NR 462.02(54)(54)“Work practice standard” means any design, equipment, work practice or operational standard, or combination thereof, that is promulgated pursuant to section 112(h) of the Act.
NR 462.02 HistoryHistory: CR 05-116: cr. Register November 2006 No. 611, eff. 12-1-06.
NR 462.03NR 462.03Emission limits and work practice standards.
NR 462.03(1)(1)What are the subcategories of boilers and process heaters? The subcategories of boilers and process heaters are large solid fuel, limited use solid fuel, small solid fuel, large liquid fuel, limited use liquid fuel, small liquid fuel, large gaseous fuel, limited use gaseous fuel and small gaseous fuel. Each subcategory is defined in s. NR 462.02.
NR 462.03(2)(2)What emission limits, work practice standards and operating limits must I meet?
NR 462.03(2)(a)(a) You shall meet the requirements in subds. 1. and 2.
NR 462.03(2)(a)1.1. You shall meet each emission limit and work practice standard in Table 1 of this chapter that applies to your boiler or process heater, except as provided under s. NR 462.04 (3).
NR 462.03(2)(a)2.2. You shall meet each operating limit in Tables 2 to 4 of this chapter that applies to your boiler or process heater. If you use a control device or combination of control devices not covered in Tables 2 to 4, or you wish to establish and monitor an alternative operating limit and alternative monitoring parameters, you shall apply to the administrator for approval of alternative monitoring under 40 CFR 63.8(f).
NR 462.03 NoteNote: The authority to approve alternative monitoring is retained by the administrator and is not delegated to the department.
NR 462.03(2)(b)(b) As provided in 40 CFR 63.6(g), EPA may approve use of an alternative to the work practice standards in this section.
NR 462.03 HistoryHistory: CR 05-116: cr. Register November 2006 No. 611, eff. 12-1-06.
NR 462.04NR 462.04General compliance requirements.
NR 462.04(1)(1)What are my general requirements for complying with this chapter?
NR 462.04(1)(a)(a) You shall be in compliance with the emission limits, including operating limits, and the work practice standards in this chapter at all times, except during periods of startup, shutdown and malfunction.
NR 462.04(1)(b)(b) You shall always operate and maintain your affected source, including air pollution control and monitoring equipment, according to the provisions in s. NR 460.05 (4) (a) 1.
NR 462.04(1)(c)(c) You may demonstrate compliance with any applicable emission limit using fuel analysis if the emission rate calculated according to s. NR 462.05 (7) (d) is less than the applicable emission limit. Otherwise, you shall demonstrate compliance using performance testing.
NR 462.04(1)(d)(d) If you demonstrate compliance with any applicable emission limit through performance testing, you shall develop a site-specific monitoring plan according to the requirements in subds. 1. to 4. This requirement also applies to you if you petition the EPA administrator for alternative monitoring parameters under 40 CFR 63.8(f).
NR 462.04 NoteNote: The authority to approve alternative monitoring parameters is retained by the administrator and is not delegated to the department.
NR 462.04(1)(d)1.1. For each continuous monitoring system (CMS) required in this subsection, you shall develop and submit to the department for approval a site-specific monitoring plan that addresses subd. 1. a. to c. You shall submit this site-specific monitoring plan at least 60 days before your initial performance evaluation of your CMS. The plan shall include all of the following:
NR 462.04(1)(d)1.a.a. Installation of the CMS sampling probe or other interface at a measurement location relative to each affected process unit such that the measurement is representative of control of the exhaust emissions, such as on or downstream of the last control device.
NR 462.04(1)(d)1.b.b. Performance and equipment specifications for the sample interface, the pollutant concentration or parametric signal analyzer and the data collection and reduction systems.
NR 462.04(1)(d)1.c.c. Performance evaluation procedures and acceptance criteria, such as calibrations.
NR 462.04(1)(d)2.2. In your site-specific monitoring plan you shall also address subd. 2. a. to c.
NR 462.04(1)(d)2.a.a. Ongoing operation and maintenance procedures in accordance with the general requirements of s. NR 460.07 (3) (a), (c) and (d) 2.
NR 462.04(1)(d)2.b.b. Ongoing data quality assurance procedures in accordance with the general requirements of s. NR 460.07 (4).
NR 462.04(1)(d)2.c.c. Ongoing recordkeeping and reporting procedures in accordance with the general requirements of s. NR 460.09 (3) (a) and (5) (a) and (b) 1.
NR 462.04(1)(d)3.3. You shall conduct a performance evaluation of each CMS in accordance with your site-specific monitoring plan.
NR 462.04(1)(d)4.4. You shall operate and maintain the CMS in continuous operation according to the site-specific monitoring plan.
NR 462.04(1)(e)(e) If you have an applicable emission limit or work practice standard, you shall develop and implement a written startup, shutdown and malfunction plan (SSMP) according to the provisions in s. NR 460.05 (4) (c).