NR 440.218(7)(a)(a) The emission limits under this section apply at all times except during periods of startup, shutdown or malfunction, provided that no hospital waste or medical/infectious waste is charged to the affected facility during startup, shutdown or malfunction. NR 440.218(7)(b)(b) The owner or operator of an affected facility shall conduct an initial performance test as required under s. NR 440.08 to determine compliance with the emission limits using the procedures and test methods listed in subds. 1. to 12. The use of the bypass stack during a performance test shall invalidate the performance test. The procedures and test methods are as follows: NR 440.218(7)(b)1.1. All performance tests shall consist of a minimum of 3 test runs conducted under representative operating conditions. NR 440.218(7)(b)2.2. The minimum sample time shall be one hour per test run unless otherwise indicated. NR 440.218(7)(b)4.4. Method 3, 3A or 3B of 40 CFR part 60, Appendix A, incorporated by reference in s. NR 440.17 (1), shall be used for gas composition analysis, including measurement of oxygen concentration. Method 3, 3A or 3B shall be used simultaneously with each reference method. NR 440.218(7)(b)5.5. The pollutant concentrations shall be adjusted to 7% oxygen using the following equation: where:
Cadj is the pollutant concentration adjusted to 7% oxygen.
Cmeas is the pollutant concentration measured on a dry basis
(20.9 - 7) is 20.9% oxygen - 7% oxygen, the defined oxygen correction basis
20.9 is the oxygen concentration in air, percent
%O2 is the oxygen concentration measured on a dry basis, percent
NR 440.218(7)(b)9.9. Method 23 of 40 CFR part 60, Appendix A, incorporated by reference in s. NR 440.17 (1), shall be used to measure total dioxin/furan emissions. The minimum sample time shall be 4 hours per test run. If the affected facility has selected the toxic equivalency standards for dioxin/furan, under sub. (3), the following procedures shall be used to determine compliance: NR 440.218(7)(b)9.a.a. Measure the concentration of each dioxin/furan tetra- through octa- congener emitted using Method 23. NR 440.218(7)(b)9.b.b. For each dioxin/furan congener measured in accordance with subd. 9. a., multiply the congener concentration by its corresponding toxic equivalency factor specified in Table 2. NR 440.218(7)(b)9.c.c. Sum the products calculated in accordance with subd. 9. b. to obtain the total concentration of dioxin/furan emitted in terms of toxic equivalency. NR 440.218(7)(b)10.10. Method 26 or 26A of 40 CFR part 60, Appendix A, incorporated by reference in s. NR 440.17 (1), shall be used to measure hydrogen chloride emissions. If the affected facility has selected the percentage reduction standards for hydrogen chloride under sub. (3), the percentage reduction in hydrogen chloride emissions (%RHCl) shall be computed using the following formula: where:
%RHCl is the percentage reduction of hydrogen chloride emissions achieved
Ei is the hydrogen chloride emission concentration measured at the control device inlet, corrected to 7% oxygen, dry basis
Eo is the hydrogen chloride emission concentration measured at the control device outlet, corrected to 7% oxygen, dry basis
NR 440.218(7)(b)11.11. Method 29 of 40 CFR part 60, Appendix A, incorporated by reference in s. NR 440.17 (1), shall be used to measure lead, cadmium and mercury emissions. If the affected facility has selected the percentage reduction standards for metals under sub. (3), the percentage reduction in emissions (%Rmetal) shall be computed using the following formula: