NR 465.09(3)(d)(d) Method 3 in 40 CFR part 60, Appendix A, incorporated by reference in s. NR 484.04 (13), shall be used to analyze the exhaust gases.
NR 465.09(3)(e)(e) Method 4 in 40 CFR part 60, Appendix A, incorporated by reference in s. NR 484.04 (13), shall be used to measure the moisture in the stack gas.
NR 465.09(3)(f)(f) Methods 2, 2A, 2C, 2D, 3 and 4 in 40 CFR part 60, Appendix A, incorporated by reference in s. NR 484.04 (13), shall be performed, as applicable, at least twice during each test period.
NR 465.09(4)(4)An owner or operator of an affected source demonstrating compliance in accordance with s. NR 465.07 (1) (d) or (2) (b) shall perform a gaseous emission test using the following procedures:
NR 465.09(4)(a)(a) Construct the overall HAP emission reduction system so that all volumetric flow rates and total HAP emissions can be accurately determined by the applicable test methods specified in sub. (3).
NR 465.09(4)(b)(b) Determine capture efficiency from the affected emission points by capturing, venting and measuring all HAP emissions from the affected emission points. The owner or operator shall isolate affected emission points located in an area with other nonaffected gaseous emission sources from all other gaseous emission points and shall determine capture efficiency according to the following procedures as appropriate:
NR 465.09(4)(b)1.1. For temporary total enclosures, capture efficiency shall be determined according to Method 204, and as applicable, Methods 204A through 204F, in 40 CFR part 51, Appendix M, incorporated by reference in s. NR 484.04 (9).
NR 465.09(4)(b)2.2. For permanent total enclosures built around the affected emissions points, and where the building that houses the process is used as the enclosure, capture efficiency shall be assumed to be 100% when the requirements for a permanent total enclosure in Method 204, in 40 CFR part 51, Appendix M, incorporated by reference in s. NR 484.04 (9), are satisfied. Notwithstanding par. (e), when a permanent total enclosure is confirmed through Method 204, a value of one shall be used for N when determining R under sub. (5), (6), (7) or (8).
NR 465.09(4)(b)3.3. Use any alternative protocol and test method provided they meet either the requirements of the data quality objective (DQO) approach or the lower confidence level (LCL) approach in 40 CFR part 63, Subpart KK, Appendix A, incorporated by reference in s. NR 484.04 (24).
NR 465.09(4)(b)4.4. Shut down all nonaffected HAP emission points and continue to exhaust fugitive emissions from the affected emission points through any building ventilation system and other room exhausts such as drying ovens. All exhaust air shall be vented through stacks suitable for testing.
NR 465.09(4)(b)5.5. Use another methodology approved by the administrator provided it complies with the criteria for acceptance under Method 301 in 40 CFR part 63, Appendix A, incorporated by reference in s. NR 484.04 (25).
NR 465.09(4)(c)(c) Operate the control device with all affected emission points that will subsequently be delivered to the control device connected and operating at maximum production rate.
NR 465.09(4)(d)(d) Determine the efficiency (F) of the control device using the following equation:
å
å
å
-
(Equation 5)
NR 465.09(4)(e)(e) Determine the efficiency (N) of the capture system using the following equation:
å
å
å
(Equation 6)
NR 465.09(5)(5)For an owner or operator complying with s. NR 465.04 (1) (a) in accordance with s. NR 465.06 (1) (a) 3., compliance is demonstrated if the product of (F x N)(100) yields a value (R) such that the value of Eac in Equation 2 in s. NR 465.06 (1) (a) 3. is no greater than 1.0.
NR 465.09(6)(6)For an owner or operator complying s. NR 465.04 (2) (a) in accordance with s. NR 465.06 (2) (a) 3., compliance is demonstrated if the product of (F x N)(100) yields a value (R) such that the value of Eac in Equation 4 in s. NR 465.06 (2) (a) 3. is no greater than 0.8.
NR 465.09(7)(7)For an owner or operator complying with s. NR 465.04 (1) (b) 2. in accordance with s. NR 465.06 (1) (c) 2., compliance is demonstrated if the product of (F x N)(100) yields a value (R) such that the value of Gac in Equation 3 in s. NR 465.06 (1) (c) 2. is no greater than 1.0.
NR 465.09(8)(8)For an owner or operator complying with s. NR 465.04 (2) (b) in accordance with s. NR 465.06 (2) (b) 2., compliance is demonstrated if the product of (F x N)(100) yields a value (R) such that the value of Gac in Equation 3 s. NR 465.06 (1) (c) 2. is no greater than 0.2.
NR 465.09 HistoryHistory: CR 00-160: cr. Register August 2001 No. 548, eff. 9-1-01; reprinted to correct error in (4) (d) and (e), Register October 2001 No. 550.
NR 465.10NR 465.10Recordkeeping requirements.
NR 465.10(1)(1)The owner or operator of an affected source shall fulfill all recordkeeping requirements of s. NR 460.09 according to the applicability criteria in s. NR 465.01 (1) (e).
NR 465.10(2)(2)The owner or operator of an affected source subject to the emission limits in s. NR 465.04 shall maintain records of the following as appropriate:
NR 465.10(2)(a)(a) A certified product data sheet for each finishing material, thinner, contact adhesive and strippable spray booth coating subject to the emission limits in s. NR 465.04.
NR 465.10(2)(b)(b) The VHAP content, in kg VHAP/kg solids (lb VHAP/lb solids), as applied, of each finishing material and contact adhesive subject to the emission limits in s. NR 465.04.
NR 465.10(2)(c)(c) The VOC content, in kg VOC/kg solids (lb VOC/lb solids), as applied, of each strippable spray booth coating subject to the emission limits in s. NR 465.04 (1) (c) or (2) (c).
NR 465.10(3)(3)The owner or operator of an affected source following the compliance method in s. NR 465.06 (1) (a) 1. or (2) (a) 1. shall maintain copies of the averaging calculation for each month following the compliance date, as well as the data on the quantity of coatings and thinners used that is necessary to support the calculation of E in Equation 1 in s. NR 465.06 (1) (a) 1.
NR 465.10(4)(4)The owner or operator of an affected source following the compliance procedures of s. NR 465.07 (1) (c) 2. or 465.08 (1) (c) 2. shall maintain the records required by s. NR 465.10 (2) as well as records of all of the following:
NR 465.10(4)(a)(a) Solvent and coating additions to the continuous coater reservoir.
NR 465.10(4)(b)(b) Viscosity measurements.
NR 465.10(4)(c)(c) Data demonstrating that viscosity is an appropriate parameter for demonstrating compliance.
NR 465.10(5)(5)The owner or operator of an affected source subject to the work practice standards in s. NR 465.05 shall maintain onsite a work practice implementation plan and all records associated with fulfilling the requirements of that plan, including, but not limited to, all of the following:
NR 465.10(5)(a)(a) Records demonstrating that the operator training program required by s. NR 465.05 (2) is in place.
NR 465.10(5)(b)(b) Records collected in accordance with the inspection and maintenance plan required by s. NR 465.05 (3).
NR 465.10(5)(c)(c) Records associated with the cleaning solvent accounting system required by s. NR 465.05 (4).
NR 465.10(5)(d)(d) Records associated with the limitation on the use of conventional air spray guns showing total finishing material usage and the percentage of finishing materials applied with conventional air spray guns for each semiannual period as required by s. NR 465.05 (8) (e).
NR 465.10(5)(e)(e) Records associated with the formulation assessment plan required by s. NR 465.05 (12).
NR 465.10(5)(f)(f) Copies of documentation such as logs developed to demonstrate that the other provisions of the work practice implementation plan are followed.
NR 465.10(6)(6)The owner or operator of an affected source following the compliance method of s. NR 465.07 (1) (d) or 465.08 (1) (d) shall maintain copies of the calculations demonstrating that the overall control efficiency (R) of the control system results in the value of Eac required by Equation 2 in s. NR 465.06 (1) (a) 3. or Equation 4 in s. NR 465.06 (2) (a) 3., records of the operating parameter values, and copies of the semiannual compliance reports required by s. NR 465.105 (4).
NR 465.10(7)(7)The owner or operator of an affected source following the compliance method of s. NR 465.07 (2) (b) or 465.08 (2) (b) shall maintain copies of the calculations demonstrating that the overall control efficiency (R) of the control system results in the applicable value of Gac calculated using Equation 3 in s. NR 465.06 (1) (c) 2., records of the operating parameter values, and copies of the semiannual compliance reports required by s. NR 465.105 (4).
NR 465.10(8)(8)The owner or operator of an affected source subject to the emission limits in s. NR 465.04 and following the compliance provisions of s. NR 465.07 (1) (a) to (c), (2) (a), (3) or (4) or 465.08 (1) (a) to (c), (2) (a), (3) or (4) shall maintain records of the compliance certifications submitted in accordance with s. NR 465.105 (3) for each semiannual period following the compliance date.
NR 465.10(9)(9)The owner or operator of an affected source shall maintain records of all other information submitted with the compliance status report required by ss. NR 460.08 (8) and 465.105 (2) and the semiannual reports required by s. NR 465.105 (3).
NR 465.10(10)(10)The owner or operator of an affected source shall maintain all records in accordance with the requirements of s. NR 460.09 (2) (a).
NR 465.10 HistoryHistory: CR 00-160: cr. Register August 2001 No. 548, eff. 9-1-01.
NR 465.105NR 465.105Reporting requirements.
NR 465.105(1)(1)The owner or operator of an affected source subject to this subchapter shall fulfill all reporting requirements of ss. NR 460.06 to 460.09 according to the applicability criteria in s. NR 465.01 (1) (e).
NR 465.105(2)(2)The owner or operator of an affected source demonstrating compliance in accordance with s. NR 465.07 (1) (a) to (c), (2) (a), (3) or (4) shall submit the compliance status report required by s. NR 460.08 (8) no later than 60 days after the compliance date. The report shall include the information required by s. NR 465.07 (1) (a) to (c), (2) (a), (3) or (4).
NR 465.105(3)(3)The owner or operator of an affected source demonstrating compliance in accordance with s. NR 465.08 (1) (a) to (c), (2) (a), (3) or (4) shall submit a report covering the previous 6 months of wood furniture manufacturing operations as follows:
NR 465.105(3)(a)(a) The first report shall be submitted no later than 30 calendar days after the end of the first 6-month period following the compliance date.
NR 465.105(3)(b)(b) Subsequent reports shall be submitted no later than 30 calendar days after the end of each 6-month period following the first report.
NR 465.105(3)(c)(c) The semiannual reports shall include the information required by s. NR 465.08 (1) (a) to (c), (2) (a), (3) and (4), a compliance certification stating whether the affected source was in compliance or noncompliance, and, if the affected source was in noncompliance, the measures taken to bring the affected source into compliance. The compliance certification shall be signed by a responsible official of the company that owns or operates the affected source.
NR 465.105(4)(4)The owner or operator of an affected source demonstrating compliance in accordance with s. NR 465.08 (1) (d) or (2) (b) shall submit the excess emissions and continuous monitoring system performance report and summary report required by s. NR 460.09 (5). The report shall include the monitored operating parameter values required by s. NR 465.08 (1) (d) or (2) (b). If the source experiences excess emissions, the report shall be submitted quarterly for at least one year after the excess emissions occur and until a request to reduce reporting frequency is approved, as indicated in s. NR 460.09 (5) (c) 2. If no excess emissions occur, the report shall be submitted semiannually.
NR 465.105(5)(5)The owner or operator of an affected source required to provide a written notification under s. NR 465.05 (12) (b) shall include in the notification one or more statements that explains the reasons for the usage increase. The notification shall be submitted no later than 30 calendar days after the end of the annual period in which the usage increase occurred.
NR 465.105 HistoryHistory: CR 00-160: cr. Register August 2001 No. 548, eff. 9-1-01; Correction in (4) made under s. 13.93 (2m) (b) 7. Stats., Register March 2004 No. 579; CR 03-037: renum. NR 465.11 to be NR 465.105 and am. (1) Register March 2004 No. 579, eff. 4-1-04.
aIncludes mono- and di-ethers of ethylene glycol, diethylene glycols and triethylene glycol; R-(OCH2CH2)n-OR’ where:
n = 1, 2 or 3
R = alkyl or aryl groups
R’ = R, H, or groups which, when removed, yield glycol ethers with the structure: R-(OCH2CH2)n-OH. Polymers are excluded from the glycol category.
bIncludes organic compounds with more than one benzene ring, and which have a boiling point greater than or equal to 100 °C.
subch. III of ch. NR 465Subchapter III — Surface Coating of Large Appliances
NR 465.21NR 465.21What this subchapter covers.
NR 465.21(1)(1)What is the purpose of this subchapter?. This subchapter establishes national emission standards for hazardous air pollutants for large appliance surface coating facilities. This subchapter also establishes requirements to demonstrate initial and continuous compliance with the emission limitations.
NR 465.21 NoteNote: This subchapter is based on the federal regulations contained in 40 CFR part 63 Subpart NNNN, created July 23, 2002.
NR 465.21(2)(2)Am I subject to this subchapter?.
NR 465.21(2)(a)(a) You are subject to this subchapter if you own or operate a facility that applies coatings to large appliance parts or products, and is a major source, is located at a major source or is part of a major source of emissions of hazardous air pollutants (HAP), except as provided in par. (d). A major source of HAP emissions is any stationary source or group of stationary sources located within a contiguous area and under common control that emits or has the potential to emit any single HAP at a rate of 9.07 Mg (10 tons) or more per year or any combination of HAP at a rate of 22.68 Mg (25 tons) or more per year. You are not subject to this subchapter if your large appliance surface coating facility is located at, or is part of, an area source of HAP emissions. An area source of HAP emissions is any stationary source or group of stationary sources located within a contiguous area and under common control that is not a major source.
NR 465.21(2)(b)(b) The large appliance surface coating source category includes any facility engaged in the surface coating of a large appliance part or product. Large appliance parts and products include cooking equipment; refrigerators, freezers, and refrigerated cabinets and cases; laundry equipment; dishwashers, trash compactors, and water heaters; and heating, ventilation and air-conditioning (HVAC) units, air-conditioning units except those in motor vehicles, air-conditioning and heating combination units, comfort furnaces, and electric heat pumps. Specifically excluded are heat transfer coils and large commercial and industrial chillers.
NR 465.21(2)(c)(c) The large appliance surface coating activities and equipment to which this subchapter applies are all of the following:
NR 465.21(2)(c)1.1. Surface preparation of large appliance parts and products.
NR 465.21(2)(c)2.2. Preparation of a coating for application, e.g., mixing in thinners and other components.
NR 465.21(2)(c)3.3. Application of a coating to large appliance parts and products using, for example, spray guns or dip tanks.
NR 465.21(2)(c)4.4. Application of porcelain enamel, powder coating and asphalt interior soundproofing coating.
NR 465.21(2)(c)5.5. Flash-off, drying or curing following the coating application operation.
NR 465.21(2)(c)6.6. Cleaning of equipment used in coating operations, e.g., application equipment, hangers and racks.
NR 465.21(2)(c)7.7. Storage of coatings, thinners and cleaning materials.
NR 465.21(2)(c)8.8. Conveying of coatings, thinners and cleaning materials from storage areas to mixing areas or coating application areas, either manually such as in buckets or by automated means such as by transfer through pipes using pumps.
NR 465.21(2)(c)9.9. Handling and conveying of waste materials generated by coating operations.
NR 465.21(2)(d)(d) This subchapter does not apply to any of the following:
NR 465.21(2)(d)1.1. The surface coating of large appliance parts such as metal or plastic handles, hinges or fasteners that have a wider use beyond large appliances.
NR 465.21(2)(d)2.2. The surface coating of large appliances conducted for the purpose of repairing or maintaining large appliances used by a facility and not for commerce unless organic HAP emissions from the surface coating itself are as high as the rates specified in par. (a).
NR 465.21(2)(d)3.3. The surface coating of heat transfer coils or large commercial and industrial chillers.
NR 465.21(2)(d)4.4. Research or laboratory facilities; janitorial, building, and facility maintenance operations; hobby shops operated for noncommercial purposes or coating applications using hand-held non-refillable aerosol containers.
NR 465.21(2)(d)5.5. Processes involving metal plating or phosphating of a substrate.
NR 465.21(2)(e)(e) If you own or operate an affected source that is subject to this subchapter and at the same affected source you also perform surface coating subject to any other national emission standards for hazardous air pollutants (NESHAP), you may choose for the affected source to comply with only one NESHAP. In order to choose this alternative, the total mass of organic HAP emissions from all surface coating operations in the affected source shall be less than or equal to the total mass of organic HAP emissions that would result if it complied separately with all applicable NESHAP. You shall make this comparison for the initial compliance period and report it in the notification of compliance status as required in s. NR 465.25 (1) (b) 10. and in the notification of compliance status required by the other NESHAP. If you choose this alternative, your demonstration of compliance with the other NESHAP constitutes compliance with this subchapter.
NR 465.21(3)(3)What parts of my plant does this subchapter cover?.
NR 465.21(3)(a)(a) This subchapter applies to each new, reconstructed and existing affected source.
NR 465.21(3)(b)(b) The affected source is the collection of all of the following items that are part of the large appliance surface coating facility:
Loading...