SPS 314.15 History History: CR 13-105: cr. Register August 2014 N0. 704, eff. 9-1-14.
SPS 314.16 SPS 314.16 Hose threads during construction. These are department informational notes to be used under NFPA 1 section 16.4.3.3.2.6:
Note: Section 213.15 of the Statutes regulates fire hose threads and fittings and reads as follows: “All fire hose fittings, apparatus fittings, 1.5 and 2.5 inches in diameter purchased or procured by a fire department or fire company shall be of the national standard hose thread as adopted by the national fire protection association. No fire department shall utilize hose and equipment not in conformance with the requirement that all threads shall be national standard hose thread as adopted by the national fire protection association. Any person offering for sale nonstandard hose couplings, fittings or apparatus fittings may be fined not less than $100 nor more than $500."
Note: NFPA 1963 contains the specifications for national standard hose thread.
SPS 314.16 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08.
SPS 314.20 SPS 314.20 Open flame devices and pyrotechnics. Substitute the following wording for the introductory paragraph in NFPA 1 section 20.1.5.3: No open flame devices or pyrotechnic devices may be used in any occupancy, unless otherwise permitted by the following:
SPS 314.20 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 09-104: am Register December 2010 No. 660, eff. 1-1-11.
SPS 314.27 SPS 314.27 Manufactured home and recreational vehicle sites. The requirements in NFPA 1 chapter 27 are not included as part of this chapter.
SPS 314.27 Note Note: See subch. XI of ch. SPS 321 and ch. SPS 326 for requirements for manufactured home sites and communities.
SPS 314.27 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08.
SPS 314.50 SPS 314.50 Commercial cooking equipment for mobile kitchens. This is a department exception to the requirements in NFPA 1 sections 50.2.1.1 and 50.4: Neither an exhaust hood nor an automatic fire suppression system is required for a mobile kitchen where all of the following conditions are met:
SPS 314.50(1) (1) The kitchen is less than 365 square feet in size.
SPS 314.50(2) (2) The kitchen is used on fewer than 12 days in a calendar year, for the purpose of cooking.
SPS 314.50(3) (3) The owner or operator of the kitchen maintains a record demonstrating compliance with sub. (2), retains the record with the kitchen, and makes the record available to an inspector upon request.
SPS 314.50 Note Note: A Department form that can be used in complying with the recordkeeping requirements in this section is available at the Department's Web site at http://dsps.wi.gov through links to Division of Industry Services forms.
SPS 314.50 History History: CR 09-104: cr. Register December 2010 No. 660, eff. 1-1-11.
SPS 314.53 SPS 314.53 Mechanical refrigeration. The requirements in NFPA 1 chapter 53 are not included as part of this chapter.
SPS 314.53 Note Note: See ch. SPS 345 for requirements for mechanical refrigeration.
SPS 314.53 History History: CR 09-104: cr. Register December 2010 No. 660, eff. 1-1-11.
SPS 314.65 SPS 314.65 Explosives, fireworks and model rocketry.
SPS 314.65(1)(1) Enforcement. This is a department informational note to be used under NFPA 495 section 1.6, as referenced in NFPA 1 section 65.9.1:
Note: Any inspections by fire inspectors do not substitute for the Department's licensing and permitting of the facilities that are regulated under this section and chapter SPS 307.
SPS 314.65(2) (2)Mixing plant operation. These are department rules in addition to the requirements in NFPA 495 chapter 5 as referenced in NFPA 1 section 65.9.1:
SPS 314.65(2)(a) (a) Personnel limitations. Only persons essential to the mixing and packaging operations shall be allowed in the mixing and packaging area at any one time.
SPS 314.65(2)(b) (b) Production limitations. No more than one day's production of blasting agent shall be permitted in the mixing and packaging area at any one time.
SPS 314.65(2)(c) (c) Labeling. All cartridges, bags or other containers of blasting agents shall be labeled to indicate their contents. Ammonium nitrate bags may not be re-used as containers for blasting agents unless they are clearly relabeled so that no mistake can be made regarding their contents.
SPS 314.65(3) (3)Magazine inspection. Substitute the following wording for the requirements in NFPA 495 section 9.7.2 as referenced in NFPA 1 section 65.9.1: All magazines containing explosive materials shall be opened and inspected at maximum intervals of 7 days to determine whether there has been unauthorized or attempted entry into the magazines or whether there has been unauthorized removal of the magazines or their contents.
SPS 314.65(4) (4)Use of explosive materials. The requirements in NFPA 495 chapters 10 and 11 as referenced in NFPA 1 section 65.9.1 are not included as part of this chapter.
SPS 314.65 Note Note: See ch. SPS 307 for requirements relating to the use of explosive materials.
SPS 314.65 History History: CR 06-120: cr. Register February 2008 No. 626, eff. 3-1-08; CR 13-105: am. (2) (intro.), (3) Register August 2014 No. 704, eff. 9-1-14.