NR 439.085(3)(a)2.a.a. Total quantity of residual fuel oil burned expressed in thousands of gallons. NR 439.085(3)(a)2.b.b. Weighted average percent of the sulfur content of the residual fuel oil burned. NR 439.085(3)(a)2.c.c. Weighted average heat content expressed in Btu per gallon of residual fuel oil burned. NR 439.085(3)(a)2.d.d. Weighted average sulfur dioxide emission rate in terms of pounds of sulfur dioxide per million Btu heat input from the residual fuel oil burned. NR 439.085(3)(b)(b) The owner or operator of a residual fuel oil burning installation which has a residual fuel oil burning rate equal to or greater than 150,000 gallons per year but less than 1.5 million gallons per year shall submit, on a quarterly basis, information on residual fuel oil quality which is calculated from the supplier’s analyses for each shipment of residual fuel oil received at the installation. Each quarterly report is due within 30 days following the end of the calendar quarter. The owner or operator of the installation shall obtain certification from the supplier that the applicable methods and procedures in s. NR 439.08 (2) were followed by the supplier. The report shall include the following information for each calendar quarter: NR 439.085(3)(b)1.1. Total quantity of residual fuel oil burned expressed in thousands of gallons. NR 439.085(3)(b)2.2. Weighted average percent of the sulfur content of the residual fuel oil burned. NR 439.085(3)(b)3.3. Weighted average heat content expressed in Btu per gallon of residual fuel oil burned. NR 439.085(3)(b)4.4. Weighted average sulfur dioxide emission rate in terms of pounds of sulfur dioxide per million Btu heat input from the residual fuel oil burned. NR 439.085(3)(c)(c) The owner or operator of a residual fuel oil burning installation which has a residual fuel oil burning rate less than 150,000 gallons per year shall retain copies of the supplier’s analyses at the installation for each shipment of residual fuel oil received. The owner or operator shall obtain certification from the supplier that the applicable methods and procedures in s. NR 439.08 (2) were followed. The supplier’s analyses shall include, at a minimum, each shipment’s residual fuel oil quantity, sulfur content and heat content. NR 439.085(4)(4) Requirements for installations burning fuels other than coal or residual fuel oil. The owner or operator of an installation subject to reporting requirements under s. NR 439.03 which burns fuel other than coal or residual fuel oil may be required to sample and analyze the fuel used in a manner specified by the department. NR 439.085 HistoryHistory: Renum. from NR 439.075 (2) and am., cr. (4), Register, May, 1992, No. 437, eff. 6-1-92; am. (2) (a) 1., Register, February, 1995, No. 470, eff. 3-1-95; am. (2) (a) 1., (b) 1. and (c) 1., Register, November, 1999, No. 527, eff. 12-1-99; CR 00-175: am. (2) (a) 1., (b) 1. and (c) 1. Register March 2002 No. 555, eff. 4-1-02; CR 02-146: am. (2) (a) 1., (b) 1., (c) 1. and (3) (a) 1., cr. (3) (intro.) Register October 2003 No. 574, eff. 11-1-03; CR 05-116: am. (2) (a) 1., (b) 1. and (c) 1. Register November 2006 No. 611, eff. 12-1-06. NR 439.09NR 439.09 Methods and procedures for continuous emission monitoring. The owner or operator of a source conducting continuous emission monitoring under s. NR 439.095 shall use the methods and procedures listed in this section to install, calibrate, maintain and operate a continuous emissions monitoring system, or other methods and procedures approved, in writing, by the department: NR 439.09(1)(1) Continuous emissions monitoring systems for measuring opacity shall comply with all the provisions and requirements in Performance Specification 1 in 40 CFR part 60, Appendix B, incorporated by reference in s. NR 484.04 (21). NR 439.09(2)(2) Continuous emissions monitoring systems for measuring sulfur dioxide or nitrogen oxides shall comply with all the provisions and requirements in Performance Specification 2 in 40 CFR part 60, Appendix B or, for affected units, the performance specifications in 40 CFR part 75, Appendices A to I, incorporated by reference in s. NR 484.04 (21) and (27). NR 439.09(3)(3) Continuous emissions monitoring systems for measuring oxygen or carbon dioxide shall comply with all the provisions and requirements in Performance Specification 3 in 40 CFR part 60, Appendix B or, for affected units, the performance specifications in 40 CFR part 75, Appendices A to I, incorporated by reference in s. NR 484.04 (21) and (27). NR 439.09(4)(4) Continuous emissions monitoring systems for measuring carbon monoxide shall comply with all the provisions and requirements in Performance Specification 4 in 40 CFR part 60, Appendix B, incorporated by reference in s. NR 484.04 (21). NR 439.09(5)(5) Continuous emissions monitoring systems for measuring total reduced sulfur shall comply with all the provisions and requirements in Performance Specification 5 in 40 CFR part 60, Appendix B, incorporated by reference in s. NR 484.04 (21). NR 439.09(6)(6) Continuous emission rate monitoring systems shall comply with all the provisions and requirements in Performance Specification 6 in 40 CFR part 60, Appendix B, incorporated by reference in s. NR 484.04 (21). NR 439.09(7)(7) Continuous emissions monitoring systems for measuring hydrogen sulfide shall comply with all the provisions and requirements in Performance Specification 7 in 40 CFR part 60, Appendix B, incorporated by reference in s. NR 484.04 (21). NR 439.09(7m)(7m) Continuous emissions monitoring systems for measuring VOCs shall comply with all the provisions and requirements in the department’s approval issued under s. NR 439.095 (1). NR 439.09(8)(8) The owner or operator of a continuous emissions monitoring system shall comply with the quality control and quality assurance plan submitted by the owner or operator of the source and approved by the department. NR 439.09(9)(9) Continuous emissions monitoring systems shall meet the following minimum frequency of operation requirements: NR 439.09(9)(a)(a) Opacity monitors shall complete one cycle of sampling and analyzing for each successive 10-second period and one cycle of data recording for each successive 6-minute period. NR 439.09(9)(b)(b) Sulfur dioxide, nitrogen oxides, oxygen, carbon dioxide, carbon monoxide, hydrogen sulfide, total reduced sulfur and VOC monitors shall complete one cycle of sampling, analyzing and data recording for each successive 15-minute period. The values recorded shall be averaged hourly. Hourly averages shall be computed from 4 data points equally spaced over each 1 hour period, except during periods when calibration, quality assurance or maintenance activities are being performed. During these periods, a valid hour shall consist of at least 2 data points separated by a minimum of 15 minutes. NR 439.09(10)(10) The owner or operator of a continuous emissions monitoring system shall submit quarterly excess emission reports to the department within 30 days following the end of each calendar quarter in accordance with pars. (a) to (d). The owner or operator shall submit either a full excess emission report under par. (a) or a summary excess emission report under par. (d), as specified in writing by the department. NR 439.09(10)(a)(a) The full excess emission reports required under this subsection shall contain the following information: NR 439.09(10)(a)1.1. The date and starting and ending times or duration of each period of excess emissions and the magnitude of the emissions. NR 439.09(10)(a)2.2. The periods of excess emissions that occur during startups, shutdowns, sootblowing, control equipment malfunction, process malfunction, fuel problems, other known causes or for unknown causes. The report shall identify the cause of any malfunction and the measures taken to reduce excess emissions.