NR 418.03(1)(b)2.c.c. Height above ground of emission point of more than 220 feet: 5.8 pounds of sulfur dioxide per million Btu heat input. NR 418.03(1)(c)(c) Any fossil fuel fired steam generating boiler rated at more than 25 million Btu heat input per hour firing liquid fossil fuel or liquid fossil fuel in combination with liquid or gaseous fuels: NR 418.03(1)(c)1.1. Distillate fuel oil: that occurring from firing a distillate fuel oil with a sulfur content equal to or less than 0.50% by weight. NR 418.03(1)(c)2.2. Residual fuel oil: that occurring from firing a residual fuel oil with a sulfur content equal to or less than 1.1% sulfur by weight. NR 418.03(2)(2) All boilers to which sub. (1) applies shall achieve final compliance and so certify to the department on or before December 31, 1982. NR 418.03 HistoryHistory: Renum. from NR 154.12 (5), Register, September, 1986, No. 369, eff. 10-1-86; am. (1) (intro.), (b) 2. b., (c) 1. and (2) (intro.), Register, May, 1992, No. 437, eff. 6-1-92; r. (2) (intro.) and (a) to (e), renum. (2) (f) to be (2), Register, December, 1995, No. 480, eff. 1-1-96. NR 418.035NR 418.035 Southeastern Wisconsin intrastate AQCR. In the Southeastern Wisconsin intrastate AQCR, installations of 250 million Btu per hour or less may not burn coal with a sulfur content exceeding 1.11 pounds per million Btu in the coal. NR 418.035 HistoryHistory: Renum. from NR 417.04 and am., Register, May, 1992, No. 437, eff. 6-1-92; am. Register, February, 1995, No. 470, eff. 3-1-95. NR 418.04NR 418.04 Milwaukee RACT sulfur limitations. NR 418.04(1)(1) No person may cause, allow or permit sulfur dioxide to be emitted to the ambient air within the corporate boundaries of the city of Milwaukee, Milwaukee county, from any direct source on which construction or modification was commenced prior to December 1, 1983, averaged over any 24-hour period in amounts greater than specified in this subsection. NR 418.04(1)(a)(a) For any electrical utility installation rated at more than 250 million Btu heat input per hour, emissions from any stack may not exceed: NR 418.04(1)(a)1.1. 3.28 pounds sulfur dioxide per million Btu heat input for solid fossil fuel, 1.60 pounds sulfur dioxide per million Btu heat input for residual fuel oil and 0.50 pounds sulfur dioxide per million Btu heat input for all other fuels, or NR 418.04(1)(a)2.2. Q, when different fuels are burned in combination. Q is determined by the following equation:
where Q is the sulfur dioxide emission limit for a stack expressed in pounds of sulfur dioxide per million Btu heat input, X is the percent of total heat input derived from solid fossil fuel, Y is the percent of total heat input derived from residual fuel oil, and Z is the percent of total heat input derived from all other fuels.
NR 418.04(2)(2) When a source is subject to the emission limitations of sub. (1), the owner or operator shall achieve final compliance with the applicable emission limitations and so certify to the department by November 9, 1985. NR 418.04 HistoryHistory: Renum. from NR 154.12 (6) and am. Register, September, 1986, No. 369, eff. 10-1-86; am. (1) (a), Register, May, 1992, No. 437, eff. 6-1-92; am. (1) (a) 2. and (2) (intro.), r. (2) (a) to (e), Register, December, 1995, No. 480, eff. 1-1-96. NR 418.05NR 418.05 Green Bay and DePere RACT sulfur limitations. NR 418.05(1)(1) No person may cause, allow or permit sulfur dioxide to be emitted to the ambient air within the corporate boundaries of the cities of Green Bay and De Pere, Brown county, from any direct source on which construction or modification was commenced prior to February 1, 1984 in amounts greater than the following: NR 418.05(1)(a)(a) Each electric utility boiler shall comply with the following emission limitations: NR 418.05(1)(a)1.1. Any electric utility boiler with the emission point at a height above ground of not less than 377 feet: 5.58 pounds of sulfur dioxide per million Btu heat input. NR 418.05(1)(a)2.2. Any electric utility boiler with the emission point at a height above ground of less than 377 feet: 0.50 pounds of sulfur dioxide per million Btu heat input. NR 418.05(1)(b)(b) Any ammonia based sulfite pulp and paper mill shall comply with the following emission limitations: NR 418.05(1)(b)1.1. Each steam generating boiler capable of firing coal, spent sulfite liquor or other fuels: 5.95 pounds of sulfur dioxide per million Btu heat input. NR 418.05(1)(b)3.3. Any pulp digester blow stack: 6.03 pounds of sulfur dioxide per hour. NR 418.05(1)(b)4.4. All brown stock washers: a total of 23.18 pounds of sulfur dioxide per hour, from all washers. NR 418.05(1)(b)5.5. All paper dryers: a total of 94.13 pounds of sulfur dioxide per hour, from all dryers. NR 418.05(1)(b)6.6. All other sources not described in subds. 1. to 6.: a total of 15.71 pounds of sulfur dioxide per hour. NR 418.05(1)(c)(c) Any paper mill in Green Bay located between milepoints 3.3 and 4.0 on the Fox river shall comply with the following emission limitations: NR 418.05(1)(c)1.1. Fossil fuel fired steam generating boilers with the emission point at a height above ground of not less than 355 feet: maximum emission from any stack of 4.55 pounds of sulfur dioxide per million Btu heat input.