in sub.
(122) unless the context requires otherwise.
ATCP 93.050(122)(a)(a) “Underground storage tank system” or “UST system” means any one or combination of tanks, including connected pipes, that is used to contain an accumulation of regulated substances, and the volume of which, including the volume of connected underground pipes, is 10 percent or more beneath the surface of the ground.
ATCP 93.050(122)(b)
(b) “Underground storage tank system” or “UST system” does not include any of the following or pipes connected to any of the following: