ATCP 93.100(2)(b)2.2. The name of the person, firm or corporation proposing the installation, if other than the owner. ATCP 93.100(2)(b)3.3. The address of the facility, including the names of adjacent streets and highways. ATCP 93.100(2)(c)1.1. A plot plan, drawn to a minimum scale of one inch equals 20 feet, indicating the location of the installation with respect to property lines; adjoining streets or alleys; fences, including those installed over or through any part of the system; and other buildings on the same property. The plot plan shall indicate the location of buildings; other tanks; loading and unloading points; utilities; sanitary or storm sewers; water mains; water service piping; community and private potable water wells or other potable water source on the subject property; any private potable water wells on adjacent property that are within 100 feet of the tank, piping or dispenser; and any offsite community wells that are within 1,200 feet of the tank, piping or dispenser. ATCP 93.100(2)(c)1m.1m. For installations where cathodic protection will be installed, buried metal underground structures and components within 200 feet, such as culverts and guy wire anchor points, should be included in the plot plan. ATCP 93.100 NoteNote: See s. ATCP 93.260 for minimum separating distances between tank systems and potable water supply sources. ATCP 93.100 NoteNote: Chapter NR 116 requires municipalities to prohibit any storage of materials that are buoyant, flammable, explosive or injurious to animal, plant or aquatic life, in floodway areas of floodplains. ATCP 93.100(2)(c)2.2. The class of construction of each building or room in a building that contains a storage tank shall also be indicated. ATCP 93.100(2)(d)(d) The location, size and capacity of each tank and the following information on the contents of the tank: ATCP 93.100 NoteNote: Flammability and combustibility classifications are established in NFPA 30 sections 4.3.1 and 4.3.2, and are expressed as a Roman numeral and a letter, such as IB or IIIA.
ATCP 93.100(2)(d)3.3. Whether the stored liquid is classified in any of the following hazard categories as defined in the applicable model fire code adopted by reference under ch. SPS 314: ATCP 93.100(2)(e)(e) The location of all piping runs and spacing between all tanks and piping. ATCP 93.100(2)(f)(f) The type of tank supports and clearances, including clearances between tanks. ATCP 93.100(2)(g)(g) The type of venting and pressure relief used and combined capacity of all venting and relief valves on each aboveground tank. ATCP 93.100(2)(h)(h) The location of fill, gauge and vent pipes and other openings for the tank. ATCP 93.100(2)(i)(i) The location of burners, tanks, pumps, piping and control valves and the relative elevations of any areas within the building where heavier-than-air vapors can accumulate. ATCP 93.100(2)(j)(j) The distances to dispensers, sizes of islands and traffic flow patterns or vehicle routes around or through the facility. ATCP 93.100(2)(k)(k) Information and specifications describing the design and placement of leak detection systems. ATCP 93.100(2)(L)1.1. Information regarding the type and operation of corrosion protection systems for tanks and piping.