NR 502.09(2)(a)(a) Incinerators having a capacity of 500 pounds per hour or less are exempt from all requirements of this section except the disposal requirements in sub. (5) (n) and the ash characterization requirements in sub. (6). The facility shall be designed and operated in conformance with emission limitations of state air pollution control regulations in chs. NR 400 to 499. NR 502.09(2)(b)(b) Incinerators burning only clean wood waste are exempt from all requirements of this section except the disposal requirements in sub. (5) (n) and the ash characterization requirements in sub. (6). NR 502.09(2)(c)(c) Municipal solid waste combustors which are regulated under s. NR 502.13 are not subject to regulation under this section. NR 502.09(2)(d)(d) Incinerators which burn only used oil which is managed in compliance with ch. NR 679 are exempt from all requirements of this section. NR 502.09(3)(a)(a) Except as otherwise specified in this section, new or expanded solid waste incinerator facilities may not be located in any of the following areas, unless an exemption has been granted under par. (b): NR 502.09(3)(a)2.2. Within 250 feet of any private water supply well, or within 1,200 feet of any public water supply well. NR 502.09(3)(b)(b) The department may require an incinerator facility meet additional locational criteria if there is significant potential for the facility to cause environmental pollution as defined in s. 283.01 (6m), Stats., nuisance conditions or bird hazard to aircraft. The department may grant exemptions from compliance with par. (a) 2. only upon demonstration by the applicant of circumstances which warrant such exemptions. Exemption from compliance with par. (a) 1. may not be granted. NR 502.09(4)(4) Plan of operation. No person may establish or construct an incinerator or expand an existing incinerator prior to obtaining approval in writing from the department of a plan of operation for the facility. The plan of operation for an incinerator shall provide a design which complies with the operational requirements in sub. (5) and contain, at a minimum, the following information: NR 502.09(4)(a)(a) A map or aerial photograph of the area showing land use and zoning within 1/4 mile of the site. The map or aerial photograph shall be of sufficient scale to show all homes, industrial buildings, roads and other applicable details and the details shall be identified and indicated on the map or aerial photograph. NR 502.09(4)(b)(b) A plot plan of the incinerator site including means of limiting access such as fencing, gates, natural barriers; methods of acceptably screening the facility from the surrounding area; general layout of equipment and flow pattern; road access; and location of existing and proposed utilities serving the incinerator. NR 502.09(4)(c)1.1. The legal description of the property where the incinerator will be located. NR 502.09(4)(c)3.3. Anticipated type and quantity of waste to be handled by the incinerator. NR 502.09(4)(c)5.5. Methods of collecting and treating or disposing of any liquid wastes or waste waters resulting from the operation of the incinerator. NR 502.09(4)(d)(d) A description of all appurtenances and procedures intended to store refuse beyond the end of the working day and to control dust, odors, fire outside the burning chamber and windblown materials. NR 502.09(4)(e)(e) A description of all methods of volume reduction including compaction, compression, baling, shredding, grinding, tamping, separating or classifying. NR 502.09(4)(g)(g) A description of incinerator inspection and maintenance schedule and procedures. NR 502.09(4)(h)(h) Detailed drawings and specifications of all structures, equipment and site. NR 502.09(4)(i)(i) A report which includes furnace design criteria and expected performance data, including emission data. NR 502.09(4)(j)(j) Identification of the site at which the ash residue will be disposed and alternative sites available for use when the primary site is inoperative. NR 502.09(5)(5) Operational requirements. No person may operate or maintain an incinerator except in conformance with the following minimum requirements, unless an exemption is granted by the department in writing: NR 502.09(5)(a)(a) The incinerator shall be equipped, operated and maintained in a nuisance-free manner. NR 502.09(5)(b)(b) Adequate shelter and sanitary facilities shall be available for personnel.