4. The fuel piping, tubing, or hose system connecting the tank to the engine shall comply with all of the following:
a. Be compatible with the fuel.
b. Be constructed, supported, and protected against physical damage and stresses arising from impact, settlement, vibration, expansion, contraction, wave action, and wildlife.
c. Be of a type that is designed to withstand the forces and pressures exerted upon it, including from any motion of the engine or a pier.
d. Be liquid-tight.
e. Have a valve at the tank to shut off the liquid supply from the tank.
(3)Tanks of less than 1,100 gallons.
(a) Aboveground tanks that have a capacity of less than 1,100 gallons shall comply with this subsection before use.
(b) Installation shall be by a certified installer.
(c) The certified installer shall fill out a tank installation notification, form TR-WM-124, and provide the form to the authorized agent or the department for inspection of the tank system.
Note: Form TR-WM-124 — Farm & Construction AST Installation Notification is available from the Bureau of Weights and Measures, PO Box 8911, Madison, WI 53708-8911, or at telephone (608) 224-4942, or from the Bureau’s Web site at http://datcp.wi.gov/Consumer/Hazardous_Materials_Storage_Tanks/Hazardous_Materials_Storage_Tank_Forms/index.aspx.
(d) Before a tank may be filled or used, the tank system shall be inspected or authorized for use by the authorized agent or the department, except as allowed otherwise by par. (g).
(e) The owner shall remit the inspection fee under Table 93.1605 to the authorized agent or the department before filling or using the tank.
(f) The tank shall be inspected within 5 business days after notification for a standard inspection and within 2 business days after notification for a priority inspection, except as provided in par. (g).
(g) The tank may be filled and used if the inspection has not been completed within the time limits after notification specified in par. (f).
(h) Tanks that are filled via hand-held nozzles shall be constantly attended during product delivery and shall be provided with overfill prevention equipment which notifies the person filling the tank, with either an audible or a visual signal, that the liquid level has reached 90 percent of the tank’s capacity.
1. Tanks shall be mounted on noncombustible supports that are adequate to provide stability.
2. The base of the tank supports shall be at the same grade level as the vehicles when positioned for fueling.
3. The bottom of the tank, irrespective of any supports, shall be elevated at least 6 inches above the surrounding grade.
(4)Tanks of 1,100 gallons or more, or located less than 40 feet from buildings. Aboveground tanks which have a capacity of 1,100 gallons or more, or which are located less than 40 feet from either the buildings and structures listed in sub. (2) (a) or important buildings or structures, shall comply with all of the following:
(a) Tank listing. The tank shall be listed and labeled for aboveground use.
(b) System design and location. The tank system shall comply with the specifications for dispensing facilities in s. ATCP 93.615 (5), with the following exceptions:
1. The tank system and the fueling operation shall be located in accordance with Table 93.630.
2. Vehicle collision protection may be omitted where a dike complying with this chapter is provided for secondary containment.
3. Tanks under this paragraph are exempt from the enclosure requirement in s. ATCP 93.615 (5) (o).
Table 93.630
Tank System Setbacks for Tanks with Secondary Containment
(c) Administrative requirements.
1. The tank system shall be installed in accordance with the manufacturer’s instructions, the applicable national standards adopted in s. ATCP 93.200, plans and specifications approved under s. ATCP 93.100 and this chapter.
2. The tank system installation shall be performed or supervised by a certified installer.
3. The tank system shall be inspected in accordance with s. ATCP 93.115 (2).
4. The tank shall be registered in accordance with s. ATCP 93.140.
History: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19; correction in (3) (h) made under s. 35.17, Stats., Register October 2019 No. 766.
ATCP 93.640Watercraft, snowmobile and ATV fueling.
(1)General requirements.
(a) General. Use of aboveground storage tank systems and fueling operations for watercraft, snowmobiles, and ATVs shall comply with NFPA 30A chapter 11, the requirements for dispensing systems in s. ATCP 93.615, and the requirements of this section, except as otherwise approved under this chapter.
(b) Tank location.
1. Aboveground tanks located on land shall be set back at least 10 feet from the ordinary high water mark of a navigable body of water.
Note: The ordinary high water mark is determined by the county zoning department or the department of natural resources.
Note: The municipality in which the tank is located may have additional requirements for the siting of the tank.
2. Tanks shall follow the setback requirements of Table 93.615-A, except that there is no required separation between the tank and the dispenser if the tank is used exclusively for watercraft, snowmobile, or ATV fueling.
(c) Tank appurtenances.
1. Any dispenser used for a fueling operation above or within 100 feet of navigable water shall use a dry-break connection or a listed no-drip nozzle with automatic shutoff.
2. A nozzle latch-open device may not be installed or used above or within 100 feet of navigable water.
(d) Hose. Hose lengths more than 18 feet long, used for dispensing fuel, shall be reeled, racked, or otherwise protected from damage.
(2)Public access watercraft fueling. All piping systems and tank systems that are installed on or after November 1, 2019, for watercraft beyond the scope of sub. (4) shall comply with PEI RP1000 and sub. (3).
Note: See s. ATCP 93.400 (3) for requirements relating to secondary containment for any underground piping, including any transition between aboveground and underground piping.
(3)Seasonal installation of a fueling system on a pier.
(a) Plan requirements. Before installing a fueling system on a pier, plans shall be submitted for review and shall specify the requirements of this subsection.
(b) Pipe and tank requirements.
1. All connections that are broken shall use dry-break couplings listed for use with petroleum products.
2. Broken connections shall be plugged during storage.
3. The tank vent shall be left open.
(c) Management plan.
1. The owner shall develop and maintain on-site a written plan for safely draining the tank and pipe system before disassembly.
2. The disassembly plan under subd. 1. shall also be submitted with the plans for a proposed system that are required under s. ATCP 93.100.
(4)Residential watercraft fueling operations.
(a) Aboveground tanks for watercraft fueling for noncommercial purposes at a private residence shall comply with the requirements for aboveground tanks in ss. ATCP 93.400 to 93.420, and this subsection.
(b) No more than 2 tanks are allowed at any residence.
(c) Tanks shall be listed and may not exceed 600 gallons in aggregate capacity.
(d) The tank shall be used only by the residents of the property for fueling their watercraft or for maintenance of their property.
1. The tank shall be located outdoors, on land, at least 25 feet from the dwelling and other important buildings, and at least 10 feet from the ordinary high water mark of a navigable waterway, public roadway, or property line.
2. All setbacks shall be measured from the inside of the dike wall to the dwelling, important building, ordinary high water mark, public roadway, or property line.
(f) A means shall be provided to prevent the discharge of liquid due to a siphoning effect. Gravity dispensing systems may not be used.
(g) Transfer of product shall be from a tank by means of an approved, fixed, fuel dispensing hand pump, or a listed, fixed, electrical pump.
(5)Emergency fueling from a tank vehicle. Where fixed dispensing facilities are not available, dispensing of Class I or II liquids directly from a tank vehicle into permanently installed fuel tanks of self-propelled watercraft shall be permitted for emergency fueling, provided the operation is in accordance with the requirements for tank vehicles in s. ATCP 93.610 (3).
(6)Snowmobile and atv fueling.
(a) General. Tank systems used for fueling snowmobiles or ATVs shall meet the requirements for dispensing systems in s. ATCP 93.615.
(b) Tank location. Tank systems adjacent to a body of water shall also follow the requirements for watercraft fueling.
(c) Collision protection.
1. Aboveground tank systems used for snowmobile and ATV fueling shall be provided with collision protection.
2. The collision protection shall be spaced no more than 30 inches on center.
3. If the fueling area is adjacent to vehicle traffic or a parking area, bollards or equivalent protection shall be placed to separate the snowmobile or ATV fueling area from motor vehicle traffic.
History: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19; correction in (3) (c) 1., (4) (e) 1. made under s. 35.17, Stats., and correction in (2), (6) (a) made under s. 13.92 (4) (b) 7., Stats., Register October 2019.
ATCP 93.650Aircraft fuel dispensing.
(1)General requirements. Fueling operations for aircraft shall follow the requirements in s. ATCP 93.610 (3) or 93.615, NFPA 407, NFPA 418, and this section.
(2)Setbacks.
(a) Aboveground tanks used for public access fueling shall be at least 30 feet from the point of fuel transfer into the aircraft.
(b) Aboveground tank setbacks from buildings, public ways, and property lines shall follow the requirements in Table 93.615-B.
1. The point of fuel transfer into the aircraft, from any tank or truck supply source, shall be at least 100 feet from public traffic or assembly areas at public events, unless a reduced distance is authorized by the fire chief.
2. The public events referred to in subd. 1. do not include passenger terminals, fixed base operators, or persons entering or exiting the aircraft.
(3)Collision protection.
(a) Barriers shall be provided to protect tanks, pumps, dispensers, and vents from collision damage from aircraft or other vehicles in accordance with s. ATCP 93.430.
(b) Where subject to collision from aircraft, barriers protecting an aboveground tank shall be located at all four corners of the storage tank system and extend at least 12 inches above the top of the tank.
(4)Product identification.