ATCP 93.610(1)(e)10.10. Tank wagons shall be provided with listed fueling hose that is stored and secured on a hanger or hose reel.
ATCP 93.610(1)(e)11.11. The pump shall be equipped with a manufactured anti-siphon device.
ATCP 93.610(1)(e)12.12. Where Class I or II liquids are dispensed, means shall be provided to electrically bond the tank to the equipment being fueled.
ATCP 93.610(1)(e)13.13. Frames, chassis, tires, and rims shall be constructed and maintained so they are adequate to support the weight of the system and keep it stable.
ATCP 93.610(1)(e)14.14.
ATCP 93.610(1)(e)14.a.a. The product stored in the tank shall be clearly marked on the tank.
ATCP 93.610(1)(e)14.b.b. Tanks with multiple compartments shall also be marked at the fill point of the tank.
ATCP 93.610(1)(e)15.15. Nozzles may not have a latch-open device.
ATCP 93.610(1)(f)(f) Operations involving tank wagons.
ATCP 93.610(1)(f)1.1. Tank wagons shall be empty of liquid product while being towed off the premises where used or on any public access road, lane or highway.
ATCP 93.610(1)(f)2.2. Tank wagons shall be protected from public access and public vehicle collision while on the premises where used.
ATCP 93.610(1)(f)3.3. Tanks placed within 25 feet of a public roadway shall be protected by collision protection.
ATCP 93.610(1)(f)4.4. Tank wagons that contained Class I liquids immediately before transport shall be purged of flammable vapors before transport off the premises where used.
ATCP 93.610(1)(f)5.5. The fueling operator shall remain in attendance at the dispensing nozzle while fuel is flowing.
ATCP 93.610(1)(f)6.6. Fuel may not be dispensed using gravity discharge.
ATCP 93.610(1)(f)7.7. No more than one tank wagon may be towed at one time by a transport vehicle.
ATCP 93.610(1)(f)8.8. Support shall be provided for single-axle units to prevent tipping.
ATCP 93.610(1)(f)9.9.
ATCP 93.610(1)(f)9.a.a. Tank placements shall comply with the setback requirements in s. ATCP 93.630 (2) (a), except as provided in subd. 9. b.
ATCP 93.610(1)(f)9.b.b. Where setbacks required in subd. 9. a. cannot be met, the setbacks from buildings and public ways shall be the maximum allowed by the current conditions at the site, as approved by the authorized agent or the department.
ATCP 93.610(2)(2)Movable tanks.
ATCP 93.610(2)(a)(a) General. This section applies to temporary uses of movable tanks constructed in accordance with NFPA 30 section 21.4.2. or a similar standard recognized by the department.
ATCP 93.610(2)(b)(b) Duration of use. After 24 months, movable tanks need to be either removed, replaced, or inspected and recertified by the manufacturer.
ATCP 93.610(2)(c)(c) Location and type of use. Movable tanks may be used only for fueling of vehicles and equipment in the following situations:
ATCP 93.610(2)(c)1.1. In accordance with sub. (1) (c) 1. to 7.
ATCP 93.610(2)(c)2.2. At recycling centers and refuse centers.
ATCP 93.610(2)(c)3.3. At power generating stations.
ATCP 93.610(2)(c)4.4. For short-term use during fuel storage equipment changeovers.
ATCP 93.610(2)(d)(d) Limitations on location and type of use. Movable tanks may not be used for any retail sales, or for fueling vehicles unless the vehicles are dedicated to the operation of the specific project or facility.