NR 670.022(1)(b)(b) Waiver of trial burn for DRE.
NR 670.022(1)(b)1.1. ‘Boilers operated under special operating requirements.’ When seeking to be licensed under ss. NR 666.104 (1) (d) and 666.110 that automatically waive the DRE trial burn, the owner or operator of a boiler shall submit documentation that the boiler operates under the special operating requirements provided by s. NR 666.110.
NR 670.022(1)(b)2.2. ‘Boilers and industrial furnaces burning low risk waste.’ When seeking to be licensed under the provisions for low risk waste provided by ss. NR 666.104 (1) (e) and s. NR 666.109 (1) that waive the DRE trial burn, the owner or operator shall submit all of the following:
NR 670.022(1)(b)2.a.a. Documentation that the device is operated in conformance with s. NR 666.109 (1) (a).
NR 670.022(1)(b)2.b.b. Results of analyses of each waste to be burned, documenting the concentrations of nonmetal compounds listed in ch. NR 661 Appendix VIII, except for those constituents that would reasonably not be expected to be in the waste. Identify the constituents excluded from analysis and explain the basis for their exclusion. The analysis shall rely on appropriate analytical techniques.
NR 670.022(1)(b)2.c.c. Documentation of hazardous waste firing rates and calculations of reasonable, worst-case emission rates of each constituent identified in subd. 2. b. using procedures provided by s. NR 666.109 (1) (b) 2.
NR 670.022(1)(b)2.d.d. Results of emissions dispersion modeling for emissions identified in subd. 2. c. using modeling procedures prescribed by s. NR 666.106 (8). The department will review the emission modeling conducted by the applicant to determine conformance with these procedures. The department will either approve the modeling or determine that alternate or supplementary modeling is appropriate.
NR 670.022(1)(b)2.e.e. Documentation that the maximum annual average ground level concentration of each constituent identified in subd. 2. b. quantified in conformance with subd. 2. d. does not exceed the allowable ambient level established in ch. NR 666 Appendix IV or V. The acceptable ambient concentration for emitted constituents for which a specific reference air concentration has not been established in ch. NR 666 Appendix IV or risk specific dose has not been established in ch. NR 666 Appendix V is 0.1 micrograms per cubic meter, as noted in the footnote to ch. NR 666 Appendix IV.
NR 670.022(1)(c)(c) Waiver of trial burn for metals. When seeking to be licensed under the Tier I (or adjusted Tier I) metals feed rate screening limits provided by s. NR 666.106 (2) and (5) that control metals emissions without requiring a trial burn, the owner or operator shall submit all of the following:
NR 670.022(1)(c)1.1. Documentation of the feed rate of hazardous waste, other fuels and industrial furnace feed stocks.
NR 670.022(1)(c)2.2. Documentation of the concentration of each metal controlled by s. NR 666.106 (2) or (5) in the hazardous waste, other fuels and industrial furnace feedstocks, and calculations of the total feed rate of each metal.
NR 670.022(1)(c)3.3. Documentation of how the applicant will ensure that the Tier I feed rate screening limits provided by s. NR 666.106 (2) or (5) will not be exceeded during the averaging period provided by that subsection.
NR 670.022(1)(c)4.4. Documentation to support the determination of the terrain-adjusted effective stack height, good engineering practice stack height, terrain type and land use as provided by s. NR 666.106 (2) (c) to (e).
NR 670.022(1)(c)5.5. Documentation of compliance with s. NR 666.106 (2) (f), if applicable, for facilities with multiple stacks.
NR 670.022(1)(c)6.6. Documentation that the facility does not fail the criteria provided by s. NR 666.106 (2) (g) for eligibility to comply with the screening limits.
NR 670.022(1)(c)7.7. Proposed sampling and metals analysis plan for the hazardous waste, other fuels and industrial furnace feed stocks.
NR 670.022(1)(d)(d) Waiver of trial burn for particulate matter. When seeking to be licensed under the low risk waste provisions of s. NR 666.109 (2) which waives the particulate standard (and trial burn to demonstrate conformance with the particulate standard), applicants shall submit documentation supporting conformance with subs. (1) (b) 2. and (1) (c).
NR 670.022(1)(e)(e) Waiver of trial burn for HCl and C12. When seeking to be licensed under the Tier I (or adjusted Tier I) feed rate screening limits for total chloride and chlorine provided by s. NR 666.107 (2) (a) and (5) that control emissions of hydrogen chloride (HCl) and chlorine gas (Cl2) without requiring a trial burn, the owner or operator shall submit all of the following:
NR 670.022(1)(e)1.1. Documentation of the feed rate of hazardous waste, other fuels and industrial furnace feed stocks.
NR 670.022(1)(e)2.2. Documentation of the levels of total chloride and chlorine in the hazardous waste, other fuels and industrial furnace feedstocks, and calculations of the total feed rate of total chloride and chlorine.
NR 670.022(1)(e)3.3. Documentation of how the applicant will ensure that the Tier I (or adjusted Tier I) feed rate screening limits provided by s. NR 666.107 (2) (a) or (5) will not be exceeded during the averaging period provided by that paragraph or subsection.
NR 670.022(1)(e)4.4. Documentation to support the determination of the terrain-adjusted effective stack height, good engineering practice stack height, terrain type and land use as provided by s. NR 666.107 (2) (c).
NR 670.022(1)(e)5.5. Documentation of compliance with s. NR 666.107 (2) (d), if applicable, for facilities with multiple stacks.
NR 670.022(1)(e)6.6. Documentation that the facility does not fail the criteria provided by s. NR 666.107 (2) (c) for eligibility to comply with the screening limits.
NR 670.022(1)(e)7.7. Proposed sampling and analysis plan for total chloride and chlorine for the hazardous waste, other fuels and industrial furnace feedstocks.
NR 670.022(1)(f)(f) Data in lieu of trial burn. The owner or operator may seek an exemption from the trial burn requirements to demonstrate conformance with ss. NR 666.104 to 666.107 and 670.066 by providing the information required by s. NR 670.066 from previous compliance testing of the device in conformance with s. NR 666.103, or from compliance testing or trial or operational burns of similar boilers or industrial furnaces burning similar hazardous wastes under similar conditions. If data from a similar device is used to support a trial burn waiver, the design and operating information required by s. NR 670.066 shall be provided for both the similar device and the device to which the data is to be applied, and a comparison of the design and operating information shall be provided. The department shall approve a license application without a trial burn if the department finds that the hazardous wastes are sufficiently similar, the devices are sufficiently similar, the operating conditions are sufficiently similar and the data from other compliance tests, trial burns or operational burns are adequate to specify (under s. NR 666.102) operating conditions that will ensure conformance with s. NR 666.102 (3). In addition, all of the following information shall be submitted:
NR 670.022(1)(f)1.1. For a waiver from any trial burn:
NR 670.022(1)(f)1.a.a. A description and analysis of the hazardous waste to be burned compared with the hazardous waste for which data from compliance testing, or operational or trial burns are provided to support the contention that a trial burn is not needed.
NR 670.022(1)(f)1.b.b. The design and operating conditions of the boiler or industrial furnace to be used, compared with that for which comparative burn data are available.