NR 440.76(7)(b)2.2. Each startup, shutdown or malfunction may not last for longer than 3 hours.
NR 440.76(8)(8)Emission limits.
NR 440.76(8)(a)(a) What pollutants are regulated by this section? The following 11 pollutants, in 4 groupings, are regulated:
NR 440.76(8)(a)1.1. ‘Organics.’ Dioxins/furans.
NR 440.76(8)(a)2.2. ‘Metals.’
NR 440.76(8)(a)2.a.a. Cadmium.
NR 440.76(8)(a)2.b.b. Lead.
NR 440.76(8)(a)2.c.c. Mercury.
NR 440.76(8)(a)2.d.d. Opacity.
NR 440.76(8)(a)2.e.e. Particulate matter.
NR 440.76(8)(a)3.3. ‘Acid gases.’
NR 440.76(8)(a)3.a.a. Hydrogen chloride.
NR 440.76(8)(a)3.b.b. Nitrogen oxides.
NR 440.76(8)(a)3.c.c. Sulfur dioxide.
NR 440.76(8)(a)4.4. ‘Other.’
NR 440.76(8)(a)4.a.a. Carbon monoxide.
NR 440.76(8)(a)4.b.b. Fugitive ash.
NR 440.76(8)(b)(b) What emission limits must I meet and by when? You shall meet the emission limits specified in Tables 1 and 2 of this section. You shall meet the limits 60 days after your municipal waste combustion unit reaches the maximum load level but no later than 180 days after its initial startup.
NR 440.76(8)(c)(c) What happens to the emission limits during periods of startup, shutdown and malfunction?
NR 440.76(8)(c)1.1. The emission limits of this section apply at all times except during periods of municipal waste combustion unit startup, shutdown or malfunction.
NR 440.76(8)(c)2.2. Each startup, shutdown or malfunction may not last for longer than 3 hours.
NR 440.76(8)(c)3.3. A maximum of 3 hours of test data may be dismissed from compliance calculations during periods of startup, shutdown or malfunction.
NR 440.76(8)(c)4.4. During startup, shutdown or malfunction periods longer than 3 hours, emissions data cannot be discarded from compliance calculations and all provisions under s. NR 440.11 (4) apply.
NR 440.76(9)(9)Continuous emission monitoring.
NR 440.76(9)(a)(a) What types of continuous emission monitoring must I perform? To continuously monitor emissions, you shall perform the following 4 tasks:
NR 440.76(9)(a)1.1. Install continuous emission monitoring systems for certain gaseous pollutants.
NR 440.76(9)(a)2.2. Make sure your continuous emission monitoring systems are operating correctly.
NR 440.76(9)(a)3.3. Make sure you obtain the minimum amount of monitoring data.
NR 440.76(9)(a)4.4. Install a continuous opacity monitoring system.