NR 812.42(11)(c)(c) Casing Height.
NR 812.42(11)(c)1.1. When doing any water well work or pump installing work that involves entry into a well located outside a building, the water well driller or pump installer shall extend the well casing pipe to at least:
NR 812.42(11)(c)1.a.a. 12 inches above grade for any well that is less than 8 inches above grade and was installed before February 1, 1991.
NR 812.42(11)(c)1.b.b. 12 inches above grade for any well that is less than 12 inches above grade and was installed on or after February 1, 1991.
NR 812.42(11)(c)2.2. When the well casing height above grade does not comply with subd. 1. a. or b., the well driller or the pump installer shall measure the well casing pipe depth to verify that the well casing pipe depth complies with the rules in effect at the time that the well was constructed, if there is no confirmable well construction report available for the well. Well details, including location, well casing pipe depth, total well depth, distances to possible contaminant sources and well owner information shall be entered on a form and submitted to the department in accordance with s. NR 812.10 (15).
NR 812.42(11)(c)3.3. The extension of the well casing pipe shall be in accordance with sub. (12).
NR 812.42(11)(d)(d) Well cap or seal. When doing any water well work or pump installing work that involves entry into a well, the well driller or pump installer shall replace any unapproved well cap or seal with an approved well cap or sanitary well seal.
NR 812.42(11)(e)(e) Nonpressurized conduit. When any water well drilling work or pump installing work is performed involving entry into a well that has a nonpressurized conduit and the nonpressurized conduit may continue to be used, the well driller or pump installer shall evaluate the integrity of the nonpressurized conduit and its connection to the well casing pipe by performing a pressure test. The nonpressurized conduit shall be tested and proven watertight under a pressure of not less than 14 psi. The pressure shall be maintained for at least 30 minutes. If the nonpressurized conduit fails the pressure test, the installation shall be changed to a pitless connection. The nonpressurized conduit shall be completely eliminated by cutting off the well casing pipe below the nonpressurized conduit and extending the well casing pipe to at least 12 inches above grade and installing pressurized discharge piping according to the requirements of ss. NR 812.28, 812.31 and 812.32 (4). The extension of the well casing pipe shall be in accordance with sub. (12).
NR 812.42(11)(f)(f) Corrections. The features specified in pars. (a) to (e) must be corrected and may not be noted on a noncomplying features form instead of correcting the noncomplying feature or testing the nonpressurized conduit.
NR 812.42(12)(12)Well casing height extensions for steel well casing pipe.
NR 812.42(12)(a)(a) The well casing pipe in the ground may only be extended up if it has the minimum wall thickness for its diameter according to the requirements of s. NR 812.11 (6) Table B and is not in a deteriorated condition. If it does not meet these requirements, the well shall be filled and sealed according to the requirements of s. NR 812.26. The well casing pipe extension (riser pipe) shall meet the requirements of s. NR 812.11 (6) and shall be attached to the top of the existing casing by any of the following methods:
NR 812.42(12)(a)1.1. Cutting off the well casing pipe in the ground squarely, providing a bevel for the top of the well casing pipe and making a watertight weld between the beveled end of the well casing pipe and the beveled end of the riser pipe.
NR 812.42(12)(a)2.2. Cutting threads on the top of the well casing pipe and the bottom of the riser pipe with a pipe die and using a full-standard recessed threaded coupling to provide a watertight connection between the two pipes.
NR 812.42(12)(a)3.3. Welding a properly-sized, snug-fitting, pipe nipple, beveled on the lower end and having threads on the upper end, and meeting the requirements of s. NR 812.11 (6) to the beveled end of the well casing pipe. The pipe nipple shall be welded on the inside and the outside contact surfaces of the pipe nipple. A threaded riser pipe shall be screwed onto the top of the welded on pipe nipple.
NR 812.42(12)(a)4.4. Reaming out the threads of a full standard recessed coupling, at least 1/3 the length of the coupling, and welding the coupling to the top of the cut-off well casing pipe with a fillet weld on the inside and outside contact surfaces of the coupling. The riser pipe shall be threaded into the top of the coupling.
NR 812.42(12)(a)5.5. The threaded lower end of a riser pipe may not be welded to the cut-off end of a well casing pipe.
NR 812.42(12)(a)6.6. Riser pipe may not be connected to the well casing pipe by means of a compressible joint.
NR 812.42(13)(13)Disinfection, flushing and sampling. When working on existing water wells or pump installations, the well and water system shall be:
NR 812.42(13)(a)(a) Disinfected and flushed in accordance with s. NR 812.41.
NR 812.42(13)(b)(b) Sampled in accordance with s. NR 812.46.
NR 812.42 HistoryHistory: Cr. Register, January, 1991, No. 421, eff. 2-1-91; am. (1) (intro.), (a), (b), (2) (intro.), (a), (d), (5) (b), (6) (a) 2., (b) 2., (e), (7) (intro.) (9) (a) 1., cr. (4) (f), (6) (b) 4., (g), (7) (e), Register, September, 1994, No. 465, eff. 10-1-94; correction in (6) (a) 3. made under s. 13.93 (2m) (b) 7., Stats., Register, May, 2000, No. 533; CR 00-111: am. (1) (b), Register October 2001 No. 550, eff. 11-1-01; correction in (6) (a) 3. made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 13-099: am. (1) (title), (intro.), (a), renum. (1) (b) to (b) 1., cr. (1) (b) 2. to 5., am. (1) (c), (2) (title), (intro.), (a), (c), renum. (d) to (d) 1. to 3. and am., renum. (3) to (3) (a) to (c), am. (4) (f), cr. (4) (g), (h), am. (6) (intro.), renum. (6) (a) 2. to 2. a., b. and am., cr. (6) (a) 2. c., am. (6) (b) 4., r. (7) (a), renum. (7) (intro.) to (7) (a), (7) (b) to (e) to (7) (a) 1. to 4., cr. (7) (b), (c), renum. (8) to (8) (b) to (d) and am., cr. (8) (a), (e), am. (9) (a) (title), 1., renum. (9) (a) 2. to (a) 2., 3. and am., cr. (9) (a) 4., am. (9) (b) (intro.), 2., 3., cr. (9) (b) 5. to 8., cr. (10) to (13) Register September 2014 No. 705, eff. 10-1-14; correction in numbering (11) (c) to (f) made under s. 13.92 (4) (b) 1., Stats., correction in (3) made under s. 13.92 (4) (b) 2., Stats., corrections in (2) (d) 1. b., (11) (c) 2., (f) made under s. 13.92 (4) (b) 7., Stats., September 2014 No. 705; CR 18-095: cr. (intro), r. (1) (intro.), am. (1) (title), (a), (b) 1 to 4., 5. (intro.), a., b., r. (1) (b) 5. c., d., cr. (1) (b) 6., 7., am. (1) (c), cr. Table E, am. (2) (intro.), (a) to (c), (d) (intro.), 1. b., 2., 3., (3), cr. (3m), am. (4) (e), (f), (g) (intro.), (h), (5) (intro.), (b), (c), (6) (a) 1., 2. a. to c., cr. (6) (a) 2. d., am. (6) (a) 3., (b) (intro.), 1., 2., 4., (c) to (e), (7) (title), (a) (intro.), (b), (c), (8) (a) (intro.), r. (8) (b), am. (8) (c), (d), (e), (9) (a) (title), 2., 3., 4. a. to c., (b) 4., cr. (9) (b) 9., am. (10), (11) (a), cr. (11) (am), am. (11) (b), (c) 2., (d), (e), (f), (12) (a) (intro.), 3., r. and recr. (13), Register June 2020 No. 774, eff. 7-1-20; (6) (a) (title), (b) (title), (c) (title) created under s. 13.92 (4) (b) 2., Stats., correction in (2) (a) made under s. 13.92 (4) (b) 7., Stats., and correction in Table E (title), (6) (b) (intro.), (9) (a) 2. made under s. 35.17, Stats., Register June 2020 No. 774.
subch. V of ch. NR 812Subchapter V — Variances
NR 812.43NR 812.43Variances.
NR 812.43(1)(1)When strict compliance with the requirements of this chapter is not feasible, a variance may be requested. All variance requests shall be in writing, except for situations that may require an immediate response, in which case a variance may be requested verbally from the owner, or the owner’s agent, and a verbal variance may be granted by the department to be followed up with a written confirmation. If the verbal request is made by the owner’s agent, the agent shall provide confirmation of the owner’s concurrence with the request. A variance request shall include the names of the owner or owners and, if known, the well or heat exchange driller, well constructor or pump installer. The reason or reasons compliance with the requirements for this chapter is not feasible shall also be provided. The department may require the owner or the owner’s agent to submit additional information necessary for the department to determine if a variance is justified. The owner or owners or the owner’s agent shall sign the variance request. The department may condition the issuance of a variance by requiring additional construction or installation features to safeguard the groundwater and water supplied by the installation from contamination. Failure to comply with the conditions of a variance or the applicable requirements of this chapter voids the variance approval.
NR 812.43(1)(a)(a) A variance request to the separation distance specified in s. NR 812.08 Table A for an existing water supply well within 1,200 feet of a proposed landfill or landfill expansion, shall be signed and submitted to the department by the owner of the well or by the owner of the landfill. Both parties shall have the right to appeal the variance approval, pursuant to ch. 227, Stats.
NR 812.43(1)(a)1.1. If the application for a variance has been submitted by the landfill owner, the application shall include documentation that written notification of the variance request has been provided to any well owner meeting conditions under the separation distance specified in s. NR 812.08 Table A.
NR 812.43(1)(a)2.2. In cases where the application for a variance has been submitted by the well owner, the application shall include documentation that written notification of the variance request has been provided to the landfill owner.
NR 812.43(1)(b)(b) A variance request to the separation distance specified in s. NR 812.08 Table A for an existing water supply well within 1,200 feet of a landfill may be granted by the department where conditions warrant, using the concept of comparable protection. Comparable protection may be provided by appropriate measures including a deeper well casing depth setting, specific grouting materials or methods, specific drilling methodology or additional well water sampling results. These measures will be determined by the department for the purpose of safeguarding the groundwater and the water supply from potential sources of contamination.
NR 812.43(1)(c)(c) A variance request to the separation distance specified in s. NR 812.08 Table A for a well to be constructed within 1,200 feet of a landfill not subject to expansion shall be signed and submitted to the department by the owner of the well. If a variance is granted, the department shall notify the landfill owner. If the landfill owner is unknown, the department shall notify the municipality where the landfill is located.