ATCP 93.335ATCP 93.335Manufacture of organic coatings.
ATCP 93.335(1)(1)Application. This section applies to storage tank systems for flammable or combustible liquids used in the manufacture of organic coatings.
ATCP 93.335(2)(2)General. The tank systems shall comply with NFPA 35.
ATCP 93.335(3)(3)Certified installer. A certified installer shall perform or supervise the installation.
ATCP 93.335(4)(4)Retroactivity. Tanks existing by November 1, 2019, shall comply with the registration requirements in s. ATCP 93.140 by November 1, 2020, and shall comply with the spill and overfill requirements in s. ATCP 93.410 and with the transfer containment requirements in s. ATCP 93.420 (5) by December 31, 2024.
ATCP 93.335 HistoryHistory: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19; correction in (4) made under s. 13.92 (4) (b) 14., Stats., Register October 2019 No. 766.
ATCP 93.340ATCP 93.340Bulk plants and terminals.
ATCP 93.340(1)(1)Clearances at bulk plants that were in existence on may 1, 1991. Bulk plant facilities that were in existence on May 1, 1991, with setbacks less than those specified in NFPA 30 section 22.4 may be renovated or updated, but no additional storage capacity may be added in violation of the specified clearances.
ATCP 93.340(2)(2)Product identification.
ATCP 93.340(2)(a)(a) Standard color code. All new and existing tanks and piping at bulk plants and terminals shall use the identification scheme in API 1637.
ATCP 93.340 NoteNote: See s. ATCP 93.230 (12) for color coding of fill pipe caps and manhole covers for underground tanks.
ATCP 93.340(2)(b)(b) Type of identification. The product identification scheme in API 1637 shall be accomplished by one of the following methods:
ATCP 93.340(2)(b)1.1. A disc tag of non-sparking material.
ATCP 93.340(2)(b)2.2. A label using minimum one-inch block letters.
ATCP 93.340(2)(b)3.3. Painted sections at least 12 inches long.
ATCP 93.340(2)(c)(c) Location of identification. Tags shall be permanently affixed to the valve at the unloading riser, the pump control valves, the valve of a storage tank and load rack and on the product pipe lines in at least 3 locations equally spaced between terminating points or valves.
ATCP 93.340(3)(3)Property maintenance. Tank yards and diked areas shall be kept free from weeds, high grass, rubbish, and combustible materials that are not essential to the operation and shall be kept clean and orderly.
ATCP 93.340(4)(4)Security at bulk plants and terminal storage facilities. Owners and operators shall be aware of regulations, standards and operating practices that relate to facility security.
ATCP 93.340 NoteNote: Information on how to develop a comprehensive site security program is available in the API document, Security Guidelines for the Petroleum Industry, or the American Chemistry Council document, Site Security Guidelines for the U.S. Chemical Industry.
ATCP 93.340(5)(5)Transfer operations at bulk plants and terminals. In order to prevent a spill from moving beyond the loading or unloading area, any new or existing aboveground or underground storage tank which has a capacity of 5,000 gallons or more and which is drained or filled by pumping to or from a transport vehicle shall be provided with a catchment basin or treatment facility to contain the maximum capacity of the largest compartment of a tank car or tank vehicle loaded or unloaded at the facility. Existing tanks shall comply with this subsection within 2 years after November 1, 2019.
ATCP 93.340 NoteNote: Federal Spill Prevention Control and Countermeasure requirements in 40 CFR 112 may apply to smaller product transfers. A catchment basin may consist of remote impounding.
ATCP 93.340(6)(6)General requirements.
ATCP 93.340(6)(a)(a) Aboveground tanks at existing facilities. Aboveground tank systems at existing bulk plants and terminals shall comply with subch. IV.
ATCP 93.340(6)(b)(b) Underground tanks at existing facilities. Underground tank systems at existing bulk plants and terminals shall comply with subch. V.
ATCP 93.340(6)(c)(c) New facilities. New bulk plants and terminals shall comply with PEI RP800; aboveground tank systems there shall also comply with s. ATCP 93.400 (3), (4), (5), and (7) to (11); and underground tank systems there shall also comply with subch. V.
ATCP 93.340 HistoryHistory: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19; correction in (6) (c) made under s. 35.17, Stats., Register October 2019 No. 766.
ATCP 93.350ATCP 93.350Hazardous substances.
ATCP 93.350(1)(1)Scope and application.
ATCP 93.350(1)(a)(a) General.