SPS 327.24(5) (5) A ceiling height of less than 7 feet may be provided between the rear rim of a bathtub and a wall of the room abutting that rim, or between the side rim and a room wall abutting that rim.
SPS 327.24(6) (6) A ceiling height of less than 7 feet may be provided between the rear wall of a shower stall and a wall of the room abutting that rear wall, or between the side wall of a shower and a room wall abutting that side wall.
SPS 327.24(7) (7) A ceiling height of less than 7 feet may be provided in a loft used as a habitable room.
SPS 327.24 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.25 SPS 327.25Fireblocking.
SPS 327.25(1) (1)Fireblocking locations. Fireblocking shall be provided in all of the following locations:
SPS 327.25(1)(a) (a) In concealed spaces of walls and partitions, including furred spaces, at the ceiling and floor levels.
SPS 327.25(1)(b) (b) At all interconnections between concealed vertical and horizontal spaces including the attachment between a carport and a camping unit.
SPS 327.25(1)(c) (c) In concealed spaces between stair stringers at the top and bottom of the run and at any intervening floor level.
SPS 327.25(1)(d) (d) At all openings around wires, cables, vents, pipes, ducts, chimneys, and fireplaces at ceiling and floor level.
SPS 327.25(2) (2)Fireblocking materials. Fireblocking shall consist of one of the following:
SPS 327.25(2)(a) (a) 2-inch nominal lumber.
SPS 327.25(2)(b) (b) Two layers of one-inch nominal lumber.
SPS 327.25(2)(c) (c) One thickness of 3/4-inch nominal plywood or wood structural panel with any joints backed with the same material.
SPS 327.25(2)(d) (d) One thickness of 1/2-inch gypsum wallboard, face nailed or face screwed to solid wood, with any joints backed with the same material.
SPS 327.25(2)(e) (e) Fiberglass or mineral wool batt insulation may be used if both of the following conditions are met:
SPS 327.25(2)(e)1. 1. The least dimension of the opening may not exceed 4 inches.
SPS 327.25(2)(e)2. 2. The batt shall be installed to fill the entire thickness of the opening or stud cavity.
SPS 327.25(2)(f) (f) For wires, cables, pipes, and vents only, non-shrinking caulk, putty mortar, or similar material may be used provided no dimension of the opening exceeds 1/2 inch around the penetrating object.
SPS 327.25(2)(g) (g) For chimneys, fireplaces, and metal vents, fireblocking shall be metal, cement board, or other noncombustible material.
SPS 327.25 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.26 SPS 327.26Smoke detectors.
SPS 327.26(1) (1) A listed and labeled battery-operated smoke alarm shall be installed in all of the following locations:
SPS 327.26(1)(a) (a) If a camping unit has a loft, an alarm shall be installed inside the loft. An alarm is not required to be installed outside of the loft.
SPS 327.26(1)(b) (b) On a floor level that contains one or more sleeping rooms, an alarm shall be installed inside each sleeping room and an alarm shall be installed outside of the sleeping rooms.
SPS 327.26(1)(c) (c) An alarm shall be installed on a floor level that does not contain a sleeping room.
SPS 327.26 Note Note: Section 101.645 (3), Stats., requires the owner of a dwelling to install a functional smoke detector in the basement of the dwelling and on each floor level except the attic or storage area of each dwelling unit. The occupant of such a dwelling unit shall maintain any smoke detector in that unit, except that if any occupant who is not the owner, or any state, county, city, village or town officer, agent or employee charged under statute or municipal ordinance with powers or duties involving inspection of real or personal property, gives written notice to the owner that the smoke detector is not functional the owner shall provide, within 5 days after receipt of that notice, any maintenance necessary to make that smoke detector functional.
SPS 327.26(2) (2) Smoke alarms and detectors shall be installed and maintained in accordance with the manufacturer's specifications. Interconnection of smoke alarms and detectors is not required.
SPS 327.26 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.27 SPS 327.27Carbon monoxide alarms.
SPS 327.27(1) (1)General. A listed and labeled carbon monoxide alarm shall be installed within 10 feet of a fireplace or fuel-burning appliance.
SPS 327.27(2) (2)Electrical service. If electrical service for a camping unit is provided by a public utility, a carbon monoxide alarm required under sub. (1) shall be continuously powered by the camping unit electrical service and shall have a backup battery power supply.
SPS 327.27 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.28 SPS 327.28Protection against decay and termites.
SPS 327.28(1)(1) Wood used in any of the applications under this section shall meet all of the following requirements:
SPS 327.28(1)(a) (a) The wood shall be labeled and pressure treated with preservative in accordance with an AWPA standard or shall be naturally durable and decay-resistant or shall be engineered to be decay resistant.
SPS 327.28(1)(b) (b) The wood shall be pressure treated with preservative or shall be naturally termite-resistant unless additional steps are taken to make the wood termite-resistant.
SPS 327.28(2) (2) Wood used in the following locations shall be as required under sub. (1):
SPS 327.28(2)(a) (a) Resting directly upon or embedded in earth.
SPS 327.28(2)(b) (b) Floor joists or sleepers that meet all of the following conditions:
SPS 327.28(2)(b)1. 1. The joists or sleepers are protected from the weather.
SPS 327.28(2)(b)2. 2. The joists or sleepers are within 18 inches above a lower floor surface, deck or soil.
SPS 327.28(2)(c) (c) Floor joists exterior to the camping unit that are within 18 inches above exterior grade, unless protected with a moisture barrier.
SPS 327.28 Note Note: Acceptable moisture barriers for this application include 3/4 -inch exterior preservative-treated plywood, or ice dam protection material listed as meeting the requirements of ASTM D 1970 or vapor retarder material, provided they are protected from physical and UV light damage.
SPS 327.28(2)(d) (d) Girders that span directly over and within 12 inches of earth.
SPS 327.28(2)(e) (e) Sills and rim joists that rest on concrete or masonry and are also below grade or within 8 inches above final exterior grade.
SPS 327.28(2)(f)1.1. Siding and sheathing in contact with concrete, masonry, or earth and within 6 inches above final exterior grade.
SPS 327.28(2)(f)2. 2. Siding and sheathing in contact with concrete or masonry and within 2 inches above an impervious surface.
SPS 327.28(2)(g) (g) Ends of wood structural members and their shims resting on or supported in masonry or concrete walls and having clearances of less than 1/2 inch on the top, sides, and ends.
SPS 327.28(2)(h) (h) Bottom plates or sole plates of walls that rest on concrete or masonry and that are below exterior grade or less than 8 inches above final exterior grade.
SPS 327.28(2)(i) (i) Columns in direct contact with concrete or masonry unless supported by a structural pedestal or plinth block at least one inch above the floor.
SPS 327.28(2)(j) (j) Any structural part of an outdoor deck, including the decking.
SPS 327.28(2)(k) (k) Permanent wood foundations.
SPS 327.28(3) (3) Wood girders that rest directly on exterior concrete or masonry shall be protected by one of the following methods:
SPS 327.28(3)(a) (a) The wood shall be pressure treated with preservative or shall be a naturally durable and decay-resistant species.
SPS 327.28(3)(b) (b) Material, such as pressure-treated plywood, flashing material, steel shims, or water-resistant membrane material shall be placed between the wood and the concrete or masonry.
SPS 327.28(4) (4) All pressure-treated wood and plywood shall be identified by a quality mark or certificate of inspection of an approved inspection agency which maintains continued supervision, testing, and inspection over the quality of the product.
SPS 327.28 Note Note: Heartwood of redwood, cypress, black walnut, catalpa, chestnut, sage orange, red mulberry, white oak, or cedar lumber are considered by the department to be naturally decay-resistant. Heartwood of bald cypress, redwood, and eastern red cedar are considered by the department to be naturally termite resistant.
SPS 327.28(5)(a)(a) Fasteners for pressure-preservative treated wood and fire-retardant-treated wood shall meet one of the following requirements:
SPS 327.28(5)(a)1. 1. The fastener is a steel bolt with a diameter of 1/2 inch or greater.
SPS 327.28(5)(a)2. 2. The fastener is made of stainless steel.
SPS 327.28(5)(a)3. 3. The fastener is made of hot-dipped, zinc-galvanized steel with the coating weight and thickness labeled as complying with ASTM A 153.
SPS 327.28(5)(a)4. 4. The fastener is made of steel with a mechanically-deposited zinc coating labeled as complying with ASTM B 695, Class 55 or greater.
SPS 327.28(5)(a)5. 5. The fastener has coating types and weights in accordance with the fastener manufacturer's recommendations. In the absence of the manufacturer's recommendations subd. 1., 2., 3., or 4. shall apply.
SPS 327.28 Note Note: “Zinc plated," “zinc coated," “chrome plated," etc., fasteners do not necessarily comply with either of these standards.
SPS 327.28(5)(b) (b) When a fastener is used with a hanger or other metal fixture, the fastener shall be of the same material as the hanger or metal fixture.
SPS 327.28 Note Note: When separate pieces are in close contact, zinc corrodes rapidly in the presence of plain steel. Zinc corrodes much more rapidly in the presence of stainless steel.
SPS 327.28(5)(c) (c) For the purposes of this section, a fastener includes nails, screws, and bolts with nuts and washers.
SPS 327.28 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.29 SPS 327.29Floor design. Floors shall support all dead loads plus the minimum unit live loads as set forth in s. SPS 327.20. The live loads shall be applied to act vertically and uniformly to each square foot of horizontal floor area.
SPS 327.29 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.30 SPS 327.30Wood floors in contact with the ground. Wood floors in contact with the ground shall be designed and constructed in accordance with the wood-foundation standards adopted in Table 327.19-2.
SPS 327.30 History History: EmR1703: emerg. cr., eff. 2-6-17; CR 17-017: cr. Register March 2018 No. 747, eff. 4-1-18.
SPS 327.31 SPS 327.31Wood frame floors. Unless designed through structural analysis, wood frame floors shall comply with the following requirements:
SPS 327.31(1) (1)Floor joists.
SPS 327.31(1)(a)(a) Floor joists shall comply with the structural requirements and live load determination under s. SPS 327.20.
SPS 327.31(1)(b) (b) Where the joists of a floor system are parallel to, and located between bearing walls above and below, the joists shall be doubled.
SPS 327.31(2) (2)Floor trusses. Metal plate connected wood floor trusses shall be designed in accordance with the Design Specifications for Metal Plate Connected Parallel Chord Wood Trusses and the National Design Specification for Wood Construction. Truss members shall not be cut, bored or notched.
SPS 327.31(3) (3)Girders and beams.
SPS 327.31(3)(a)(a) Wood girders and beams shall be fitted at the post or column. Adjoining ends shall be fastened to each other to transfer horizontal loads across the joint. Beams shall also be fastened to the posts with framing anchors, angle clips, or equivalent.
SPS 327.31(3)(b) (b) Where intermediate beams are used, they shall rest on top of the girders; or shall be supported by ledgers or blocks fastened to the sides of the girders; or they may be supported by approved metal hangers into which the ends of the beams shall be fitted.
SPS 327.31(3)(c) (c) Lateral restraint for all wood beams shall be provided at all columns using a saddle or other approved connection where the beam meets one of the following conditions:
SPS 327.31(3)(c)1. 1. The beam is not restrained at both ends.
SPS 327.31(3)(c)2. 2. The beam is more than 11 1/4 inches deep using actual measurement.
SPS 327.31 Note Note: A saddle supports the beam on the bottom and allows for the through-connection of fasteners into the side of the beam.
SPS 327.31(4) (4)Bearing and end configuration.
SPS 327.31(4)(a)(a) Sawn lumber.
Loading...
Loading...